Design and principle of operation

The following applies to the version 

without 

explosion protection

 (100033844):

 

Use of the option module in hazardous 

areas is not permissible.

2.1 

Technical data

4 to 20 mA current output

Module 100049064

 

with explosion protection

 1)

Module 100033844

 

without explosion protection

Version

Magnetoresistive measuring system

Supply voltage U

B

12 to 28 V DC

12 to 36 V DC

Output signal

4 to 20 mA, two-wire system according to DIN 66258

Perm. load R

B

 in Ω

R

B

 = (U

B

 – 12 V)/0.020 A|(R ≤600 Ω at 24 V and 20 mA)

Power consumption

0.252 mW for 12 V DC and 21 mA

Settings

Zero calibration|Span calibration|Characteristic selection|Test 

function

Characteristic

Output and reading linear or square root extraction depending 

on installed flow characteristic

 

Characteristic set at the factory

Deviation from terminal-based 

linearity

<±0.2 %, related to 270° measuring span

Sensitivity

<±0.05 %, related to 270° measuring span

Effect of ambient temperature in 

the range from –40 to +80 °C

<0.1 %/10 K for zero and span

Type of protection

ATEX: II 2 G Ex ia IIC T4 Gb

IECEx: Ex ia IIC T4 Gb

Conformity

1) 

The technical data for the explosion-protected devices may be restricted by the limits specified in the 

test certificates.

Содержание Media 5

Страница 1: ...Material number 3 Serial number 4 QR code to go to product documentation 3 1 2 WARNING POTENTIAL ELECTROSTATIC CHARGING HAZARD SEE INSTRUCTIONS Module Made in Germany SAMSON AG Germany Firmware Mater...

Страница 2: ...sions The following applies to the version with explosion protection 100049064 1 When working on explosion protected versions of the option module personnel must undergo special training or instruc ti...

Страница 3: ...R 600 at 24 V and 20 mA Power consumption 0 252 mW for 12 V DC and 21 mA Settings Zero calibration Span calibration Characteristic selection Test function Characteristic Output and reading linear or...

Страница 4: ...eas Dial screws Housing screws Cover plate Fig 3 Standard version of Media 5 Indicat ing unit with cover plate 1 Undo the four housing screws Remove the housing cover 2 Unscrew the two dial plate scre...

Страница 5: ...r weight Mating plate Pointer axis Pointer Fig 5 Fixing the magnetoresistive measuring system 6 If the terminal board has not yet been connected connect the connecting cable and connector at the back...

Страница 6: ...nsists of an actively controlled current loop with a 4 to 20 mA loop current This current depends on the position of the pointer on the Media 5 device Pointer position 0 to 270 corresponds with the 4...

Страница 7: ...n Characteristic 4 mA 20 mA ammeter Zero calibration The electric zero is adapted to the mechani cal zero As a result a 4 mA signal is also issued at p 0 bar corresponding to the pointer s zero point...

Страница 8: ...ero and span calibration ranges Characteristic Three characteristics are available Linear Root extracting User defined factory set ting Activate characteristic level Key LED Function 3x key Green Blin...

Страница 9: ...according to explosion protection requirements has issued an inspection certificate or given the device a mark of conformity Inspection by a qualified inspector is not required if the manufacturer per...

Страница 10: ...2020 09 11 English SAMSON AKTIENGESELLSCHAFT Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samsongroup com www samsongroup com IP 9519 1 EN...

Отзывы: