MAXILUBE
IF-105
MUIF3AEN.doc
21.4.2005 Rev. 3A
7 (9)
Alarm, low pressure
If the pressure in the line does not rise high enough during pressurization time, code
ALP
is
blinking on the display and the red LED-signal
L1
or
L2
of the line which has caused the alarm
is blinking.
In pressure transmitter operation
, an alarm is triggered, if the line pressure does not reach
the set high limit within the set maximum pressurization time. The same line will be pressurized
again, when the alarm has been reset by pressing the
SET
button.
In pressure switch operation
an alarm is triggered, if the line pressure switch does not close
within the set maximum pressurization time. The same line will be pressurized again, when the
alarm has been reset by pressing the
SET
button.
3.3.3 Alarm from LG-ind doser operation indicator
LG-ind doser operation indicators are in use when parameter
LGI
has been set in status
YES
.
The alarm is triggered when the LG-ind doser operation indicator does not sense the operation
of a doser during a lubrication cycle. Code
AIn
is displayed. Lubrication continues normally
despite the alarm. This feature is different from any other alarms. Alarm can be reset with
SET
–button.
3.3.4 Alarm from air pressure switch of grease spray system
Air pressure control is in use when parameter
AC
has been set in status
YES
.
The alarm is triggered if the air pressure switch is not open when pressurization starts or not
closed when pressurization has stopped. Code
Air
is displayed. The same line will be
pressurized again, when the alarm has been reset by pressing the
SET
button.
3.4 Manual operation
Transfer to manual operation mode in the selected channel by setting the parameter
HL
in
status
On
.
One can transfer out of manual operation mode into automatic operation mode as follows:
•
by setting the parameter
HL
in status
OFF
•
automatically when 60 minutes have elapsed since transferring into manual operation
mode
•
by restarting MaxiLube (MaxiLube always starts in automatic operation mode in all
channels)
In manual operation mode
SET
-button is used to:
•
start
the
pumping
•
stop the pumping
•
transfer the pumping to another line
The lubrication program keeps the pressure in the set high limit value in the line which is
pumped. In oil lubrication system pressure monitoring is not available.