background image

7

Smarty 2X/3X P

www.salda.lt

operational limits

power consumption

Smarty 2X P

Smarty 3X P

Supply air

Supply air

60

50

40

30

20

10

0

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

60

50

40

30

20

10

0

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

50

14

150

42

200

250

56

69

300

83

v [m /h]

3

Δ P

[Pa]

stat

v [l/s]

Δ P

[Pa]

stat

v [l/s]

v [m /h]

3

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

v [m /h]

3

Δ P

[Pa]

stat

v [l/s]

Δ P

[Pa]

stat

v [l/s]

v [m /h]

3

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Exhaust air

Exhaust air

60

50

40

30

20

10

0

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

60

50

40

30

20

10

0

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

50

14

150

42

200

250

56

69

300

83

v [m /h]

3

Δ P

[Pa]

stat

v [l/s]

Δ P

[Pa]

stat

v [l/s]

v [m /h]

3

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

v [m /h]

3

Δ P

[Pa]

stat

v [l/s]

Δ P

[Pa]

stat

v [l/s]

v [m /h]

3

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Specific fan power (SFP)

Specific fan power (SFP)

60

50

40

30

20

10

0

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

60

50

40

30

20

10

0

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

50

14

150

42

200

250

56

69

300

83

v [m /h]

3

Δ P

[Pa]

stat

v [l/s]

Δ P

[Pa]

stat

v [l/s]

v [m /h]

3

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

v [m /h]

3

Δ P

[Pa]

stat

v [l/s]

Δ P

[Pa]

stat

v [l/s]

v [m /h]

3

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Temperature efficiency

Temperature efficiency

60

50

40

30

20

10

0

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

60

50

40

30

20

10

0

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

600

500

400

300

200

100

50

14

150

42

200

250

56

69

300

83

50

14

150

42

200

250

56

69

300

83

v [m /h]

3

Δ P

[Pa]

stat

v [l/s]

Δ P

[Pa]

stat

v [l/s]

v [m /h]

3

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

v [m /h]

3

Δ P

[Pa]

stat

v [l/s]

Δ P

[Pa]

stat

v [l/s]

v [m /h]

3

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Δ P

[Pa]

stat

v [m /h]

3

v [l/s]

P [W]

Temperature  efficiency (balanced mass flow):

Extract air = 20 °C/60 % RH 

Outdoor air = -7 °C / 2 °C / 7 °C

Содержание Smarty 2X P

Страница 1: ...Subject to technical modification Smarty 2X 3X P_MI_P0112_AZ_0002 AHU WITH HEAT RECOVERY Smarty 2X P Smarty 3X P Mounting and installation instructions...

Страница 2: ...quipment 16 Mounting 16 Mounting positions 16 Drainage 17 Connection of air ducts 20 Wiring Diagram 20 Connection of accessories 21 Controller miniMCB EX1 V1 0 21 Outdoor Air Pre Heater 25 Outdoor Air...

Страница 3: ...f installation of electric appliances It is forbidden to turn on and use unearthed device Follow the requirements of the device s labels that indicate Danger Warnings Connection of electricity and mai...

Страница 4: ...ion only Required ambient temperatures must be from 5 o C to 40 o C For the cold climate zones air temperatures below 5 o C integrated or optional pre heater is required Not suitable for swimming pool...

Страница 5: ...223 mm Smarty 3X P 1225 mm 408 5 mm G3 8 150 mm 324 mm 21 3 mm 150 160 mm 1381 5 mm 685 5 mm 128 mm 128 mm 429 5 mm Smarty 2X P Smarty 3X P Weight without package and accessories kg 30 53 With respec...

Страница 6: ...85 0 75 0 085 0 75 speed min 1 4525 4525 4525 3200 3200 3200 control input VDC 0 10 0 10 0 10 0 10 0 10 0 10 protection class IP 44 IP 44 IP 44 IP 54 IP 54 IP 54 insulation class B B B B B B Supply ai...

Страница 7: ...Pa stat v l s v m h 3 P Pa stat v m h 3 v l s P W P Pa stat v m h 3 v l s P W Specific fan power SFP Specific fan power SFP 60 50 40 30 20 10 0 600 500 400 300 200 100 50 14 150 42 200 250 56 69 300 8...

Страница 8: ...negative pressure in premises Place of operation Indoors outdoors indoors and outdoors outdoors with special accessories Operation in explosive environment impossible Transporting of the polluted air...

Страница 9: ...versions 5 Control board 6 CE7 7 power supply cable 3m supply air sensor TJ 7 Pressure sensor only Smarty 3X P 1 1 2 pcs 8 Supply air fan PV 9 Air flow marking 10 Flange 4 pcs 11 Condensate tray 12 Ex...

Страница 10: ...e MB Gateway PRGPU082 Legs Smarty 2X P legs GAGKS MARTY168_1005_0 Condensate pump MAXI BLUE SET PRGSIK002 Channel humidity transmitter S KFF U ZAKKT0051 Humidity transmitter RH S RFF U D F2 ZAKKT0050...

Страница 11: ...B Gateway PRGPU082 Filters MPL G4 ZFEPF109 MPL F7 pasirenkamas ZFEPF108 Legs Smarty 3X P legs GAGKS MARTY168_1000 Clamps AP 150 GAPAP003 AP 160 GAPAP004 Ventilation grille ALU 160 GGRALU003 Condensate...

Страница 12: ...cables connection boxes air extract or exhaust flanges Avoid hits and shock overloads Before installation units must be stored in a dry room with the rela tive air humidity not exceeding 70 at 20 C an...

Страница 13: ...Outdoor air temperature sensor Ptouch Control panel TE Exhaust air temperature sensor shall be ordered separately Stouch Control panel PIR Motion detector M2 Outdoor air damper actuator DJ Smoke dete...

Страница 14: ...temperature sensor shall be ordered separately Stouch Control panel PIR Motion detector M2 Outdoor air damper actuator DJ Smoke detector M3 Exhaust air damper actuator WSG Supply and exhaust air gril...

Страница 15: ...xhaust air temperature sensor shall be ordered separately Stouch Control panel PIR Motion detector M2 Outdoor air damper actuator DJ Smoke detector M3 Exhaust air damper actuator WSG Supply and exhaus...

Страница 16: ...t for opening of the maintenance door and filter covers If the installed ventilation unit is adherent to the wall it may transmit noise vibrations to the premises Though the level of noise caused by t...

Страница 17: ...of not less than 3 1 meter of a pipe shall be inclined down by 60 mm Before turning on the heat recovery unit 1 it is necessary to pour 0 5 l of water or more pipe loop 3 should always be full and to...

Страница 18: ...nage it is necessary to remove a plate VI in a metal part of the housing and make a hole The cover I III should be removed and a bath IV V caps should be removed from the hole Condensate drainage must...

Страница 19: ...teral condensate drainage it is necessary to remove a plate III in a metal part of the housing and make a hole The cover I should be removed and a bath II caps should be removed from the hole Condensa...

Страница 20: ...hould be installed further from potential air pollution sources Use holders while installing air ducts next to the ventilation equipment They suppress vibration and assure a firm installation of vario...

Страница 21: ...24VDC_P 3 3V_1W DI4 TACHO2_K DI3 TACHO2_A TACHO1_K DI2 TACHO1_A DI5 12VDC DI6 12VDC DI7 12VDC 12VDC DI8 AI4 NTC GND GND AI3 NTC GND AI2 NTC GND AI1 NTC DI9 3 3V_1W DI10 3 3V_1W AI4 0 10V GND GND 24VDC...

Страница 22: ...ontrol 2 STEP_B 3 STEP_B 4 STEP_A 5 STEP_A 6 24VDC_P X4 1 DI2 TACHO1_A Supply fan speed RPM 2 TACHO1_K 3 DI3 TACHO2_A Extract fan speed RPM 4 TACHO2_K 5 DI4 Fire protection input NC 6 3 3V_1W X5 1 DI5...

