background image

2

GENERAL

4

The Inverter Installation Kit consists of two cables and fuse arrangement for connecting the battery to the 
inverter in a safe manner.

Fuse Protection in the Battery Circuit

A battery is an unlimited source of current. Under short circuit conditions, a battery can supply thousands of 
Amperes of current. If there is a short circuit along the length of the cables that connect the battery to the 
inverter, thousands of Amperes of current can fl ow from the battery to the point of shorting and that section 
of the cable will overheat, the insulation will melt and the cable will ultimately break. This interruption of very 
high current will generate a hazardous, high temperature, high energy arc with accompanying high pressure 
wave that may cause fi re, damage nearby objects and cause injury. To prevent occurrence of hazardous 
conditions under short circuit conditions, an appropriate fuse should be used in the battery circuit that has the 
required current interrupting capacity (Termed AIC – Ampere Interrupting Capacity). For this purpose, fuse with 
AIC rating of 10000 A at 14 V / 5000 A at 32 V, or higher should be used. 
The following types of fuses are included in the Kit:

•  400 A, 125 VDC,  Model JLLN 400 manufactured by Littelfuse

 

-  AIC of 20,000 A

 

-  UL Class “T” rated, UL listed as per UL Standard 248-15

•  Marine Rated Battery Fuse (MRBF Series) made by Cooper Bussmann

 

-  Voltage rating of max 58 VDC

 

-  Current ratings of 100 A (MRBF-100), 200 A (MRBF-200) and 

 

   300 A (MRBF-300) 

 

-  AIC of 10000 A at 14VDC, 5000 A at 32 VDC and 2000 A at 58 VDC

 

-  Ignition protected as per SAE J1171

 

-  Weather Proof (IP66)

Caution!

 

The fuse should be placed as close to the battery Positive terminal as possible, preferably 

within 7” of the battery terminal.

Sizing of Cables to Reduce Voltage Drop, Heating and Power Loss

The fl ow of electric current in a conductor is opposed by the resistance of the conductor. The resistance of 
the conductor increases linearly as the length of the conductor is increased and decreases as the cross-section 
(thickness) of the conductor is increased. Flow of current through the resistance of the conductor produces 
voltage drop and power loss due to heating. The voltage drop due to resistance of the conductor increases 
linearly as the current increases.

The power loss because of heating due to resistance of the conductor increases by the square of the increase in 
the current -  e.g. if the current increases 2 times, the heating / power loss increases 4 times. Thus, it is desirable 
that thicker and shorter conductors be used to reduce the undesirable effects of voltage drop, heating and 
power loss.

The size (thickness / cross-section) of the conductors is designated by AWG (American Wire Gauge). Please note 
that a smaller AWG # denotes a thicker size of the conductor up to AWG #1. Wires thicker than AWG #1 are 
designated AWG 1/0, AWG 2/0, AWG 3/0 and so on. In this case, increasing AWG # X/0 denotes thicker wire. 

Содержание DC-1000-KIT

Страница 1: ...Owner s Manual Please read this manual before operating your Inverter Installation Kit Inverter Installation Kit DC 1000 KIT DC 2000 KIT DC 2500 KIT DC 3500 KIT ...

Страница 2: ...2 INDEX 1 0 Important Safety Precautions 3 2 0 General 4 3 0 Installations Instructions 7 4 0 Specifications 14 5 0 Warranty 15 ...

Страница 3: ...uld be taken to ventilate the battery area and follow the battery manufacturer s recommendations Never smoke or allow a spark or flame near the batteries Use caution to reduce the risk of dropping a metal tool on the battery It could spark or short circuit the battery or other electrical parts and could cause an explosion Remove metal items like rings bracelets and watches when working with batter...

Страница 4: ...ade by Cooper Bussmann Voltage rating of max 58 VDC Current ratings of 100 A MRBF 100 200 A MRBF 200 and 300 A MRBF 300 AIC of 10000 A at 14VDC 5000 A at 32 VDC and 2000 A at 58 VDC Ignition protected as per SAE J1171 Weather Proof IP66 Caution The fuse should be placed as close to the battery Positive terminal as possible preferably within 7 of the battery terminal Sizing of Cables to Reduce Volt...

Страница 5: ... to operate normally within a specified lower and upper input voltage range The lower operating voltage limit of inverters is normally 10 V 20 V and 40 V for 12 V 24 V and 48 V battery systems respectively When this limiting voltage is seen at the input terminal of the inverter it will shut down due to low input voltage protection Thus if there is excessive voltage drop in the input connection bet...

