Strip adequate insulation from the end of the wire (Fig. 3.11). Avoid nicking the wire when
stripping the insulation. Wire End Terminals have been provided for firm connection under the
set screw. Insert the bare end of the wire into the barrel portion of the Wire End Terminal &
crimp barrel portion using suitable crimping tool (Fig 3.11).
Insert the terminated end of the wire fully into the terminal slot till it stops. Tighten the screw
firmly. Tightening torque for the screws – 7 to 12 Kgf*cm / 0.5 to 0.9 lbf*ft.
Fig 3.11 Stripped Wire End Terminal on AC Wiring
3.8 SIZING OF WIRING AND BREAKERS - AC INPUT SIDE
WARNING!
AC Breakers for the AC input circuits have NOT been provided internally. These have to be
provided externally by the installer / user based on guidelines given below. Please note that
guidelines given below on wire sizing and over-current protection will be superseded by the
applicable National / Local Electrical Codes.
ATTENTION!
Breakers AC pour les circuits d’entrée AC ont pas été fournis en interne. Ceux-ci doivent être fournies à l’extérieur par
l’installateur / utilisateur sur la base des directives données ci-dessous. Se il vous plaît noter que les directives ci-dessous
sur dimensionnement des câbles et protection contre les surintensités seront remplacées par les nationaux / codes
électriques locaux applicables.
3.8.1 Tables for Wire and Breaker Sizing - AC Input Side
Tables 3.2.1 to 3.2.3 provide details of wire and breaker sizing for the AC input side.
•
Table 3.2.1:
For EVO-2212, 2224, 3012 and 4024 with AC Input Current Limit (Max
Current) set at 30A (Default Setting)
•
Table 3.2.2:
For EVO-3012 and 4024 when AC Input Current Limit (Max Current) is
programmed at 45A
•
Table 3.2.3:
For EVO-4024 when AC Input Current Limit (Max Current) is pro-
grammed at 60A
AC wiring and breaker sizes depend upon the maximum continuous AC input current under
various operating conditions described in the succeeding paragraphs.
•
The Maximum Load Current on the output side has to be limited to the rated output Amp
SECTION 3 |
Installation
Stripped Wire End
Wire End Terminal
Crimp Barrel Portion
↓
→
Содержание Evolution EVO-2212
Страница 89: ...SAMLEX AMERICA INC 89 Notes ...
Страница 90: ...90 SAMLEX AMERICA INC Notes ...
Страница 91: ...SAMLEX AMERICA INC 91 Notes ...
Страница 133: ...SAMLEX AMERICA INC 41 APPENDIX A Notes ...
Страница 134: ...42 SAMLEX AMERICA INC APPENDIX A Notes ...
Страница 135: ...SAMLEX AMERICA INC 43 APPENDIX A Notes ...