Sacred Sun FCP Скачать руководство пользователя страница 25

(1) One-Month Inspection 

Item 

Details 

Standard 

Measures 

Total voltage during   

recovery charge or   

equalizing charge (

❉1)

 

Check voltage   

indication  value  on  panel 

surface voltmeter(

❉2)

 

Equalizing  charge  voltage 

(2.45V/cell) 

×

  number  of 

cells. 

When 

deviating 

from 

standard, 

adjust 

by 

equalizingcharge voltage   

(2.45V/cell)  ×  number  of 

cells. (

❉3)

 

Caution: 

Measuring  equipment  used  to take  these  measurements  should  be  calibrated  on  a  regular  basis,  with 

use made only of items that fall within the allowable margin of error. 

(

1) When the charge method is unclear, please ask the maker of the storage battery system. 

(

2) When there is not the panel surface voltmeter, please ask the maker of the storage battery system a 

confirmation method of the voltage. 

(

3) When the adjustment method is unclear, please ask the maker of the storage battery system. 

(2) Six-Month Inspection 

Item 

Details 

Standard 

Measures 

  Total  voltage  during 

recovery  charge  or 

equalizing 

charge 

(

❉4)

 

(1)  Measure  total  voltage 

with voltmeter of 0.5-class 

or above. 

(2) 

Check 

voltage 

indication  value  on  panel 

voltmeter. (

❉5)

 

(1) 

Value 

of 

equalizing 

charge voltage (2.45V/cell) × 

number of cells.     

(2) Allowable margin for 

panel mounted gauges as 

stated in JIS C1102-2 

(direct-acting indicator 

electric gauges). 

(1) When voltage value 

deviates  from  standard, 

adjust 

by 

equalizing 

charge  voltage(2.45V/cell) 

× number of cells.   

(2)  Repair  or  replace 

gauges  deviating  over  the 

allowable degree. 

  Voltage  of  each  cell 

duringrecovery charge   

or equalizing charge 

  (

❉4)

 

Measure 

open 

circuit 

voltage of each cell. 

The voltage is measured 

from  2  to  24  hours  after  the 

recovery 

charge 

or 

equalizing 

charge 

was 

completed.  The  voltage  of 

each  cell  must  be  2.10V  or 

more. The voltage of any cell 

must  be  within  the  following 

range: 

Average 

voltage 

±0.05V 

When  the  voltage  value 

deviates from the standard 

value,  observe  for  1  to  2 

months,  and  contact  the 

manufacturing company. 

Visual appearance of 

storage battery, etc. 

Check  for  presence  of 

breaking  or  deformation 

damage in battery box, lid, 

etc., as well as electrolyte   

leakage. 

Absence 

of 

cracking, 

deformation 

and 

other 

damage 

or 

electrolyte 

leakage. 

In  cases  of  damage  or 

electrolyte 

leakage, 

investigate the cause, and 

replace 

the 

battery 

containing 

anydamaged 

items  or  found  to  have 

electrolyte leakage. 

Check for presence of dirt 

or stains from dust, etc. 

Absence  of  dirt,  stains  or 

corrosion. 

Clean  any  dirt  or  stains 

with a damp cloth. 

Check for evidence of rust  Absence of stains or   

Clean, 

treat 

for 

rust 

Содержание FCP

Страница 1: ...FCP Battery Installation and Operation Instruction Shandong Sacred Sun Power Sources Co Ltd...

Страница 2: ...Cautions 13 6 Use Environment and Use Conditions 14 7 Handling When Commencing Use 15 8 Everyday Maintenance and Handling 19 9 Measures at Abnormalities 24 10 Measures When Suspending Use 25 11 Other...

Страница 3: ...ecomposition diagram 2 Battery accessories list 2 1 Rack accessories No Name Type Quantity Remark 1 Base 1 Insulation shields Terminal block Insulating base Terminal block fixing plate Unit brace Batt...

Страница 4: ...me Type Quantity Remark 2 Unit brace 4 3 Barrier FCP 500 218 24 4 12 218 24 4 FCP 1000 980 42 3 8 980 42 3 4 Terminal block fixing plate J00109610102 2 5 Insulating base FCP 500 WX 195 2 FCP 1000 WX 1...

Страница 5: ...3 1Bag Flat washer GB95 2002 C 8 26 Nut GB T41 2000 C M8 13 11 Fixing bolt GB T70 1 2008 M8 25 10 1Bag only for FCP 1000 Flat washer GB95 2002 C 8 10 Spring washer GB859 1987 8 10 12 Fixing bolt GB T7...

