1.4.5 Specifying Charging / Discharging Currents: C-Rate
Electrical energy is stored in a cell / battery in the form of DC power. The value of the stored
energy is related to the amount of the active materials pasted on the battery plates, the surface
area of the plates and the amount of electrolyte covering the plates. As explained above, the
amount of stored electrical energy is also called the Capacity of the battery and is designated by
the symbol “C”.
The time in Hours over which the battery is discharged to the “End Point Voltage” for purposes
of specifying Ah capacity depends upon the type of application. Let us denote this discharge
time in hours by “T”. Let us denote the rate of discharge current of the battery as a multiple of
Ah capacity "C" and call it as the "C-Rate”. If the battery delivers a very high discharge current,
the battery will be discharged to the “End Point Voltage” in a shorter period of time. On the
other hand, if the battery delivers a lower discharge current, the battery will be discharged to
the “End Point Voltage” after a longer period of time. Mathematically, C-Rate is defined as:
“C-RATE” = CAPACITY “C” in Ah ÷ DISCHARGE TIME “T”
Table 1.8 below gives some examples of C-Rate specifications and applications:
TABLE 1.8 DISCHARGE CURRENT RATES - “C-RATES”
Hours of discharge time “T” till
the “End Point Voltage”
“C-Rate” Discharge Current
in Amps = Capacity “C” in Ah
÷ Discharge Time “T” in Hrs.
Example of C-Rate
Discharge Currents
for 100 Ah battery
0.5 Hrs.
2C
200A
1 Hrs.
1C
100A
5 Hrs.
(Inverter application)
C/5 or 0.2C
20A
8 Hrs.
(UPS application)
C/8 or 0.125C
12.5A
10 Hrs.
(Telecom application)
C/10 or 0.1C
10A
20 Hrs. (
Automotive application)
C/20 or 0.05C
5A
100 Hrs.
C/100 or 0.01C
1A
NOTE:
When a battery is discharged over a shorter time, its specified “C-Rate” will be higher. For ex-
ample, the “C-Rate” at 5 Hour discharge period i.e. C/5 Amps will be 4 times higher than the “C-Rate” at
20 Hour discharge period i.e. C/20 Amps.
1.4.6 Charging / Discharging Curves
Fig. 1.4 shows the charging and discharging characteristics of a typical 12V / 24V Flooded
Lead Acid battery at electrolyte temperature of 80°F / 26.7°C. The curves show the % State
of Charge (X-axis) versus terminal voltage (Y-axis) during charging and discharging at different
C-Rates.
Please note that X-axis shows % State of Charge. State of Discharge will be =
100% - % State of Charge
. These curves will be referred to in the subsequent explanations.
SECTION 1 |
Safety Instructions & General Information
Содержание Evolution EVO-2212
Страница 89: ...SAMLEX AMERICA INC 89 Notes ...
Страница 90: ...90 SAMLEX AMERICA INC Notes ...
Страница 91: ...SAMLEX AMERICA INC 91 Notes ...
Страница 133: ...SAMLEX AMERICA INC 41 APPENDIX A Notes ...
Страница 134: ...42 SAMLEX AMERICA INC APPENDIX A Notes ...
Страница 135: ...SAMLEX AMERICA INC 43 APPENDIX A Notes ...