Advanced Program Group
(continued)
61
A453 [Boost Select]
Related Parameter(s):
d004, P101, P102
Sets the boost voltage (% of
P101
[Motor NP Volts]) and redefines the Volts per Hz curve.
(1)
(1)
Drive may add additional voltage unless option 5 is selected.
Options
1
“30.0, VT”
2
“35.0, VT”
Variable Torque
3
“40.0, VT”
4
“45.0, VT”
5
“0.0 no IR”
6
“0.0”
Constant Torque
7
“2.5, CT”
[Default for
3.7, 5.5, 7.5 & 11.0 kW
(5.0, 7.5, 10.0 & 15.0 HP) Drives]
8
“5.0, CT” (Default)
9
“7.5, CT”
10
“10.0, CT”
11
“12.5, CT”
12
“15.0, CT”
13
“17.5, CT”
14
“20.0, CT”
Содержание HPVFE