EB 9527-3 EN
27
Settings
The test medium must free of oil and grease when the device is used to measure oxygen.
Process medium: gaseous oxygen · Max. temperature: +60 °C, max. oxygen pressure: 30 bar
When the device is used for oxygen service, make sure that the dp cell and any SAMSON accessories
only come into contact with gaseous oxygen.
Fig. 8:
Test setup
0
20
40
60
80
100
%
m
3
x1000
– +
Off
.
~
–
+
–
+
Precision regulator with Class 0.1 pressure gauge
Only use oil-free air or other
gases, e.g. N
2
.
Supply unit
mA reading
Supply air reducing station with
oil filter and test pressure gauge
Test pressure
A
B
NOTICE
!
Display:
∆p100 = X.XXX
(x1000) mbar.
−
Use a precision regulator to apply a test
pressure corresponding to the max. dif-
ferential pressure Δp100 while monitor-
ing the pressure gauge.
Press and hold key until the current mea-
sured value is displayed. The signal I in-
dicates the current value in mA.
Press key to calibrate span. The signal
changes to 20 mA, the reading corre-
sponds to Δp100.
Release key.
Activate write protection and span pro-
tection by setting switch
4
and switch
3
to
ON
.