12
Commissioning
Before you finish
FOR RIGHT PUMP UNIVERSALS, ENSURE
THAT THE PRESSURE VESSEL IS FITTED TO
THE BRASS CONNECTION ON THE TOP OF
THE PUMP WITH THE
½
” RUBBER WASHER
AND IS HAND TIGHT.
•
Flush inlet pipework and carefully fill
pump with water by discharging water
from the outlet flexible coupler into a
container.
•
Fit pump inlet filters.
It is CRITICAL to discharge water through
the pump into a container using natural flow
before connecting the pump to outlet pipework
in order to ensure the air has been discharged
from inlet pipework and pump chambers.
This will not happen if the outlet pipework is
connected to the pump. The best method is:-
•
Connect discharge pipework.
•
Check that all the pump isolating valves
are open.
•
Fill system. Check for leaks.
•
DO NOT RUN PUMP DRY – to do so will
cause irreparable damage to your pump
and will invalidate your warranty.
•
Open shower mixer valve/system outlets
to maximum hot and cold to check the
natural flow (unpumped) flow of at least
2 litre per minute, individually on hot or
cold– positive head systems.
•
Open hot water outlets fully for 5 to 6
seconds and then turn outlets off. Then
open cold water outlets fully for 5 to 6
seconds and turn outlets off. If flow is
poor and inconsistent repeat above steps
until flow is steady.
•
Repeat 2-3 times.
MAX
H
C
Figure 14