61
Inverter specifications
30 kVA
40 kVA
50 kVA
60 kVA
80 kVA
Power factor
1
Permitted crest factor
3:1
Overload
110% ~ 125% (for 10 min.)
125% ~ 135% (for 5 min.)
135% ~ 150% (for 1 min.)
> 150% (immediate transfer to bypass)
Overcurrent limit
300 %
Output THDv
≤ 1% (linear load) / < 4.0 (non-linear load)
Maximum synchronism speed
10.0 Hz/s (default value)
Inverter voltage range
± 5 %
Tab. 19.
Inverter characteristics
9.4.5. Communications
Communication specifications
Parameters
Communication port 1
RS 232 / RS 485
Communication port 2
USB
Expansion slot 1
NIMBUS card
Expansion slot 2
Free slot (*)
Digital inputs
4 inputs
Relay interface
4 programmable relays
Protocol
MODBUS RTU
Display
5" touchscreen
EPO function
2-pole normally closed contact
(*) Options:
- SNMP.
- RS232, RS485, USB.
- AS400 (relay extension).
- Remote battery temperature.
Tab. 20.
Communications available.
9.4.6. Efficiency
Efficiency specifications
30 kVA
40 kVA
50 kVA
60 kVA
80 kVA
General efficiency in battery mode (> 25% charge)
up to 96.5%
General efficiency in normal mode
up to 96.2%
Heat losses, normal mode, 100% charge (W)
1470
1920
2300
2700
3680
Air volume for cooling (m3/hour)
427
854
Tab. 21.
Efficiency characteristics
SLC CUBE4
- UNINTERRUPTIBLE POWER SUPPLY SYSTEM
-
USER MANUAL
Содержание SLC CUBE4
Страница 1: ...30 80 kVA USER MANUAL...
Страница 66: ...66 SALICRU...
Страница 67: ...67 SLC CUBE4 UNINTERRUPTIBLE POWER SUPPLY SYSTEM USER MANUAL...
Страница 68: ...68 SALICRU...
Страница 69: ...69 SLC CUBE4 UNINTERRUPTIBLE POWER SUPPLY SYSTEM USER MANUAL...