21
SALICRU
Operating mode screen, Line mode code «02». 220Vac
fig. 26.
equipments.
Operating mode screen, Line mode code «02». 110Vac
fig. 27.
equipments.
5.2.4. Battery mode / Battery test mode.
The LCD panel on Battery mode is showed in figure 29. The avail-
able information in the LCD panel is input, battery, UPS output and
load. The operating code of the UPS is «03».
In the same figure the «INVERTER» block (square with the INVERTER
label) is active, it means that the inverter supplies the power used
by the load or loads, but it doesn’t charge the batteries because the
mains is not present or bad.
When the UPS is operating on Battery mode, the acoustic alarm
1.
beeps once every 4 seconds. If the button « I » of the front panel
is pressed for more than 1 second, the alarm will stop. Press
the button « I » for more than 1 second again to reactivate the
acoustic alarm function.
If the UPS runs on Battery mode and the input voltage mains
2.
overcomes the specific range of the equipment, the «H»
symbol will be displayed as an alarm mode. Meanwhile, if the
input voltage mains is lower than the specific range of the
equipment, the «L» alarm will be displayed. If there is not input
mains, there will not be any symbol and both the voltage and
frequency will be displayed as zero.
The same figure 29 shows the battery test mode and the «H» and
«L» symbols will be displayed during the test, if the input voltage
overcomes or it is lower than the specific ranges of the equipment.
The operating mode code of the UPS is «03» on battery mode, and
«04» on battery test mode..
Operating mode screen, Battery mode code «03».
fig. 28.
220Vac equipments.
5.2.5. fault mode.
Anyone of the fault or warning codes showed in the table 8 are
considered as fault mode. Besides, some warning word can also be
displayed in the LCD panel like for example «SHORT», which means
that the equipment or load is in short circuit and therefore the UPS
is on inverter fault mode. See table 4 of chapter 3.
5.2.6. Settings through the LCD panel.
The output voltage range, output frequency and bypass status
can be set directly through the LCD panel of the UPS. The output
voltage range can be selected among 208V, 220V, 230V and 240V.
The output frequency range can be set to 50Hz or 60Hz. The Bypass
can be enabled or disabled. Nevertheless, the settings can only be
done with the UPS on bypass or No output modes.
On Bypass or No output mode, press the button «
» (Select) of the
LCD panel for more than one second and the black point will blink
close to the «208V» indication of the LCD panel. If we press the
button «
» (Select) again, the black point will move through the
rest of values: «220V», «230V», «240V», «50Hz», «60Hz», «Bypass
disable», «Bypass enable». When pressing the button «
» (Enter)
for more than 1 second, the black point will not blink and the voltage
range or output frequency or Bypass status will be modified by the
selected value. In case the button «
» (Enter) or button «
» (Se-
lect) are not pressed in 10 seconds period, the black point will dis-
appear without applying any changes.
Only one voltage or frequency value can be selected at the same
time. The values will be changed once the UPS is started up through
the button «I».
The UPS will transfer to bypass mode for a few seconds when «By-
pass enable» is selected, and to no output mode when «Bypass
disable» is selected.