Страница 23: ...GND 3 PE X10 1 PE Electric Water Heater power line circulation pump max 0 6kW 2 DO1 L L2 _2 3 N L1 _2 X11 1 N L1 _2 230VAC Power supply for X10 and X12 2 L L2 _2 3 PE X12 1 PE Preheater power line max...

Страница 24: ...ig 3 EX1 controller zones B Connector Contactor No Contactor name Functional block name miniEX1 X19 1 AI1 0 10V A1 Supply air CO2 or RH input 0 10VDC 2 GND 3 24VDC X20 1 GND Electric Water heater cont...

Страница 25: ...60 ON OFF EKA 160 2 0 1f PSIEKA16004 SP59 0 10V EKA NIS 160 2 0 1f PSIEKANIS09 SP58 Smarty 3X P up to 10 245 10 5 88 160 ON OFF EKA 160 1 0 1f PSIEKA031 SP59 0 10V EKA NIS 160 1 0 1f PSIEKANIS03 SP58...

Страница 26: ...nnection scheme 12 04 2016 06 23 2016 06 23 2016 06 23 PE L N PE K1 1 2 3 4 5 6 K1 A1 A2 X5 1 DI5 X5 2 12VDC X5 3 DI6 X5 4 12VDC miniMCB V0 2 AT1 AT1 RT1 RT1 X5 1 DI5 X5 2 12VDC X5 3 DI6 X5 4 12VDC mi...

Страница 27: ...V control is chosen heater voltage supply circuit can be connected to the controller s relay output up to 0 6 kW Greater power is con nected using external commutation components Heater Capacity by Re...

Страница 28: ...2X 3X P 1 2 1 3 D zone X10 and A zone X5 of automation controller KE Mini MCB TJ 0 10V SP55 DRAWN BY CHECKED BY SIGNATURE DUTIES NAME DATE UAB SALDA Drawing Book CHECKED BY 1 1 2 3 4 4 5 6 7 7 Externa...

Страница 29: ...Power over 0 6 kW 1f miniMCB1 miniMCB1 SP60 DRAWN BY CHECKED BY SIGNATURE DUTIES NAME DATE UAB SALDA Drawing Book CHECKED BY 1 1 2 3 4 4 5 6 7 7 External heater SP60 KE 0 10V V1 1 Principle connection...

Страница 30: ...xternal heater SP61 KE On Off V1 1 Principle connection scheme 1 0 2016 06 23 2016 06 23 2016 06 23 PE L N KE1 X10 1 PE X10 2 DO1 L L2 X10 3 N L1 miniMCB V0 2 X10 1 PE X10 2 DO1 L L2 X10 3 N L1 miniMC...

Страница 31: ...ram 13 15 p Wiring diagram Automation controller D zone Upon activation of output X13 3 the dampers shall open Upon activation of output X13 4 the dampers shall close Exhaust ait temperature sensor Ex...

Страница 32: ...stalled inside supply air duct Wiring diagram Automation controller B zone X19 Supply air CO2 or RH input 0 10VDC 24VDC GND 1 2 3 AI1 0 10V Vin GND AO1 Transmitter 2 Extract air CO2 or RH input 0 10VD...

Страница 33: ...duct Tool for drilling holes are required for its installation CO 2 concentration ppm 3000 Effect on an individual 2500 2000 Reduced concentration drowsi ness headache etc 1500 1000 Pettenkofer limit...

Страница 34: ...to the rules on installing electrical equipment It is prohibited to use extension wires cables and power network plug socket distribution devices Prior to carrying out any ventilation unit installati...

Страница 35: ...rs etc earthing and protection systems are properly installed condition of all seals and sealing surfaces is proper Failure Cause Explanation corrective actions Unit is not operating No supply voltage...

Страница 36: ...36 Smarty 2X 3X P www salda lt...

Отзывы: