67
No.
Fault
Type
(1)
Description
Action
F33
Auto Rstrt Tries
➁
Drive unsuccessfully attempted to
reset a fault and resume running
for the programmed number of
A451
[Auto Rstrt Tries].
Correct the cause of the fault and manually clear.
F38
Phase U to Gnd
➁
A phase to ground fault has been
detected between the drive and
motor in this phase.
1.Check the wiring between the drive and motor.
2.Check motor for grounded phase.
3.Replace drive if fault cannot be cleared.
F39
Phase V to Gnd
F40
Phase W to Gnd
F41
Phase UV Short
➁
Excessive current has been
detected between these two
output terminals.
1.Check the motor and drive output terminal wiring
for a shorted condition.
2.Replace drive if fault cannot be cleared.
F42
Phase UW Short
F43
Phase VW Short
F48
Params Defaulted
The drive was commanded to
write default values to EEPROM.
1.Clear the fault or cycle power to the drive.
2.Program the drive parameters as needed.
F63
SW OverCurrent
➀
Programmed
A448
[SW Current
Trip] has been exceeded.
Check load requirements and
A448
[SW Current
Trip] setting.
F64
Drive Overload
➁
Drive rating of 150% for 1 minute
or 200% for 3 seconds has been
exceeded.
Reduce load or extend Accel Time.
F70
Power Unit
➁
Failure has been detected in the
drive power section.
1.Cycle power.
2.Replace drive if fault cannot be cleared.
F71
Net Loss
The communication network has
faulted.
1.Cycle power.
2.Check communications cabling.
3.Check network adapter setting.
4.Check external network status.
F81
Comm Loss
➁
RS485 (DSI) port stopped
communicating.
1.If adapter was not intentionally disconnected,
check wiring to the port. Replace wiring, port
expander, adapters or complete drive as required.
2.Check connection.
3.An adapter was intentionally disconnected.
4.Turn off using
C304
[Comm Loss Action].
F100
F122
Parameter
Checksum
➁
The checksum read from the
board does not match the
checksum calculated.
Set
P112
[Reset To Defalts] to option 1
“Reset
Defaults
”.
I/O Board Fail
➁
Failure has been detected in the
drive control and I/O section.
1.Cycle power.
2.Replace drive if fault cannot be cleared.
(1)
See
page 4-1
for a description of fault types.
Содержание HPVFE