6  

IP 9519-1 EN

Installation

9.  Insert the terminal board at the side un-

derneath the dial plate.
Use Phillips screwdriver to tighten the 
retaining screw.

10. Insert the connecting cable into the guid-

ing of the indicating unit.

Fig. 8: 

Inserting the terminal board

11. Guide the measuring signal lines (min. 

8 mm stripped length) through the cable 
gland and connect them to the spring-
cage terminal (31, 32) on the terminal 
board (see Fig. 9). Observe the correct 
polarity.

Measuring signal connection

The option module with current output is de-
signed as a two-wire system.

~

31+

32–

31+

32–

Fig. 9: 

Measuring signal connection in two-

wire system

The option module consists of an actively 
controlled current loop with a 4 to 20 mA 
loop current. This current depends on the 
position of the pointer on the Media 5 
device:

 

Pointer position 0 to 270° corresponds 
with the 4 to 20 mA loop current.

The measuring signal and supply voltage of 

the option module are transmitted by the 

same pair of wires. It is connected to the ter-
minal board over two spring-cage terminals.

Fig. 10: 

Connecting the measuring signal lines 

on the terminal board

The Media 5 Differential Pressure and Flow 
Meter supplies a 4 to 20 mA current regard-
less of the supply voltage. 

Risk of the supply voltage falling lower 

than the required level due to the use of a 

shunt.

 

Î

To maintain the functioning of the option 
module when a shunt is used, apply the 
following formula to take the loop volt

-

age into account: U

Loop-min

 = 12 V + 

(R

shunt

 x 21 mA)

NOTICE

!

Содержание Media 5

Страница 1: ...Material number 3 Serial number 4 QR code to go to product documentation 3 1 2 WARNING POTENTIAL ELECTROSTATIC CHARGING HAZARD SEE INSTRUCTIONS Module Made in Germany SAMSON AG Germany Firmware Mater...

Страница 2: ...sions The following applies to the version with explosion protection 100049064 1 When working on explosion protected versions of the option module personnel must undergo special training or instruc ti...

Страница 3: ...R 600 at 24 V and 20 mA Power consumption 0 252 mW for 12 V DC and 21 mA Settings Zero calibration Span calibration Characteristic selection Test function Characteristic Output and reading linear or...

Страница 4: ...eas Dial screws Housing screws Cover plate Fig 3 Standard version of Media 5 Indicat ing unit with cover plate 1 Undo the four housing screws Remove the housing cover 2 Unscrew the two dial plate scre...

Страница 5: ...r weight Mating plate Pointer axis Pointer Fig 5 Fixing the magnetoresistive measuring system 6 If the terminal board has not yet been connected connect the connecting cable and connector at the back...

Страница 6: ...nsists of an actively controlled current loop with a 4 to 20 mA loop current This current depends on the position of the pointer on the Media 5 device Pointer position 0 to 270 corresponds with the 4...

Страница 7: ...n Characteristic 4 mA 20 mA ammeter Zero calibration The electric zero is adapted to the mechani cal zero As a result a 4 mA signal is also issued at p 0 bar corresponding to the pointer s zero point...

Страница 8: ...ero and span calibration ranges Characteristic Three characteristics are available Linear Root extracting User defined factory set ting Activate characteristic level Key LED Function 3x key Green Blin...

Страница 9: ...according to explosion protection requirements has issued an inspection certificate or given the device a mark of conformity Inspection by a qualified inspector is not required if the manufacturer per...

Страница 10: ...2020 09 11 English SAMSON AKTIENGESELLSCHAFT Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samsongroup com www samsongroup com IP 9519 1 EN...

Отзывы: