8000m Series
-
28
-
Function
Code
Function
Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F4.08
V/F voltage 3 0.0%~100.0%
0.1%
100.0%
●
F4.09
Coefficient
of V/F Slip
compensation
0.0%~200.0%
0.1%
0.0%
○
F4.10
Energy-saving
selection
0:Disabled
1:Enabled automatically
0
○
F4.11
Reserved
F4.12
Low-frequency
threshold of
restraining
oscillation
0~10
2
○
F4.13
High-frequency
threshold of
restraining
oscillation
0~10
0
○
F4.14
Reserved
F4.15
Boundary
frequency of
restraining
oscillation
0.00Hz~F0.10 (Maxi.
frequency)
0.01Hz 30.00Hz
○
F4.16
Reserved
F4.17
AVR function
selection
0:Invalid
1:Valid all the time
2: Only invalid during
deceleration
1
○
F5 Group: Input Terminals Parameters
F5.00
M1 terminal
function
0:Invalid
1:Forward run (FWD)
2:Reverse run (REV)
3:3-wire control
4:Forward jog run (FJOG)
1
●
F5.01
M2 terminal
function
2
●