6
RIRS 1900VE/VW EKO 3.0
www.salda.lt
[ lt ]
[ dk ]
[ en ]
[ de ]
- Maintenance and repair should only be per-
formed by experienced and trained staff.
- The fan should be inspected and cleaned if
needed at least once a year.
- Be sure the fan is disconnected from power
source before performing any maintenance
or repair.
- Proceed to maintenance and repair after any
rotation in the fan stopped.
- Observe staff safety regulations during main-
tenance and repair.
- The motor is of heavy duty ball bearing con-
struction. The motor is completely sealed and
requires no lubrication for the life of the motor.
- Detach fan from the unit (a-b-c-d).
- Impeller should be specially checked for
buil-up material or dirt which may cause an
imbalance. Excessive imbalance can lead to ac-
celerated wear on motor bearings and vibration.
- Clean impeller and inside housing with mild
detergent, water and damp, soft cloth.
- Do not use high pressure cleaner, abrasives,
sharp instruments or caustic solvents that may
scratch or damage housing and impeller.
- Montage und Elektroarbeiten nur durch aus-
gebildetes und eingewiesenes Fachpersonal
und nach den jeweils zutreffenden Vorschriften
ausführen.
- Die Anlage muss min. einmal pro Jahr geprüft
und gereinigt werden.
- Vor der Wartung oder Reparatur sicherstellen,
dass die Anlage vom Stromnetz getrennt ist.
- Arbeiten dürfen nur bei abgeschaltetem und
mechanischem Stillstand des Laufrades sowie
nach Abkühlung der Heizung vorgenommen
werden! Gegen Wiedereinschalten sichern!
- Arbeitssicherheitsregelungen bei der tech-
nischen Bedienung beachten.
- In der Motorkonstruktion sind hochwertige
Lager eingebaut. Die Lager sind eingepresst
und erfordern keine Schmierung.
- Ventilator von der Anlage abschalten (a-b-
c-d).
- Die Flügel vom Ventilator auf Ablagerungen
und Staub prüfen, starke Verschmutzung kann
zu Unwucht führen. Die Unwucht verursacht
eine Vibration und schnelleren Lagerverschleiß.
- Flügel und Gehäuse mit einem sanften Rei-
Unplug unit from mains first and wait for 2
minutes (till fans fully stop) before opening
the covers.
Bevor die Gerätetüren geöffnet werden dürfen,
Gerät elektrisch vom Versorgungsnetz trennen
und etwa 2 Min. warten, bis die Ventilatoren
völlig stehen bleiben.
Prieš atidarydami agregato duris būtinai atjun-
kite elektros srovę ir palaukite, kol pilnai nustos
suktis ventiliatoriai (apie 2 min.).
Anlægget kobles fra strømforsyningen, vent
ca. 2 minutter til ventilatorerne er stoppet helt
før dækslerne åbnes.
Dirt increases air resistance in the filter, there-
fore less air is supplied into the premises.
- It is advisable to change the filters every 3-4
months, or in accordance with the readings of
filter contamination sensor. (Sensor PS 600 is
integrated in the unit).
Verunreinigte Filter erhöhen die Druckverluste,
d.h. ein geringeres Luftvolumen gelangt in die
Räume.
- Die Filter werden ca. alle 3 Monate bzw. je
nach Signal der Filterüberwachung ersetzt. (Die
Druckdosen PS600B sind im Gerät eingebaut).
Užsiteršę filtrai, didina oro pasipriešinimą, dėl
to sumažėja į patalpas paduodamo oro kiekis.
- Filtrus patartina keisti kas 3-4 mėnesius arba
pagal filtro užterštumo jutiklio parodymus (juti-
klis PS 600 integruotas į agregatą).
Snavs øger luftmodstanden i filtret, hvorefter
mindre luft blæses ind i lokalerne.
- Det er tilrådeligt at skifte filtre hver 3-4 må-
neder, eller i overensstemmelse med signal
fra filtervagten. (Sensor PS 600 er integreret
i anlægget).
- Aptarnavimo darbus turėtų atlikti tik patyrę ir
apmokyti darbuotojai.
- Ventiliatorius turi būti apžiūrimas ir valomas
mažiausiai 1 kartą per metus.
- Prieš pradedant aptarnavimo ar remonto
darbus įsitikinkite, ar įrenginys atjungtas nuo
elektros tinklo.
- Aptarnavimo darbus pradėkite tik sustojus
bet kokiam judėjimui ventiliatoriuje.
- Vykdydami techninio aptarnavimo darbus lai-
kykitės visų darbo saugos taisyklių.
- Variklio konstrukcijoje panaudoti aukšto na-
šumo guoliai. Jie yra užpresuoti ir nereikalauja
jokio tepimo per visą variklio tarnavimo laiką.
- Atjunkite ventiliatorių nuo įrenginio (a-b-c-d).
- Būtina kruopščiai apžiūrėti ventiliatoriaus
sparnuotę, ar nesusidarė dulkių ir kitokių me-
džiagų apnašos, galinčios išbalansuoti spar-
nuotę. Išbalansavimas sukelia vibraciją ir grei-
tesnį variklio guolių susidėvėjimą.
- Nuvalykite sparnuotę ir korpuso vidų švelniu,
netirpdančiu bei korozijos neskatinančiu plovi-
kliu ir vandeniu.
- Valydami sparnuotę nenaudokite aukšto
- Vedligeholdelse og reparation bør kun udføres
af erfarent og uddannet personale.
- Ventilatoren skal inspiceres og rengøres efter
behov dog mindst en gang årligt.
- Vær sikker på at blæseren er koblet fra
strømforsyningen og ventilatoren er stoppet helt,
før der udføres vedligeholdelse eller reparation.
- Alle sikkerhedsforskrifter skal overholdes
under udførsel af vedligeholdelse og reparation.
- Motoren er konstrueret med stærke kuglelejer.
Motoren er fuldstændig forseglet og kræver
ingen smøring.
- Frigør ventilatoren fra enheden (1-2-3).
- Kontroller ventilatoren for snavs og støv, kraf-
tig forurening kan forårsage ubalance. Ubalance
forårsager hurtigere slid på kuglelejerne.
- Rengør ventilatoren og husets inderside
med en blød klud med et mildt rengøringsmid-
del og vand.
- Brug ikke højtryksspuler, slibemidler, skarpe
instrumenter eller ætsende opløsningsmidler,
der kan ridse eller ødelægge hus og ventilator.
- Ventilatoren må ikke lægges i nogen væske.
- Ved rengøring beskyttes motor mod vand
Tiekiamas oras
Indblæsning
Supply
Zuluft
- temperatūra min./maks.
- temperatur min/max
- temperature min./max.
- Temperatur min./max.
[°C]
-23 / +40
- maks. drėgmė
- luftfugtighed max
- max. humidity
- max. Feuchtigkeit
[%]
90
Lent. 1
Таb. 1
Tab. 1
Tab. 1
Ištraukiamas oras
Udsugning
Extract
Abluft
- temperatūra min./maks.
- temperatur min/max- tem-
perature min./max.
- Temperatur min./max.
[°C]
+15 / +40
- maks. drėgmė
- luftfugtighed max
- max. humidity
- max. Feuchtigkeit
[%]
60
be cinkui, plastmasei, gumai agresyvių medžia-
gų; be kietų, lipnių bei pluoštinių medžiagų da-
lelių) orą iš patalpos.
Darbinė Ištraukiamo ir tiekiamo oro tempera-
tūra bei drėgmė nurodyta lentelėje (Lent.1)
forårsage korrosion af metal, eller er aggres-
sive overfor zink, plast og gummi og uden faste,
klæbrige eller fiberholdige partikler).
Temperatur og luftfugtighed er angivet i tabel 1.
corrosion, of substances aggressive to zinc,
plastic and rubber, and of particles of solid,
adhesive and fibred materials).
The working extract and supply air temperatu-
res, and humidity are given in the table (Tab. 1).
ausschließlich sauberer Luft (ohne chemische
Verbindungen, die Metallkorrosion hervorrufen;
ohne aggressive Substanzen, die Zink, Kunst-
stoff und Gummi angreifen; ohne Partikeln von
festen, klebenden sowie faserigen Materialien)
in den/aus dem Raum gefertigt und bestimmt.
Abluft- und Zulufttemperatur sowie -feuchti keit
sind in der Tabelle (Tab.1) angegeben.
Esant žemesnei tiekiamo oro temperatūrai
nei -23 °C rekomenduojama naudoti elektrinį
pašildytuvą.
Darbo aplinkos temperatūra privalo būti nuo
+5 iki +40
o
C.
Lauke eksploatuojami vėdinimo įrenginiai pra-
dedami naudoti tik tada, kai užtikrinamos ga
mintojo nustatytos privalomos sąlygos:
• Įrenginiai, kurie prieš sumontuojant yra san-
dėliuojami objekte, turi būti užsandarinti papil-
domomis priemonėmis, kad įrenginio viduje
nesikauptų drėgmė.
• Jei įrenginys sumontuojamas ir nepalei-
džiamas pastoviai veikti, privaloma užtikrinti,
kad per ortakius į vėdinimo įrenginį nepatektų
šiltas/drėgnas oras ir drėgmė nesikondensuotų
įrenginyje.
• Ilgai neeksploatuojant ar retai jungiant vė-
dinimo įrenginius privaloma visu galingumu
1/24h prapūsti - džiovinti sistemą.
• turi būti instaliuota ir įjungta įtampa į agregato
automatiką, vandeninių gaminių sistema pripil-
dyta glikolio/vandens.
Nesilaikant šių reikalavimų gamintojas turi
teisę gedimo atveju netaikyti garantijos dėl
atsiradusios drėgmės/vandens sugadintuose
komponentuose.
Ved temperatur under -23
o
C anbefales det at
anvende en el-forvarmer.
Operationel temperatur skal være mellem
5-40 ° C.
De lufthåndteringsenheder der er installeret
udendørs, må kun startes når de følgende
obligatoriske betingelser som er fastlagt af
producenten, er opfyldt:
• Enheder som opbevares på byggepladsen
før de installeres, skal forsegles med yderligere
midler for at undgå ophobning af fugtighed inde
i enheden.
• Hvis enheden installeres og ikke startes til
kontinuerlig drift, skal det sikres at der ikke
kommer varm eller fugtig luft ind i enheden via
luftkanaler, og at ingen fugtighed kondenserer
inde i enheden.
• Hvis ventilationsenhederne står stille i længere
tid eller startes sjældent, skal systemet blæses
igennem med maksimal kapacitet 1/24 t. for
at affugtes.
• Strømforsyning til enhedens automatik er
installeret og tilsluttet, og ved vandprodukter er
systemet fyldt med glykol/vand.
I tilfælde af manglende overholdelse af de
ovenstående krav er producenten berettiget
ikke at lade garantien gælde i forbindelse med
forekomst af fugtighed eller vand i beskadigede
komponenter.
It is recommended to use electrical pre-heater
if the supply air temperature is below -23
o
C.
Required ambient temperatures must be from
+5
o
C to +40
o
C.
The air handling units installed outdoors shall be
started only when the following obligatory condi-
tions established by the manufacturer are met:
• Units that are stored at the site before instal-
lation shall be sealed using additional means in
order to prevent the accumulation of moisture
inside the unit.
• If the unit is installed and is not started for
ontinuous operation, it must be ensured that no
warm/humid air enters the unit through air ducts
and that no moisture condensates inside the unit.
• If the ventilation units stand idle for a long
time or are started infrequently, the system must
be blown down at the maximum capacity 1/24
h to dehumidify.
• Voltage to the automatics of the unit is installed
and connected; the system of water products is
filled with glycol/water.
In case of failure to comply with the require-
ments set out above, the manufacturer shall have
the right not to apply the warranty in respect of
the occurrence of moisture/water in damaged
components.
Bei Außentemperaturen unter -23 °C ist es zu
emphehlen ein Vorheizrgeister zu benutzen.
Temperatur der Arbeitsumgebung muss im
Bereich von +5…+40 °C liegen.
Die im Freien betriebenen Lüftungseinrichtun-
gen werden nur dann eingeschaltet, wenn alle
obligatorischen, durch Hersteller angegebenen
Bedingungen gewährleistet sind. Die Bedin-
gungen sind:
• Die bevor Montage in Baustelle gelagerten
Einrichtungen sollen zusätzlich verdichtet
werden, um die Feuchtigkeitsansammlung in
Einrichtung zu vermeiden.
• Wird die Einrichtung montiert, doch instand
nicht gesetzt, so soll der Durchfluss von warmer
bzw. feuchter Luft in Lüftungseinrichtungen
verhindert werden, um Kondensatansammlung
in Einrichtung zu vermeiden.
• Werden die Lüftungseinrichtungen nur selten
betrieben oder Betriebspausen ausgesetzt, so ist
das System einmal in 24 Stunden mit maximaler
Leistung zu belüften und zu trocknen.
• Die Steuerungselektronik der Lüftungsein-
richtung ist montiert und stromgespeist. Das
Wassersystem ist mit Mischung von Glykol und
Wasser befüllt.
Der Hersteller übernimmt keine Gewähr-
leistung, die im Folge der Nichtbeachtung
oben genannten Anweisungen und daraus
resultierenden Einrichtungsbeschädigungen
durch Feuchtigkeits-bzw. Wassereinwirkung
entstehen.