-15-
Gas Conversion (NG - ULPG)
If the required gas conversion kit is not supplied with your appliance, Gas Conversion shall only
be undertaken by authorised persons.
The NG TO ULPG conversion kit contains
•
Test point adapter
•
ULPG Gas Type label
•
Auxiliary Jet ø 0.53mm
•
Rapid Jet ø 0.9mm
•
Semi-Rapid Jet ø 0.69mm
•
Wok Jet ø 0.50mm (IN) + ø 1.02mm
(OUT)
Converting to a different gas type
When converting from NG to ULPG ensure that the NG regulator is
removed and replaced with the Test Point Assembly supplied in this
kit. An AGA Approved gas regulator suitable for a supply pressure of
2.75 kPa should be part of the gas tank supply and the test point
pressure must be adjusted to 2.75 kPa.
Changing the Jets
1.
Remove pan supports, burner heads and cups.
2.
Use a size 7 socket wrench to unscrew and remove the
jets, replacing them with those supplied in this kit. Ensure
you use the correct jet for the corresponding burner.
3.
Fit the Gas Type label supplied with this kit next to the
gas connection point and remove the existing label.
Setting the minimum level
1.
Remove panels, knobs and water dish.
2.
Reassemble the burner heads, caps and knobs.
3.
Light one of the burners and turn the tap to minimum
flame.
4.
Use a thin blade screwdriver to turn the by-pass screw
located on the right of the brass shaft as shown
(right). Turn the bypass screw fully counter
clockwise. The result should be a small, stable
flame which is uniform around the entire burner
ring. If not, turn the by-pass screw anti-
clockwise until satisfied with the flame.
5.
Check that the burner does not go out when the
tap is turned quickly from the maximum to the
minimum position.
6.
Repeat for each burner.
7.
Remove the burner heads, caps and knobs.
8.
Reassemble the panels, burner heads, caps,
knobs and pan supports.