6 .4
Before beginning the pairing process, it is important to be sure that the ARV10RFM or AVA10M30RF
Radiator Valve Actuator was installed and adapted properly as detailed in their installation instructions .
The following is a review of those instructions .
ARV/AVA Radiator Valve Actuator Installation Review
Step 1. Install the batteries and wait until the LED is solid red before installing the actuator on the radiator
valve . Remember that the actuator should only be finger tight on the valve . Using pliers or other tools can
damage the device .
Step 2. After attaching the actuator to the valve, press any of the buttons to initialize the ARV/AVA Radiator
Valve Actuator . This process may take several minutes, and the valve may continue to initialize after the light is
no longer illuminated .
ARV/AVA Radiator Valve Actuator Pairing Procedure
Before pairing, the ARV/AVA Radiator Valve Actuator(s) and AX10RF Receiver (if desired) must be powered in
accordance with the installation instructions included with the devices .
• The LED indicator on the ARV/AVA Radiator Valve Actuator(s) should be off with NO MOTOR ACTIVITY .
• If and AX10RF Receiver is used, the LED backlight on the Auto/Manual switch of this device should be
flashing red and the switch should be in the AUTO position
Step 1. Press and hold the lighted red pairing button on the AC10RF Coordinator for 5 seconds, until the LED
begins flashing .
DO NOT BEGIN pairing with the ARV/AVA Radiator Valve Actuator unless the light is out and there is NO
MOTOR ACTIVITY. Listen closely to the Valve Actuator to be sure it is not operating before proceeding.
A maximum of 6 ARV10RFM or AVA10M30RF Radiator Valve Actuators
can be paired with each AWRT10RF Wireless Radiant Thermostat.
10 seconds
The LED indicator will flash red.
Step 2. Press and hold the pairing button until the LED
indicator begins flashing (approximately 10 seconds) on
each ARV/AVA Radiator Valve Actuator to be associated
with the AWRT Wireless Radiant Thermostat .
LED is off.
Auto
Manual
On
Off
LED is solid red.
When the ARV/AVA
valve actuators join the
network,the LED indicator
on the Radiator Valve
Actuator will turn off .
If an AX10RF Receiver
joins the network, the
LED backlight on the
Auto/Manual switch
will stay solid red .
Pairing with ARV10RFM or AVA10M30RF Radiator
Valve Actuators
Section 6
AWRT10RF Pairing without Internet
Connection (AC10RF Coordinator)