![Samson TROVIS 5474 Скачать руководство пользователя страница 92](http://html1.mh-extra.com/html/samson/trovis-5474/trovis-5474_mounting-and-operating-instructions_4048411092.webp)
Co9: Modbus/meter bus
Fb Function
SZ WE Function block parameter
/ Range of values (default setting)
00 Modbus
ON Co9 -> Fb00 = ON: Modbus active
only with Co9 -> Fb06 = OFF and Co9 -> Fb10 = OFF
01 Modem function
OFF Co9 -> Fb01 = ON: Modem function active
02 Modem dialing
procedure
OFF Co9 -> Fb02 = ON: Pulse
Co9 -> Fb02 = OFF: Tone
03 Lock dial-up
OFF Co9 -> Fb03 = ON: No dial-up in case an error
Co9 -> Fb03 = OFF: Dial-up in case an error
04 Modbus
16-bit addressing
OFF Co9 -> Fb04 = ON: 16-bit addressing
Co9 -> Fb04 = OFF: 8-bit addressing
05 Reserved
06 Text message alarm
to a mobile phone
OFF Co9 -> Fb06 = ON: Text message alarm to a mobile phone
only with Co9 -> Fb00 = OFF and Co9 -> Fb10 = OFF
07 SMS dialing
procedure
OFF Co9 -> Fb07 = ON: Pulse
Co9 -> Fb07 = OFF: Tone
08 Reserved
09 Reserved
10 Alarm sent per fax
OFF Co9 -> Fb10 = ON: Alarm sent per fax
only with Co9 -> Fb00 = OFF and Co9 -> Fb06 = OFF
11 Fax dialing
procedure
OFF Co9 -> Fb11 = ON: Pulse
Co9 -> Fb11 = OFF: Tone
21
to
23
Meter 1
to
Meter 3
OFF Co9 -> Fb21 = ON: Meter 1 is being processed
to
Co9 -> Fb23 = ON: Meter 3 is being processed
Function block parameters:
Meter bus address for WMZ / 0 to 255 (255)
Model code WMZ / P15, PS2,1434, CAL3, APAtO, SLS (1434)
Reading mode WMZ / 24h, con, CoiL (con)
Fb = Function block, WE = Default setting, SZ = Key number
92
EB 5474 EN
Appendix
Содержание TROVIS 5474
Страница 79: ...System Anl 3 System Anl 4 EB 5474 EN 79 Electrical connection...
Страница 80: ...System Anl 5 System Anl 6 80 EB 5474 EN Electrical connection...
Страница 127: ...EB 5474 EN 127 Index Key number 1732...
Страница 129: ...EB 5474 EN 129...
Страница 130: ...130 EB 5474 EN...