Fb Function
WE
Anl
Function block parameter
/ Range of values (default setting)
06 Three-step pulsing/
on-off signal RüL-RK1
ON 1 to 7 Co1 -> Fb06 = ON, only with Co1 -> Fb05 = OFF:
Three-step signal
Co1 -> Fb06 = OFF: On-off signal
Function block parameters
Hysteresis / 1 to 30 °C (5°C)
Min. activation time / 0 to 600 s (120 s)
Min. deactivation time / 0 to 600 s (120 s)
07 Modulation feedback
K1
ON 3, 6, 7 Co1 -> Fb07 = ON: External feedback; the actually measured
resistance data are given
Function block parameters
Lower value (Start) = 0 % Modulation (0 = 1 k
Ω
)
Upper value (Stop) = 100 % Modulation (1000 = 2 k
Ω
)
Co1 -> Fb07 = OFF: Internal feedback
Function block parameters:
K
P
(proportional gain) / 0.1 to 99.9 (2)
T
N
(reset time) / 0 to 999 s (30 s)
T
V
(derivative-action time) / 0 to 999 s (0 s)
T
Y
(Modulation transit time) / 5 to 240 s (30 s)*
* Only when Co1 -> Fb05 = ON is also configured
Fb = Function block, WE = Default setting
EB 5474 EN
83