Страница 6: ...o Poly Ethylene jacket This provides the high 2000 V insulation and resistance to abrasion oils acids and heat UL listed to UL Standard UL44 Thermo set Insulated Wires and Cables Type RHH RHW CSA listed to CSA Standard C22 2 No 38 Thermoplastic Insulated Wires and Cables Type R 90 Characteristics of Fuses and Fuse Holders Provided with the Kits DC 1000 KIT DC 2000 KIT and DC 2500 KIT are provided ...

Страница 7: ...tive cables Positive cable Terminal lugs at each end are covered with red heat shrink as in Fig 3 1 Negative cable Terminal lugs at each end are covered with black heat shrink as in Fig 3 2 Fig 3 2 Negative Cable end Fig 3 1 Positive cable end B Connect one end of the positive cable to the positive terminal of the inverter usually red in color C Identify the components of the Fuse Assembly Refer t...

Страница 8: ...d of the Positive cable into the CFBAR stud so that it sits over the fuse MRBF See Fig 3 8 F Next insert the flat washer the spring washer and the M 8 nut on to the CFBAR stud and tighten the nut with a wrench See Fig 3 9 Fig 3 7 Fuse MRBF inserted into the stud on CFBAR Fig 3 5 M 8 Nut Flat Washer and Spring Washer Fig 3 6 Insulating cap Fig 3 8 ...

Страница 9: ...e exposed portion of the stud of the CFBAR See Figures 3 10 and 3 11 H Bolt the CFBAR to the Positive terminal stud of the Battery usually denoted by the sign as shown in Fig 3 12 Fig 3 10 Insulating Cap slid over the rectangular portion of CFBAR Fig 3 11 CFBAR with fitted fuse MRBF Fig 3 9 Fuse MRBF and Positive cable fixed to the CFBAR ...

Страница 10: ... ensure that all the connections are tight DC 3500 KIT A Identify the Positive Negative Cables Positive cable Terminal lugs at each end are covered with Red heat shrink as in Fig 3 13 Negative cable terminal lugs at each end are covered with Black heat shrink as in Fig 3 14 B The Class T Fuse Assembly Fig 3 15 consists of the following components assembled as one unit Fig 3 12 Installed arrangemen...

Страница 11: ...is 0 6 15 5 mm Hexagonal headed socket screws requires Allen Key size 5 16 are used to clamp the cable ends Snap on cover Is made of clear polycarbonate and provides touch safety C The fuse should normally be installed within 7 inches of the Positive Terminal of the battery Cut the Positive cable based on the desired location of the Class T Fuse Assembly using an appropriate wire cutter Strip 1 05...

Страница 12: ...ll be required to be pressed together closely to reduce the diameter near the cut face to less than 0 6 To help keep the strands towards the cut face pressed together for easier entry into the terminal for cable entry tightly warp insulation tape around 0 2 to 0 3 from the cut face If required straighten and compress the bent frayed spread out ends to reduce the diameter to the minimum Now insert ...

Страница 13: ...Negative cable to the Negative terminal of the inverter usually Black in color H Connect the other end of the Negative cable to the battery Negative terminal usually denoted by the sign When the lug of the Negative cable first makes a contact with the Negative terminal of the battery a spark may be observed This is normal This spark occurs because of the initial charging current of the input side ...

Страница 14: ...T DC 2500 KIT DC 3500 KIT Cable Gauge AWG 4 AWG 2 AWG 2 0 AWG 4 0 Cable Length 10 feet 10 feet 10 feet 10 feet Voltage drop 12 V system 3 ft length 0 8 2 5 1 2 1 0 6 ft length 1 6 5 1 2 3 2 0 10 ft length 2 7 8 4 3 9 3 3 24 V system 3 ft length 0 4 1 3 0 6 0 5 6 ft length 0 8 2 5 1 2 1 0 10 ft length 1 3 4 2 1 9 1 7 Fuse Size 100 Amp 200 Amp 300 Amp 400 Amp Included hardware 6 Nos 11 5 Black Tie W...

Страница 15: ...Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misuse of the equipment including exposure to excessive heat salt or fresh water spray or water immersion No other express warranty is hereby given and there are no warranties which extend beyond thos...

Страница 16: ... Coquitlam B C Canada V3K 6V2 T 604 525 3836 F 604 525 5221 e mail samlex samlexamerica com website www samlexamerica com 091 2009_DC 1000 KIT_DC 2000 KIT_DC 2500 KIT_DC 3500 KIT_Inverter_Installation_Kit_Manual_Jan2010 ...

Отзывы: