background image

SANTA FE ADVANCE INSTALLER'S AND OWNER'S MANUAL

3

Installer’s & Owner’s Manual

4. Unit Assembly
4.1 Installing Feet (Optional)

Included with your SAKURA Dry-Boy 
are four leveling feet. It 
is important to level the unit for 
proper draining.  (See section 
5.1.4, Figure 6)

Installing Leveling Feet 
See Figures 2 and 2a for installing leveling feet.
1.  Lay down a protective pad (pillow, blanket, etc.).
2.   Carefully turn unit onto side opposite filter opening and drain 

port.

3.   Align leveling foot shaft with one of the four threaded hole 

locations as shown in Figure 2.

4. Screw each leveling foot in ten revolutions.
5. Carefully bring unit to upright position.
6.   Level unit for proper drainage as described in section 5.1.4 

(Figure 6) of this manual.

7. Wait 10 minutes before operating.

 CAUTION!

Note: Operating the unit immediately after bringing it to an upright 
position can possibly damage the compressor. A short amount 
of time is needed to allow the oil to return to it’s reservoir for 
lubrication.

4.2 Drain Hose

Take drain hose off of drain port. With scissors, cut one inch off of 
hose end to eliminate dented area. Place drain hose end on drain 
port until fully seated. Refer to Section 5.1.4 regarding proper 
drainage.

5. Installation
5.1 Location

SAKURA Dry-Boy  can be installed in a variety oflocations to 
meet the owner’s needs, but should beinstalled directly in the area 
to be dehumidified. Other considerations include:

1.   Providing access to a 115 VAC power outlet (10' power cord 

is provided).

2.   Locating near a floor or other suitable drain (8' drain hose 

included).

3.   Do not install SAKURA Dry-Boy  with the intake or 

exhaust of the unit within 1' of a wall or other obstruction. 
Do not place the unit where curtains or debris can be 
drawn onto the intake and restrict airflow. Do not operate in 
standing water or place the unit near open water. Refer to 
Figure 5.

4.   SAKURA Dry-Boy  drains via a gravity system. A level 

indicator has been included near the intake of the unit. 
To ensure the unit will drain properly, the unit should be 
positioned so the level bubble appears in the non-shaded 
area of the level indicator as shown. Refer to Figure 6. If 
the unit is placed on an unlevel surface, adjust leveling feet 
using a crescent wrench or 7/16" open wrench. Move handle 
end of wrench from left to right to lower one foot. Adjust all 
four feet underneath the unit until bubble in the level dial is 
in the correct position. Failure to level the unit may result 
in leakage or improper drainage. See Section 4.2 regarding 
drain hose installation.

Figure 2: Insert leveling feet in 
locations

Figure 2a: Screw each leveling 
foot in ten revolutions

Figure 1: Four leveling feet

Figure 3: Drain port

Figure 2a: Drain hose position

Figure 5: Installing SAKURA Dry-Boy  in area with proper clearance.

Figure 6: Level bubble should be in indicator area for proper drainage.

Содержание Dry-Boy SDB-45

Страница 1: ...SAKURA Basement Air System for Basement Crawlspace Dehumidification Installer s Owner s Manual High Efficiency Dehumidifier Dry Boy Model SDB 45 ...

Страница 2: ...btain maximum benefit from your SAKURA Dry Boy dehumidifier Read and Save These Instructions WARNING This symbol means important instructions Failure to heed them can result in serious injury or death CAUTION This symbol means important instructions Failure to heed them can result in injury or material property damage 1 Intended Application SAKURA Dry Boy is intended for installation in crawl spaces...

Страница 3: ... but should beinstalled directly in the area to be dehumidified Other considerations include 1 Providing access to a 115 VAC power outlet 10 power cord is provided 2 Locating near a floor or other suitable drain 8 drain hose included 3 Do not install SAKURA Dry Boy with the intake or exhaust of the unit within 1 of a wall or other obstruction Do not place the unit where curtains or debris can be dra...

Страница 4: ... RH drops 5 below the set point Approximate Humidity Levels Per Setting Dry 35 to 45 Relative Humidity Normal 45 to 55 Relative Humidity Recommended for most applications Humid 55 to 65 Relative Humidity The dehumidifier will run continuously until the relative humidity RH is reduced to the humidity control dial setting There is no benefit to setting the humidity control to dry in rooms under 65 doi...

Страница 5: ...efer to Figure 11 Allow the filter to dry completely before reinstalling Reinstall the filters per the instructions below or on the tag located on the 1 4 pre filter CAUTION NOTE Failure to follow filter handling instructions may result in improper function of the dehumidifier and cause premature filter wear 7 3 Remove Filters 1 Gently remove the 1 4 pre filter by pulling on the tab attached to the filter...

Страница 6: ...t breaker tripped 2 Humidity control set to Humid setting 3 Loose connection in internal wiring 4 Humidity control is defective No dehumidification Compressor does not run but blower runs with fan switch AUTO and humidity control turned to ON 1 Defrost thermostat open ambient temperature too low 2 Loose connection in compressor circuit 3 Defective compressor overload 4 Defective compressor or compr...

Страница 7: ... Remove middle top cover screw located on the drain port side Do not discard this screw It will be used to attach the mounting bracket in the next step Step 3 Align mounting bracket of condensate pump with the dehumidifier screw hole Reinstall screw that was removed in step 2 Step 4 Remove the 7 hose from the plastic bag and install this hose from the condensate pump onto the adaptor as indicated M...

Страница 8: ...8 Installer s Owner s Manual CONDENSATE PUMP INSTALLATION Step 5 Attach the 20 drain hose to the condensate pump and route it to a floor drain Plug in the condensate pump and the assembly is completed ...

Страница 9: ... metal plenum Lock the collar in position by bending the collar tabs outwards and flatten Step 4 All collar tabs are flattened Repeat steps 1 4 for top duct assembly Optional Accessory Duct Kit Duct Kit Assembly Instructions Do not drill any pilot holes into the plastic housing You may damage the internal components When installing screws be careful not to strip Lightly tighten screws ATTACHING COLL...

Страница 10: ...CT ASSEMBLY 1 Check sealing foam on the top duct assembly Ensure none has come loose 2 Place top duct assembly ensure the sealing foam makes contact around the plastic surfaces 3 Center the top duct assembly ensure the sealing foam makes contact around the plastic surfaces 4 Ensure the rear flange of the top duct assembly is seated flush against the back of the plastic housing See Figure 2 5 DO NOT ...

Отзывы: