PA1: Boiler 1
(systems Anl 1 to 7)
PA2: Boiler 2
(systems Anl 4 to 7)
Parameters
PA1
PA2
Range of values
Maximum flow temperature
20 to 160 °C
Minimum return flow temperature
20 to 120 °C
Minimum activation time
0 to 90 min
Minimum deactivation time
0 to 90 min
Function block parameters (Co1/Co2):
Start-up time for boiler (Fb01 = OFF)
0 to 5400 s
K
P
(proportional gain)
(Fb05 = ON/OFF)
0.1 to 99.9
T
N
(reset time) (Fb05 = ON/OFF)
0 to 999 s
T
V
(derivative-action time)
(Fb05 = ON/OFF)
0 to 999 s
K
P
(proportional gain) (Fb06 = ON)
0.1 to 99.9
T
N
(reset time) (Fb06 = ON)
0 to 999 s
T
V
(derivative-action time)
(Fb06 = ON)
0 to 999 s
T
Y
(valve transit time) (Fb06 = ON)
5 to 240 s
Hysteresis (Fb06 = OFF)
0 to 30 °C
Min. activation time (Fb06 = OFF)
0 to 600 s
Min. deactivation time (Fb06 = OFF)
0 to 600 s
K
P
(proportional gain) (Fb07 = OFF)
0.1 to 99.9
T
N
(reset time) (Fb07 = OFF)
0 to 999 s
Start (lower value) (Fb07 = ON)
0 to 1000
Stop (upper value) (Fb07 = ON)
0 to 1000
T
V
(derivative-action time)
(Fb07 = OFF)
0 to 999 s
T
Y
(modulation transit time)
(Fb07 = OFF)
5 to 240 s
118
EB 5474 EN
Appendix