Advanced Program Group
(continued)
52
A403 [S Curve %]
Sets the percentage of acceleration or deceleration time that is applied to the ramp as S Curve. Time is added, 1/2 at the beginning and 1/2 at
the end of the ramp.
Values
Default
0% (Disabled)
Min/Max:
0/100%
Display:
1%
A404 [Jog Frequency]
Related Parameter(s
): P105, t201, t202, A405
Sets the output frequency when a jog command is issued.
Values
Default
10.0 Hz
Min/Max:
0.0
/P105
[Maximum Freq]
Display:
0.1 Hz
A405
[Jog Accel/Decel]
Related Parameter(s):
t201, t202, A404
Sets the acceleration and deceleration time when a jog command is issued.
Values
Default
10.0 Secs
Min/Max:
0.1/600.0 Secs
Display:
0.1 Secs
A409 [Internal Freq]
Related Parameter(s):
P108
Provides the frequency command to the drive when
P108
[Speed Reference]
is set to 1 “Internal Freq”. When enabled, this parameter will
change the frequenc
y command in “real time” using the integral keypad Up Arrow or Down Arrow when in program mode.
Important:
Once the desired command frequency is reached, the Enter key must be pressed to store this value to EEPROM memory. If the
ESC key is used before the Enter key, the frequency will return to the original value following the normal accel/decel curve.
Values
Default
60.0 Hz
Min/Max:
0.0/400.0 Hz
Display: 0.1 Hz