88
EB 8387-5 EN
Appendix
Code
no.
Parameter
– Readings/
values [default setting]
Description
45 Forced venting status
Read only
Indicates whether the option is installed or not.
NO
No forced venting installed
YES
Forced venting installed
If a voltage supply is connected at the terminals of the forced
venting option,
YES
and
HIGH
appear on the display in alternat-
ing sequence. If a voltage supply is not connected (actuator vent-
ed, fail-safe position indicated on the display by the
S
icon),
YES
and
LOW
appear on the display in alternating sequence.
46* Bus address
Read only
47* Write protection status
[NO], YES, ESC
When write protection is active, device data can be read using FF
communication but not overwritten.
48* Diagnostics
Diagnostic parameters d
d0 Temperature
Read only
Current operating temperature [°C] inside the positioner
(accuracy ±3 %)
d1 Min. temperature
Read only
The lowest temperature below 20 °C that has ever occurred.
d2 Max. temperature
Read only
The highest temperature above 20 °C that has ever occurred.
d3 Number of zero
calibrations
Read only
Indicates number of zero calibrations performed since the last
initialization
d4 Number of
initializations
Read only
The total number of initializations that have been performed
since the last reset.
d5 Zero limit
0.0 to 100.0 % [5 %]
of the nominal range
User-defined zero monitoring: used for error monitoring of the
zero shift.
Содержание 3731-5
Страница 71: ...EB 8387 5 EN 71...
Страница 102: ...102 EB 8387 5 EN...
Страница 103: ...EB 8387 5 EN 103...
Страница 104: ...104 EB 8387 5 EN...
Страница 105: ...EB 8387 5 EN 105...
Страница 106: ...106 EB 8387 5 EN...
Страница 107: ...EB 8387 5 EN 107...
Страница 110: ...110 EB 8387 5 EN...
Страница 111: ...EB 8387 5 EN 111...