INVERTER RELATED

Preventing paralleling of the AC output 

The AC output of this inverter cannot be synchronised with another AC source and 
hence, it is not suitable for paralleling. The AC output of the inverter should never be 
connected directly to an electrical breaker panel / load center which is also fed from 
the utility power / generator. Such a connection may result in parallel operation of the 
different power sources and AC power from the utility / generator will be fed back 
into the inverter which will instantly damage the output section of the inverter and 
may also pose a fire and safety hazard. If an electrical breaker panel / load center is 
fed from an inverter and this panel is also required to be powered from additional 
alternate AC sources, the AC power from all the AC sources like the utility / generator 
/ inverter should first be fed to a manual selector switch and the output of the selector 
switch should be connected to the electrical breaker panel / load center. 
To prevent possibility of paralleling and severe damage to the inverter, never use a 
simple jumper cable with a male plug on both ends to connect the AC output of the 
inverter to a handy wall receptacle in the home / RV. 

Connecting to multi-wire branch circuits 

Do not directly connect the hot side of the inverter to the two hot legs of the 120 / 
240 VAC electrical breaker  panel / load centre where multi-wire ( common neutral ) 
branch circuit wiring method is used for distribution of AC power. This may lead to 
overloading / overheating of the neutral conductor and is a risk of fire.

A split phase transformer ( isolated or auto-transformer ) of suitable wattage rating 
( 25 % more than the wattage rating of the inverter )  with primary of  120 VAC and 
secondary of 120 / 240 VAC ( Two 120 VAC split phases 180 degrees apart) should be 
used. The hot and neutral of the 120 VAC output  of the inverter should be fed to 
the primary of this transformer and the 2 hot outputs ( 120 VAC split phases ) and the 
neutral from the secondary of this transformer should be connected to the electrical 
breaker panel / load centre.

Preventing input over voltage

It is to be ensured that the input voltage of the inverter does not exceed 16.5 VDC 
(PST-30S-12A) or 33 VDC (PST-30S-24A) to prevent permanent damage to the inverter. 
Please observe the following precautions:

• 

Ensure that the maximum charging voltage of the battery charger / alternator / 
solar charge controller is below 16.5 VDC (PST-30S-12A) or 33 VDC (PST-30S-24A)

• 

Do not use unregulated solar panels to charge a battery. Under cold ambient 
temperatures, the output of the solar panel may exceed 18 VDC for 12V battery 
system of 36VDC for 24V battery system. Always use a charge controller between 
the solar panel and the battery.

• 

Do not connect the inverter to a battery that has a voltage higher than the rated 
battery input voltage of the inverter.

Preventing reverse polarity on the input side

When making battery connection on the input side, make sure that the polarity of 
battery connection is correct (Ensure that the centre contact of the cigarette lighter 
receptacle is connected to the positive of the battery. The centre pin (tip) of the 
cigarette lighter plug attached to the inverter is positive). If the input is connected in 
reverse polarity, DC fuse inside the inverter will blow and may also cause permanent 
damage to the inverter.

Содержание PST-30S-12A

Страница 1: ...300 Watt Pure Sine Wave DC AC Inverter PST 30S 12A PST 30S 24A Owner s Manual Please read this manual before operating your DC AC inverter...

Страница 2: ...and Grounding 9 10 11 Limiting Electromagnetic Interference EMI 11 Powering direct embedded SMPS 12 Principle of Operation 13 Layout 13 Specifying Batteries Chargers and Alternators 14 15 16 17 18 In...

Страница 3: ...s To ensure proper ventilation do not install in a low clearance compartment Preventing fire and explosion hazards Working with the inverter may produce arcs or sparks Thus the inverter should not be...

Страница 4: ...it phase transformer isolated or auto transformer of suitable wattage rating 25 more than the wattage rating of the inverter with primary of 120 VAC and secondary of 120 240 VAC Two 120 VAC split phas...

Страница 5: ...ble for use in buildings including homes for recreational vehicles boats and portable applications Will it be connected to the utility grid in some way Electrical conventions and safety standards diff...

Страница 6: ...er will further limit its ability to start a motor A battery bank that is undersized in poor condition or has corroded connections can be a weak link in the power chain The inverter cables and the bat...

Страница 7: ...0 VAC To obtain 240 VAC from a 120 VAC inverter use a 120 VAC to 240 VAC transformer If you do not already have a pump installed you can get a 120 volt pump if you don t need more than 1 2 HP Idle pow...

Страница 8: ...for resistive type of loads that have unity 1 Power Factor In a reactive type of load like electric motor driven loads fluorescent lights computers audio video equipment etc the phase of the sine wav...

Страница 9: ...wave form is a sine wave with very low harmonic distortion and clean power like utility supplied electricity Inductive loads like microwaves and motors run faster quieter and cooler Reduces audible an...

Страница 10: ...ected to earth Examples are the neutral conductor in AC wiring and the negative conductor in many DC systems A grounded system is a system in which one of the current carrying conductors is grounded A...

Страница 11: ...to the AC power source The plug of the power cord has three pins two flat pins also called poles that are connected to the two current carrying conductors and a round pin which is connected to a non...

Страница 12: ...bare metal Use star washers to penetrate paint and corrosion The inverter contains internal switching devices which generate conducted and radiated electromagnetic interference EMI The magnitude of EM...

Страница 13: ...f up to 4 This will mean that for a particular rated RMS current applicable for a linear load the general purpose SMPS will draw much larger peak currents approx up to 4 times more than its rated RMS...

Страница 14: ...o a reference sine wave 1 2 3 1 120V AC output receptacle 2 L E D indicator 3 On Off Switch 4 Input terminals back of unit not shown RED Positive BLACK Negative 5 Cooling fan back of the unit not show...

Страница 15: ...of deep cycle lead acid batteries wet and sealed A wet cell battery has a high tolerance to overcharging However it will release hydrogen gas when charging that must be properly vented and the water...

Страница 16: ...is not linear but is more or less according to the table below Table 1 Battery Capacity versus Rate of Discharge Hours of Discharge Usable Capacity 20 100 10 87 8 83 6 75 5 70 3 60 2 50 1 40 Using th...

Страница 17: ...connection of batteries When two or more batteries are connected in series their voltages add up but their AH capacity remains the same For example when two 12 V 105 AH batteries are connected in ser...

Страница 18: ...bove may be used to calculate the AC watts by multiplying 120 VAC by the AC current in Amperes The next step is to derive the DC current in Amperes A from the AC watts as per formulae 2 above An examp...

Страница 19: ...should be powered from the deep cycle batteries For charging the SLI and the auxiliary deep cycle batteries the output from the alternator should be fed to these two sets of batteries through a batter...

Страница 20: ...ol dry environment Do not expose to moisture rain snow or liquids of any type To reduce the risk of overheating and fire do not obstruct the suction and discharge openings of the cooling fan To ensure...

Страница 21: ...the solar wind hydro charging source directly to the battery through the series connected switching MOSFET s The battery is a capacitive type of load and will thus dampen the input voltages of the cha...

Страница 22: ...e inverter and the battery assuming that two one positive and one negative cables are used for the connection Distance up to 3 Distance up to 6 Ampere rating of fuse PST 30S 12A 12 AWG 8 AWG 40 A PST...

Страница 23: ...may also pose a fire and safety hazard If an electrical breaker panel load center is fed from an inverter and this panel is also required to be powered from additional alternate AC sources the AC pow...

Страница 24: ...ck by detecting leakage and cutting off the AC source Installation in recreation vehicles RV may require GFCI protection on the AC output In addition electrical codes may require GFCI protection for c...

Страница 25: ...the DC side circuit will still be alive even when the switch is in the off position Hence disconnect the DC and AC sides before working on any circuits connected to the inverter When the inverter is s...

Страница 26: ...the inverter cable and fuse sizes on page 20 If the voltage at the DC input terminals falls below 10 5 V for PST 30S 12A or 21 V for PST 30S 24A a buzzer alarm will be sounded The LED 2 will continue...

Страница 27: ...ssistance Shut down due to over temperature In case of failure of the cooling fan or in the case of inadequate heat removal due to higher ambient temperatures insufficient air exchange the temperature...

Страница 28: ...y input circuit are tight Correct the polarity of the input connections and replace the internal fuse Note Reverse polarity may cause permanent damage If the unit does not work after replacing the fus...

Страница 29: ...s working check that the ventilation slots on the suction side and the openings on the discharge side of the fan are not obstructed 3 If the fan is working and the openings are not obstructed check th...

Страница 30: ...actor of 0 8 to 0 6 The power that can be delivered to such type of loads will reduce by this factor See page 7 for details Low Input Voltage Warning Alarm 10 5 V 21 V Low Input Voltage Shut down 10 V...

Страница 31: ...attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misu...

Страница 32: ...34 2009 017_PST 30 12A_PST 30 24A_Jan2010 e mail samlex samlexpower com website www samlexpower com 110 17 Fawcett Rd Coquitlam B C Canada V3K 6V2 T 604 525 3836 F 604 525 5221 Toll Free 1 800 561 588...

Отзывы: