5-4
EB 3009 EN
Installation
Table 5-1:
Inlet and outlet lengths
DN
min.
a x DN
min.
b x DN
a
Inlet length
b
Outlet length
State of process me-
dium
Valve conditions
Inlet length a
Outlet length b
Gas
Ma ≤ 0.3
2
4
Vapors
1)
Ma ≤ 0.3
2
4
Liquid
Free of cavitation/w < 3
m
/
s
2
4
Cavitation producing noise/w ≤ 3
m
/
s
2
4
1)
No saturated steam
_
_
+
+
2
4
6
3
5
1
p
1
p
2
1 Shut-off valve
2 Strainer
3
Pressure gauge (flow pipe)
4
Type 42-10 RS Check Valve (backflow protection)
5
Pressure gauge (return flow pipe)
6 Shut-off valve
Fig. 5-2:
Type 42-10 RS (installation example)