Salamander Pumps Right Pump Series Скачать руководство пользователя страница 13

13

Helpful    

Guidelines - 

Cold Water Supplies and 

Storage

Aeration of pump and 

cylinder from a cold water 

storage tank

This occurs when the incoming cold mains ball 

valve is positioned above the cold feeds to the 

cylinder and to the pump – aerated water is 

drawn into the pump as illustrated.

Figure 15: Aeration

Chronic aeration of the pump occurs when this 

problem is combined with inadequate storage 

capacity and/or when the volume of water 

drawn by the pump and other services exceeds 

the refill rate and creates a vortex which draws 

air and possibly debris into the pump.

 

Cold storage usable capacity

The usable capacity of cold storage is easily 

calculated as the capacity of water in the cold 

tank above the cold feeds to the cylinder, the 

pump and other outlets – see formula.

Formula for calculation on 

rectangular tank:

Depth (15”) x width (23”) x length (36”)
= 12,420 cu inches
Volume cu inches (12,420) x 0.01639
= 203.56 litres
Volume litres (203.56) x 0.22
= 44.78 gallons.

Formula for calculation on 

circular tank:

Depth (15”) x radius (17”) x radius (17”)
x 3.142 (Pi)
= 13,621 cu inches
Volume cu inches (13,621) x 0.01639
= 223 litres
Volume litres (223) x 0.22
= 49 gallons.

Figure 16

The bottom of the cold 

Scan QR to learn more

Содержание Right Pump Series

Страница 1: ...d warranty guide for the Right Pump range ISSUE 21 Oct 2021 This document should be given to the end user and retained for future reference Should you need to contact Salamander Pumps you will need th...

Страница 2: ...regarding installation The back cover explains the methods to register your pump for the 3 year warranty Please leave this installation guide with the customer for reference to maintenance safety info...

Страница 3: ...surevesselinstallation TypicalInstallations RightPumpUniversal 10 Commissioning 12 HelpfulPumpWiseGuidelines 13 ColdWaterSuppliesandStorage Hot WaterBlendingValve 14 HelpfulPumpWiseGuidelines 15 Water...

Страница 4: ...bar pressure only exception are the RP50TU and the RP55SU which is in 5m equivalent to 50kPa 0 5 bar pressure We recommend the pump is activated for at least 5 minutes every 4 weeks to exercise all m...

Страница 5: ...tres of 15mm pipe All up and over pipe work must be vented at the highest point on the outlet of the pump and a non return valve NRV may require fitting to the hot outlet only Note this is only for th...

Страница 6: ...uplers Hoses The anti vibration AV couplers are designed to limit the transfer of pump vibration to the associated pipe work All Salamander AV couplers are BSP x 22mm push fit with built in isolating...

Страница 7: ...aximum static head should be 5m equivalent to 50kPa 0 5bar pressure The plumbing installation must comply with TheWater Supply Water Fittings Regulations 1999 and BS EN 806 4 2010 buildings regulation...

Страница 8: ...Where this flow cannot be achieved a negative head pump is required 600mm or less possible negative head Usable capacity minimum 50 gallons per bathroom Vent and other services Cold water storage H C...

Страница 9: ...no natural flow exists Negative head is also needed for electric showers dishwashers washing machines or where pumped hot water meets mains cold Non ReturnValves Non return valves MUSTNOTbe fitted in...

Страница 10: ...accommodated by using a single ended Right pump universal which is complete with a pressure vessel Right pump universal to boost tank fed supplies to instantaneous electric showers and water heaters F...

Страница 11: ...valve or before an open outlet Figure 12 Tank fed hot with mains cold Please note mains fed systems require the use of a break tank however for a more suitable alternative please see the Salamander Ma...

Страница 12: ...bers This will not happen if the outlet pipework is connected to the pump The best method is Connect discharge pipework Check that all the pump isolating valves are open Fill system Check for leaks DO...

Страница 13: ...and creates a vortex which draws air and possibly debris into the pump Coldstorageusablecapacity The usable capacity of cold storage is easily calculated as the capacity of water in the cold tank abo...

Страница 14: ...r is factory set at 55 60 C MAX 65 C HWSTMVblendingvalvecontroller A Salamander approved HWS Blending valve controller will protect booster pumps in systems where the temperature of the stored hot wat...

Страница 15: ...er level switch which must be positioned 102mm higher than the highest outlet from the cold water storage tank When the water level drops too far the WSP will switch off the pump until the cold water...

Страница 16: ...of an approved top entry flange Figure 21 Horizontal cylinders Approvedflanges cylinders The 22mm No Stop Essex and the other approved top entry flanges with extension pipes into the cylinder represen...

Страница 17: ...larly on the hot side as illustrated is likely to Interfere with the initiation and smooth operation of the pump Restrict the supply water to the pump and risk internal mechanical damage Figure 24 Inv...

Страница 18: ...gall minute shower will use up 50 galls 227 Litres of the cold water storage capacity approx 60 of which 30 gallons 136 Litres will be hot water from the cylinder Storedhotwater temperature Extract f...

Страница 19: ...amander Pumps Right Pump range is fully WRAS approved Mechanicalseals Scale deposits in water supplies can cause the mechanical seal to stick if left for long periods without use We recommend the Righ...

Страница 20: ...perature 65 C Connections Pump Connections 3 4 BSP Flexible hoses Connections UK Model Isolating valves on all hoses Female x 15mm Push Fit Female x 22mm Push Fit Motor Type A C Induction Motor Duty R...

Страница 21: ...Charge 12 psi 18psi 34 psi 12 psi 18 psi 34 psi Connections Pump Connections BSP Flexible hoses Connections UK Model Isolating valves on all hoses Female x 22mm Push Fit x 280mm long Motor Type A C I...

Страница 22: ...alamander instructions Check suitability of pump is installation in negative head Check inlet filters are not blocked Check flow rate min of 2l min required on both hot and cold Float sticking in outl...

Страница 23: ...or system Ensure pump is sufficient to run the equipment Hot temp set too high Reduce cylinder stat setting to 65 C max or fit HWS TMV Pump starts with all outlets closed Leak in system Check for leak...

Страница 24: ...ate of purchase and is subject to the installation guidelines being followed correctly please refer to our Pre Installation Checklist on page 2 and our Commissioning Checklist on page 11 For a standar...

Страница 25: ...replacement and shall under no circumstances extend to any financial loss or damage including consequential losses alleged to have been suffered by the claimant Subject as provided in this warranty a...

Страница 26: ...pect of any service engineer s time and replacement of any parts Please speak to ourTechnical Support team for further details and confirmation of costs e ThisWarranty is given in addition to and does...

Страница 27: ...27...

Страница 28: ...28 Registeryourwarranty Applyonlineat www salamanderpumps co uk Applybyphone 01915162002 Unit2cColimaAvenue EnterpriseParkWest Sunderland SR53XE Getintouch we reheretohelp calluson01915162002...

Отзывы: