TABLE 1.6 INVERTER SIZING FACTOR
Type of Device or Appliance
Inverter Sizing Factor
(See Note 1)
Air Conditioner / Refrigerator / Freezer (Compressor based)
5
Air Compressor
4
Sump Pump / Well Pump / Submersible Pump
3
Dishwasher / Clothes Washer
3
Microwave (where rated output power is the Cooking Power)
2
Furnace Fan
3
Industrial Motor
3
Portable Kerosene / Diesel Fuel Heater
3
Circular Saw / Bench Grinder
3
Incandescent / Halogen / Quartz Lamps
3
Laser Printer / Other Devices using Quartz Lamps for heating
4
Switch Mode Power Supplies (SMPS): no Power Factor correction
2
Photographic Strobe / Flash Lights
4 (See Note 2)
NOTES FOR TABLE 1.6:
1 Multiply the Running Active Power Rating {Watts} of the appliance by this Factor to arrive at the
Continuous Power Rating of the inverter for powering this appliance.
2 For photographic strobe / flash unit, the Surge Power of the inverter should be > 4 times the
Watt Sec rating of photographic strobe / flash unit.
1.3.4 Limiting Electro-Magnetic Interference
These inverters contain internal switching devices that generate conducted and radiated elec-
tromagnetic interference (EMI). The EMI is unintentional and cannot be entirely eliminated. The
magnitude of EMI is, however, limited by circuit design to acceptable levels as per limits laid
down in North American FCC Standard FCC Part 15(B), Class B. These limits are designed to
provide reasonable protection against harmful interference when the equipment is operated
in
a residential environment
. These inverters can conduct and radiate radio frequency energy and,
if not installed and used in accordance with the instruction manual, may cause harmful interfer-
ence to radio communications. The effects of EMI will also depend upon a number of factors
external to the inverter like proximity of the inverter to the EMI receptors, types and quality of
connecting wires and cables etc. EMI due to factors external to the inverter may be reduced as
follows:
•
Ensure that the inverter is firmly grounded to the Ground System of the building or the
vehicle.
•
Locate the inverter as far away from the EMI receptors like radio, audio and video de-
vices as possible.
•
Keep the DC side wires between the battery and the inverter as short as possible.
•
Do NOT keep the battery wires far apart. Keep them taped together to reduce their
inductance and induced voltages. This reduces ripple in the battery wires and improves
performance and efficiency.
SECTION 1 |
Safety Instructions & General Information
Содержание Evolution EVO-2212
Страница 89: ...SAMLEX AMERICA INC 89 Notes ...
Страница 90: ...90 SAMLEX AMERICA INC Notes ...
Страница 91: ...SAMLEX AMERICA INC 91 Notes ...
Страница 133: ...SAMLEX AMERICA INC 41 APPENDIX A Notes ...
Страница 134: ...42 SAMLEX AMERICA INC APPENDIX A Notes ...
Страница 135: ...SAMLEX AMERICA INC 43 APPENDIX A Notes ...