12.Batery setting charging/discharging parameters
Parameter type
FCP-1000 Setting parameters
FCP-500 Setting parameters
Max. continuous charging current(A)
0.2C
10
0.3 C
10
Floating charging voltage (V)
2.23V/cell
2.23V/cell
Daily charge voltage (V)
2.45V/cell
2.45V/cell
Equalizing charge voltage (V)
2.45V/cell
2.45V/cell
Recommended equalizing charge period
1~2 weekly
1~2 weekly
High Voltage Alarm (V)
2.45V/cell
2.45V/cell
Max continuous discharge current(A)
0.4 C
10
0.4 C
10
Discharge protection Voltage
1.80V/Cell
1.80V/Cell
Equalizing charge to Floating charge
transition condition
12h after charge voltage reaches
2.45V/cell
12h after charge voltage reaches
2.45V/cell
Temperature compensation coefficient
-3.50 mV/
℃
/cell
-3.50 mV/
℃
/cell