Страница 6: ...ading valve tool WX 251 1 21 QC passed 1 set 22 Packing list 1 set 2 2 Connectors part No Name Type Quantity Remark 1 battery connection between layers FCP 500 OX185 240 3 FCP 1000 OX185 380 2 battery...

Страница 7: ...d all molds during unpacking 3 1 3 For easy installation the battery mold rack can also be the whole installation or more than one unit mold as large module decomposition before installation 3 1 4 The...

Страница 8: ...on the ground crossed crossed position is consistent with the battery mold rack base dimensions 3 3 3 Placing the base into the crossed position and adjust correct well marked diagonal fixed on foot...

Страница 9: ...rranged holes in 4 holes After adjusting the relative position of unit mold and base putting the bolts into the other two holes to both fixed Then out of the positioning pin and insert the bolt fixed...

Страница 10: ...larity 3 5 2 1000Ah battery need to use auxiliary lifting board installation pay attention to the battery tilt angle when the lifting as the below figure show 3 5 2 Install the battery in place If the...

Страница 11: ...stallation firm and correct 3 6 2 Then install the black insulating base to the fixed plate need the 5 Ball hexagonal wrench through copper wiring rotating seat to fix the reserved bolts when installi...

Страница 12: ...ries carefully check the bolts if there is loosening Note the spring flat must be flattened 3 7 3 After installed the rigid connectors install the rigid connector protection cover There are two kind o...

Страница 13: ...3 7 4 The finished connected battery mold drawing as below Rigid connector Positive protection cover is red negative is black...

Страница 14: ...result in the danger of serious injury or even death to the user Warning This label indicates that mistaken use ignoring the label poses the possibility of serious injury or even death to the user as...

Страница 15: ...r injuries If the electrolyte does get on something in this way immediately wash it off with large amounts of water In particular if the solution gets into the eyes or is mistakenly consumed immediate...

Страница 16: ...storage battery in a location where it may be become immersed in water Immersion in water may cause electric shock or fire 4 Handling When Commencing Use 4 1 Opening the Package and Inspecting When t...

Страница 17: ...specified in the table below Table 1 Chemical anchor bolt tightening torque Nominal diameter Specified torque N m kgf cm M12 42 1 N m 430 kgf cm M16 107 8 N m 1 100 kgf cm Note These values are the s...

Страница 18: ...hrough the unit battery mounting holes and temporarily secure the bolts using the nuts with two plain washers See Figure 3 Figure 3 Installing the batteries on the second and higher stages Install the...

Страница 19: ...g plates and battery terminals Sequentially connect the connecting plates by using M10 bolts with a flat washer and a spring washer according to the working drawing Tighten all the connecting bolts to...

Страница 20: ...gap between the unit and the battery bottom Be careful the top of the cover of the battery so that it does not clash with the unit when the battery is inserted Remove synthetic resin plate then See F...

Страница 21: ...rdance with Section 4 3 Auxiliary Charge 4 5 Pre Use Preparations Following the Auxiliary Charge in Section 4 3 and the Pilot Operation in Section 4 4 with the exception of instances in which actual u...

Страница 22: ...regularly tightened Failure to perform regular inspections can cause damage to the storage battery or result in ignited explosions 5 2 Discharge Discharge final voltage should be as shown in Table 3...

Страница 23: ...2 Recovery charge Conduct recovery charges in accordance with the equalizing charge Caution When the charge voltage deviates from the manufacturer stipulated values the following types of adverse eff...

Страница 24: ...vent storage battery problems before than can occur periodic inspections should be conducted within the suggested periods Any deviation from standards should be dealt with through proper measures with...

Страница 25: ...lowable margin for panel mounted gauges as stated in JIS C1102 2 direct acting indicator electric gauges 1 When voltage value deviates from standard adjust by equalizing charge voltage 2 45V cell numb...

Страница 26: ...y system a confirmation method of the voltage 3 One year inspection For one year inspections perform the sequence of the six month inspections plus the following item Item Details Standard Measures Co...

Страница 27: ...torque values Continuing use without such retightening can be the cause of sparking terminal breakage or other problems 7 Measures When Suspending Use Because storage batteries will gradually lose the...

Страница 28: ...cause of fire or electric shock Avoid causing sparks or short circuiting Electric energy remaining in a storage battery can be the cause of ignited explosions Caution Spent storage batteries should b...

Страница 29: ...abnormal storage battery d Storage battery has reached end of service life a Lower voltage setting to stipulated value and observe results If the temperature still remains high arrange for manufacture...

Страница 30: ...Equalizing charge voltage V 2 45V cell 2 45V cell Recommended equalizing charge period 1 2 weekly 1 2 weekly High Voltage Alarm V 2 45V cell 2 45V cell Max continuous discharge current A 0 4 C10 0 4...

Отзывы: