28
EB 9527-3 EN
Settings
8.5 Adjusting limit contacts
8.5.1
Max. filling limit during
operation
The filling limit during operation preset by
the software can be modified only in filling
level mode at the operating keys.
UCW marker
Deactivate write protection by setting switch
4
to
OFF
.
Press and hold key for approx. 8 s until
UCW
is shown at the top and the associ-
ated value in % at the bottom of the dis-
play.
Press key to confirm reading.
Press key to reduce value in steps of 1 %,
or
Press key to raise the value.
Press key to confirm the adjusted value.
Activate write protection by setting switch
4
to
ON
.
8.5.2 Alarm contacts A1 and
A2
Alarm
A1
and
A2
markers
In counting flow rate mode (Media 6 Z), only
alarm A1 is available.
Both limit contacts are preset by the software
to function as either min. or max. contacts.
A1MIN
or
A1MAX
as well as
A2MIN
or
A2MAX
appear on the display. Both con-
tacts must be set and confirmed separately.
Deactivate write protection by setting switch
4
to
OFF
.
Press and hold key for approx. 8 s until
UCW
appears at the top of the display.
Press keys to switch between
A1
and
A2
contacts.
Press key to confirm selected contact.
Press key to reduce value in steps of 1 %,
or
Press key to raise the value.
Press key to confirm the adjusted value.
Press and hold key for approx. 8 s until
UCW
appears.
Press keys to switch to the second contact
to be set.
Confirm selection and set alarm contact
as described above.
Activate write protection by setting switch
4
to
ON
.
8.6
Switching the LCD on and
off
The LCD can be switched on or off.
Press and hold the
and
keys for three
seconds until the LCD is switched on or off.
Note
Note