22 | SAMLEX AMERICA INC.
APPENDIX A
SECTION 4 |
Parameter Setup
side charging current and the pass through load current. Based on the rated capacity of the
Grid Branch Circuit/Generator, the net AC input current will be required to be limited to pre-
vent overloading of the Grid Branch Circuit/Generator.
EVO Series has a very powerful battery charger that will require a proportionate higher AC in-
put current from the Grid/Generator. The Grid/Branch Circuit/Generator will also be required
to provide current to the AC loads. The desired maximum value of input current from Grid/
Generator can be programmed (Default is 30A). The EVO will automatically reduce charging
current to support the AC loads on priority and use whatever is extra for charging. This will
prevent overloading of the Grid Branch Circuit/Generator. If the AC input current is over the
setting value by 1A for 5 seconds, the EVO Inverter Charger will stop outputting and display
an error message “Input over current” on LCD screen.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
MAXIMUM CURRENT
30.00 A
DEFAUT FREQ
0= 60Hz
Up Key
ò
Enter Key
ò
Up Key x 1
ò
HIGH CUT OFF:
If the AC input frequency is over the value of “HIGH CUT OFF” when in "Charging Mode",
the EVO Inverter Charger will transfer to Inverting Mode.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
HIGH CUT OFF
65.00 Hz
DEFAUT FREQ
0= 60 Hz
Up Key
ò
Enter Key
ò
Up Key x 2
ò
HIGH RESET:
This is the reset frequency at which the unit will revert to "Charging Mode" after it has
switched over to "Inverter Mode" due to input frequency rising above "HIGH CUT OFF".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
HIGH RESET
64.00 Hz
DEFAUT FREQ
0= 60 Hz
Up Key
ò
Enter Key
ò
Up Key x 3
ò
LOW CUT OFF:
If the AC input frequency is below “LOW CUT OFF” value when in "Charging Mode", the
EVO Inverter Charger will transfer to Inverting Mode.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
LOW CUT OFF
55.00 Hz
DEFAUT FREQ
0= 60 Hz
Up Key
ò
Enter Key
ò
Up Key x 4
ò
LOW RESET:
This is the reset frequency at which the unit will revert to "Charging Mode" after it has
switched over to "Inverting Mode" due to input frequency falling below "LOW CUT OFF".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
LOW RESET
56.00 Hz
DEFAUT FREQ
0= 60 Hz
Up Key
ò
Enter Key
ò
Up Key x 5
ò
Содержание Evolution EVO-2212
Страница 89: ...SAMLEX AMERICA INC 89 Notes ...
Страница 90: ...90 SAMLEX AMERICA INC Notes ...
Страница 91: ...SAMLEX AMERICA INC 91 Notes ...
Страница 133: ...SAMLEX AMERICA INC 41 APPENDIX A Notes ...
Страница 134: ...42 SAMLEX AMERICA INC APPENDIX A Notes ...
Страница 135: ...SAMLEX AMERICA INC 43 APPENDIX A Notes ...