background image

20

SALICRU

Model

Rated voltage  

of batteries

Minimum values,  

fast type fuses 

DC voltage (V)

Current (A)

SLC-700-TWIN RT2

(12 V x 3) = 36 V

125

20

SLC-1000-TWIN RT2

32

SLC-1500-TWIN RT2

50

SLC-2000-TWIN RT2

(12 V x 4) = 48 V

SLC-3000-TWIN RT2

(12 V x 6) = 72 V

SLC-4000-TWIN RT2

(12 V x 16) = 192V

400

20

SLC-5000-TWIN RT2

32

SLC-6000-TWIN RT2
SLC-8000-TWIN RT2

40

SLC-10000-TWIN RT2

50

Tab. 2. 

Protection features between device and battery 

module.

 

Before starting the connection process between 

battery module or modules and device, check that 

the device and loads are ‘Off’.

Also, when the batteries are installed by the user 

independently, the protection fuse or isolator must be 

deactivated.

 

Connection of the battery module to the device is made by 

means of a cable featuring polarised connectors at both 

ends, which is supplied with the first one. Two connectors 

are available for this purpose on the device and battery 

module.

Similarly, the battery modules feature two connectors that 

allow the linking of modules in parallel.

 

Each battery module is independent for each device. 

Two devices must not be connected to the 

same battery module

.

Likewise, in parallel systems (4 to 10 kVA models), with 

each device connected to its battery module or modules, 

they should be considered as single devices that are 

independent of each other.

 

Fig. 13 shows the connection of a 10 kVA device in a 

rack arrangement with two battery modules. For a larger 

number, proceed in a manner similar to those shown in the 

illustration.

Fig. 13. 

Connection to battery modules.

5.2.4.  Connection of the input earth terminal 

(

)

 and the 

earth connection terminal 

(

)

 .

 

As the device has Class I protection against electric 

shock, it is essential to install a protective earth 

conductor (connect earth (

)). Connect this conductor 

before supplying voltage to the input terminals.

 

Make sure that all of the loads connected to the UPS are only 

connected to its earth connection terminal (

). Failure to 

limit the earthing of the load or loads and battery module or 

modules to this 

single point

 will create earth return loops 

that will degrade the quality of the power supplied.

 

All terminals identified as an earth connection (

) are 

connected to each other, to the earth terminal (

) and to 

the device’s earth.

5.2.5.  Terminals for EPO (emergency power off).

 

The UPSs have two terminals for the installation of an 

external emergency power off (EPO) output button.

 

The device is dispatched from the factory with its EPO 

circuit set to closed (NC) by default. In other words, the 

UPS will cut the output power supply, emergency power 

off, when the circuit is opened:

 

ˆ

Either by removing the female connector from the socket 

where it is inserted. This connector has a cable connected 

as a jumper that closes the circuit (see Fig. 14-A).

 

ˆ

Or by pressing the button external to the device 

belonging to the user installed between the terminals 

of the connector (see Fig. 14-B). The connection on the 

button must be in the normally closed contact (NC), so 

it will open the circuit when activated.

The reverse functionality can be selected through the 

communications software and control panel.

Except for specific cases, we advise against this type 

of connection in view of the purpose of the EPO button, 

since it will not act upon an emergency request if either 

of the two cables that run from the button to the UPS is 

accidentally cut.

By contrast, this anomaly would immediately be detected 

in a closed EPO circuit, with the inconvenience of an 

unexpected cut in the powering of the loads, but a 

guarantee of effective emergency functionality.

 

To recover the normal operating state of the UPS, it is 

necessary to insert the connector with the jumper in its 

receptacle or deactivate the EPO button. The device will 

be operational.

A

B

Fig. 14. 

Connector for external EPO.

Содержание SLC-700-TWIN RT2 (B0)

Страница 1: ...SLC TWIN RT2 0 7 10 kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL...

Страница 2: ...caltower typemountingwithPDU 5 1 5 7 Rackmountingin19 cabinetwithPDU 5 1 5 8 Preliminaryconsiderationsbeforeconnection 5 1 5 9 Preliminary considerations before connection regarding the batteriesandth...

Страница 3: ...2 4 3 Warningoralertcodes 7 2 4 4 Errororfaultcodes 7 2 4 5 Warningoralertindicators 7 3 CONTROLPANELFOR4KVATO10KVAMODELS 7 3 1 Audiblealarms 7 3 2 Opticalindications 7 3 3 Locationoftheadjustmentpar...

Страница 4: ...ed personnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images...

Страница 5: ...sioning to be performed in a simple and orderly manner without having any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save the documentation downloaded...

Страница 6: ...duct may cause radio interference in which case the user must take additional measures SLC TWIN RT2 4 10 kVA This is a category C3 UPS This is a product for commercial and industrial application in th...

Страница 7: ...self will always prevail The nameplate of the device shows all of the values relating to its main properties and characteristics Act accordingly for its installation 0 7 to 3 kVA models 4 to 10 kVA mo...

Страница 8: ...grammable at disconnection for non critical loads Connector for connection to external battery module Standard and B1 3 kVA models COM port USB RS232 COM port AC power IEC connector Smart slot protect...

Страница 9: ...ry module connector Fig 3 Rear view of battery modules for extended backups PDU for 4 to 6 kVA devices Output circuit breaker Output IEC connectors Output circuit breaker Output IEC connectors PDU for...

Страница 10: ...without batteries but with a space reserved for installation in the same box for models whose standard version specifies this For other models the battery pack will be installed in the manner conside...

Страница 11: ...ains contact T S S With the inverter shut down the output supplies mains power directly through the static bypass of the device provided that it has AC input power Frequency converter CF mode Operatin...

Страница 12: ...hout interruptions to the power supply of the protected system while preventing unnecessary hazards for the technical personnel 4 5 3 Communication card The UPS features a slot at the rear for inserti...

Страница 13: ...PS 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic pieces to extend the base of the UPS and enab...

Страница 14: ...distance is considerable it is recommended to transport the device in its packaging to the installation site and then unpack it 5 1 5 Siting immobilising and considerations All TWIN RT2 series UPSs ar...

Страница 15: ...the guides at the required height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto the guides and insert it all t...

Страница 16: ...he upper or lower part of the cabinet it is recommended that two people carry out the installation operations Fix the UPS and the battery module to the cabinet frame by means of the screws supplied wi...

Страница 17: ...n of the cables must always be considered in relation to the size of the terminals of the switches so that they are correctly fastened across their entire cross section for optimum contact between the...

Страница 18: ...nnecting systems in parallel only in models 3 kVA To access the signal block it is necessary to remove its protective cover Slot for the integration of one of the optional electronic communication uni...

Страница 19: ...g 2 as critical loads will be reserved Take into account that they are set by default as critical loads The 3 kVA models also have a 16A IEC connector that enables the connection of a load of the tota...

Страница 20: ...voltage to the input terminals Make sure that all of the loads connected to the UPS are only connected to its earth connection terminal Failure to limit the earthing of the load or loads and battery...

Страница 21: ...of each UPS In the event of acquiring a manual bypass board through another conduit check that it has this auxiliary contact and connect it to the terminal block of the UPS or each device in parallel...

Страница 22: ...ngth between the input and output cables of the device must be less than 20 When the distance between the UPSs in parallel and the circuit breaker board is more than 20 metres the difference in length...

Страница 23: ...rom each other Fig 20 View of ViewPower s main screen Installation procedure Go to the web page http support salicru com Select the required operating system and follow the instructions described on t...

Страница 24: ...and output protections to On Turn the battery switch to On models B0 and B1 Turn the device s input circuit breaker to On Press the ON button for more than 2 seconds the audible alarm will sound for...

Страница 25: ...t will be necessary to adapt the board or acquire a new one if it has not been previously anticipated Since it is necessary to change the parallel bus connection to incorporate the new device into the...

Страница 26: ...ible accidents To prevent incorrect operations it is necessary to fit the mechanical lock and the covers of the manual bypass mechanisms and their fixing screws Press the ON button on all of the UPSs...

Страница 27: ...ted to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P1 Indicates that the programm...

Страница 28: ...ESC ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated bac...

Страница 29: ...hrough the menu structure in relation to the point where it is located accessing the following variable with each press OFF ENTER UPS shutdown Press this button for at least 2 seconds Confirmation of...

Страница 30: ...ctly related to the capacity of the battery pack The charger will adapt the charging factor automatically according to the value of the total capacity entered up to the maximum of the current that is...

Страница 31: ...60 1 CF with output frequency of 60 Hz 1 With parameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enabled DIS Bypass disabled wit...

Страница 32: ...the output voltage from the bypass in ECO mode energy saving LCD display CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 o...

Страница 33: ...oo low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code 7 2 4 5 Warning or alert indicators Code...

Страница 34: ...e menu structure to the previous variable in relation to the point where it is located ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to con...

Страница 35: ...odes list Description and settings Code 01 Output voltage Fig 27 Parameter 3 setting Output voltage It is possible to choose one of the following values for the output voltage between phase and neutra...

Страница 36: ...Bypass enabled When selected bypass mode is enabled DIS Bypass disabled If selected automatic bypass is permitted but not manual switch to bypass At this point manual switch to bypass is understood as...

Страница 37: ...external battery pack of 45 Ah belonging to it 45 Ah 7 Ah 6 4 When rounding down value 6 must be entered in parameter 3 The basic reason for adjusting the setting is as follows without it affecting t...

Страница 38: ...n the regulation ranges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD display ECO CF mode Description When the output frequency is selecte...

Страница 39: ...switch cover open 3D Bypass not available 3E Start up fault Tab 20 Warning or alert code 7 3 4 4 Error or fault codes Code Error or fault description 01 DC bus start up fault 02 DC bus overvoltage 03...

Страница 40: ...nal which is in turn connected to earth any metal part of the device Repair and or maintenance work must be carried out by our T S S except for the replacement of batteries which can be performed by q...

Страница 41: ...After repeated overloads the UPS is locked in Bypass mode The connected loads are powered directly from the mains Disconnect the excess loads from the output sockets shut down the device and restart i...

Страница 42: ...of the following fault codes 01 02 03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS Thi...

Страница 43: ...load in ECO mode 95 96 97 99 Overload in line mode 110 130 5 min 100 110 2 min 130 140 30 sec 110 130 1 min 140 150 1 5 sec 130 1 sec 150 100 ms Overload in battery mode 110 130 2 min 100 110 30 sec 1...

Страница 44: ...ill be 78 of the rated 6 As a frequency converter the power supplied will be 60 of the rated DSP Digital signal processor A DSP is a processor or microprocessor based system that has a set of instruct...

Страница 45: ...ht spectrum to infrared the latter called IRED infra red emitting diode Circuit breaker A circuit breaker is a device capable of interrupting the electrical current of a circuit when it exceeds certai...

Страница 46: ...46 SALICRU...

Страница 47: ...47 SLC TWIN PRO2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL...

Страница 48: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Отзывы: