5.  Wire Power Meter to 

Gateway Adapter

Wire ports 11,12, and 13 on the power meter to the gateway adapter, and plug it 
into the gateway.  Use 22/3 or 22/4 shielded wire. 

1.  Connect port 11 (A) on the power meter to A on the gateway adapter.

2.  Connect port 12 (B) on the power meter to B- on the adapter.

3.  Connect port 13 (G) on the power meter to GND on the adapter.

Connect the gateway to power with the 120V AC wall adapter, or with the direct 
12V-48V DC adapter. 

Once the meter is properly mounted to the DIN Rail or enclosure, all wiring is 
completed, and terminal block covers are installed, power can be turned back 
on. 

With power back on, the gateway will automatically connect to the cloud via 
its cellular connection and update to the latest software. The LED indicates the 
gateway status. Confirm that the gateway LED turns green.

6.  Connect Gateway 

to Power

7.  Turn Power On

Solid Orange: 

The gateway is booting up

Blinking Orange: 

The gateway is attempting to establish a secure cellular or WiFi connection

Solid Green: 

The gateway is securely connected to the cloud

Содержание PM20

Страница 1: ...Samsara PM Series Power Monitoring Install Guide...

Страница 2: ...al Turn off all power supplying the equipment before performing the installation System Type Description Allowable Voltages CTs Needed Single phase 2 Wire 1 line and neutral 20 480V 1 Single phase 3 W...

Страница 3: ...al and then hot wire s System Type Labeling CTs Needed Wiring Diagram 3 Phase 4 Wire Label the hot wires as L1 L2 and L3 Label the neutral as N 3 See below 3 Phase 3 Wire Label the hot wires as L1 L2...

Страница 4: ...Ts to L1 L2 and L3 hot wires 2 Connect the CT1 so that the L1 hot wire passes through it and the arrow on the CT points towards the load Repeat for CT2 and CT3 respectively Ensure all CTs are oriented...

Страница 5: ...irect 12V 48V DC adapter Once the meter is properly mounted to the DIN Rail or enclosure all wiring is completed and terminal block covers are installed power can be turned back on With power back on...

Страница 6: ...tage is correct given your system voltage Not all possible systems are listed below System Type System Voltage Approximate Phase Voltage Reading in Samsara Cloud Single phase 2 Wire 120V 120V Single p...

Страница 7: ...the CT white wire to port 2 on the power meter Must be completed BEFORE connecting the CT to the hot wire 2 Connect the CT so that the L1 hot wire passes through it and the arrow on the CT points tow...

Страница 8: ...s 2 and 4 Must be completed BEFORE connecting CTs to L1 and L2 hot wires 2 Connect the CT1 so that the L1 hot wire passes through it and the arrow on the CT points towards the load Repeat for CT2 Ensu...

Страница 9: ...rt 6 on the power meter Must be completed BEFORE connecting CT to hot wire 3 Connect the CT1 so that the L1 hot wire passes through it and the arrow on the CT points towards the load Connect the CT3 s...