![Samson 3731-5 Скачать руководство пользователя страница 60](http://html1.mh-extra.com/html/samson/3731-5/3731-5_mounting-and-operating-instructions_3899035060.webp)
60
EB 8387-5 EN
Operating the positioner
The maximum possible travel must always be greater than the rated travel entered. If this is
not the case, initialization is automatically canceled (error message Code 52) because the
rated travel could not be achieved.
Enable configuration:
Configuration is locked again if no settings are entered within 120 s.
1.
Turn until Code
3
appears (reading:
OFF
).
2. Press
, the code number
3
blinks.
3.
Turn until
ON
appears.
4. Press
to confirm (reading: ).
Enable configuration
Default: OFF
Enter the pin position and nominal range:
1.
Turn until Code
4
appears.
2. Press
, the code number
4
blinks.
3.
Turn to select pin position on lever (see
relevant section on attachment).
4. Press
to confirm. The nominal range is
displayed in mm/°.
mm
Pin position
Default: OFF
5.
Turn until Code
5
appears.
6. Press
, the code number
5
blinks.
7.
Turn to select the nominal range of the
valve.
8. Press
to confirm.
mm
Nominal range
(locked when Code 4 =
'OFF')