![Samson TROVIS 5474 Скачать руководство пользователя страница 116](http://html1.mh-extra.com/html/samson/trovis-5474/trovis-5474_mounting-and-operating-instructions_4048411116.webp)
13.5 Technical data
Inputs
Sensor inputs and
binary inputs
Max. 17 configurable inputs for sensors (Pt 100, Pt 1000, Ni 200, Ni
1000, PTC, NTC or 0-20 mA, 4-20 mA) or binary alarms
Other inputs
2 analog inputs 0-10 V, R
i
= 18 k
Ω
Outputs
Control signal y
Three-step signals: Load 250 V~, 2 AC
On-off signals: Load 250 V~, 2 AC
Continuous control signal: 0 to 10 V, permissible load > 4.7 k
Ω
Binary outputs
6 outputs to control pumps and valves,
load max. 250 V~, 2 AC
2 outputs for alarms,
load max. 50 V~, 100 mA
Interfaces
Serial RS-232 interface for connection of a modem;
interface for meter bus
Operating voltage
230 V, 48 to 62 Hz, output 8 VA
Ambient temperature
Permissible: 0 to 40 °C · Storage: –20 to 60 °C
Degree of protection
IP 40 according to IEC 529
Class of protection
II according to VDE 0106
Degree of contamination 2 according to VDE 0110
Overvoltage category
II according to VDE 0110
Humidity rating
F according to VDE 40040
Noise immunity
According to EN 61000-6-1
Noise emission
According to EN 61000-6-3
Weight
Approx. 0.6 kg
116