Appendix
12.3 Code list
Code
no.
Parameter
– Readings/
values [default setting]
Description
Note: Codes marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
0 Operating mode
[MAN], AUtO, SAFE, ESC
MAN
Manual mode
AUtO
Automatic mode
SAFE
Fail-safe position
ESC
Cancel
In MAN and AUtO mode, the system deviation is represented by
the bar graph elements.
The reading indicates the valve position or angle of rotation in %
when the positioner is initialized. If the positioner is not initial-
ized, the position of the lever in relation to the mid-axis is dis-
played in degrees (°).
Switchover from automatic to manual mode is bumpless.
In fail-safe position, the
S
icon is displayed.
Init
AtO/AtC
Init
Start initialization
Determine the fail-safe position:
AtO
:
AIR TO OPEN (the signal pressure opens the valve, e.g.
for a fail-close valve)
AtC
:
AIR TO CLOSE (the signal pressure closes the valve, e.g.
for a fail-open valve)
1 Manual set point w
[0] to 100 % of the nominal
range
Set the manual set point
The current travel/angle is displayed in % when the positioner is
initialized. If the positioner is not initialized, the position of the le-
ver in relation to the mid-axis is indicated in degrees (°).
Note:
can only be selected when Code
0
=
MAN
2
Reading direction
[Normal] or upside down
ESC
The reading direction of the display is turned by 180°.
Содержание 3731-5
Страница 71: ...EB 8387 5 EN 71...
Страница 102: ...102 EB 8387 5 EN...
Страница 103: ...EB 8387 5 EN 103...
Страница 104: ...104 EB 8387 5 EN...
Страница 105: ...EB 8387 5 EN 105...
Страница 106: ...106 EB 8387 5 EN...
Страница 107: ...EB 8387 5 EN 107...
Страница 110: ...110 EB 8387 5 EN...
Страница 111: ...EB 8387 5 EN 111...