9.1) Installation as a BOOSTER SET system

It  allows  the  activation  of  1  or  2  pumps,  independently  or  jointly,  with  or  without  starting 
alternation, through pressure switches, float switches, tank probes, pressure transducer or by 
time programming. To avoid dry running, in addition to the built-in current protection, system 
shutdown can be selected through a minimum pressure switch, a float switch, hanging probes 
in the well (2 or 3 well probes can be selected) or no element of protection.

In the case of operation by means of a pressure transducer, configurable with full scale from 
1 bar to 40 bar, the starting delay of the auxiliary pump can be configured, in case the main 
pump is not able to exceed the starting pressure. Auxiliary pump starting can also be disabled 
if only 1 pump is required to run at a time. In any case, and as long as the auxiliary start has 

not been disabled, the standby pump will start automatically even if the set delay time has not 
been met, if the pressure drops to half the start pressure, to avoid an excessive drop pressure 

in the installation.

9.2) Installation as a WASTE WATER lifting system

It allows the activation of 1 or 2 pumps, independently or jointly, with or without starting al

-

ternation, through float switches, pressure transducer (any level control device that provides 
a 4-20mA signal) or by time programming. To avoid dry running, in addition to the built-in 
current protection, there is an input for the system’s joint shutdown float. In addition, a second 
stop float of the entire system can be configured for double safety (this option can be easily 
enabled from the application fine settings menu).

9.3) Installation as a BOREHOLE PUMP system

It allows the starting of a well pump through a pressure switch signal, level float switch, tank 
probes, pressure transducer or by time programming. To protect the pump from running dry, 
it is possible to use 2 or 3 probes in the well. In this case, although it is not usual, the system 
could operate in a tank with 2 well pumps in which alternating start-up or joint operation is 
required, as if it were a pressure group of surface pumps.

9.4) COMBINED installation (only available in the device for 2 pumps)

It allows the start/stop of 2 pumps completely independent of each other, as described in the 
heading of this section of the manual. The protections of the pumps against dry work, phase 
consumption  anomaly,  etc...  are  independently  configurable  for  each  pump,  being  able  to 
enable/disable these functions in 1 of the pumps, in the 2 or in none of them, at choice of the 
user. In this type of application, the start/stop through the irrigation controller signal will only 
work for pump 2.

Содержание easytronic

Страница 1: ...INSTALLATION AND MAINTENANCE MANUAL MANUAL DE INSTALACI N Y MANTENIMIENTO Cat MET Rev 07 10 2021...

Страница 2: ...EL CTRICAS 5 8 FORMATO DE PANTALLA 8 9 TIPOS DE APLICACI N 9 10 ASISTENTE DE CONFIGURACI N 11 11 MEN DE CONFIGURACI N 12 12 VISUALIZACI N R PIDA DE AJUSTES B SICOS 15 13 GESTI N DE AVISOS 16 14 ALARMA...

Страница 3: ...onocimientos salvo que un responsable de su seguridad les haya explicado las instrucciones y supervisado el manejo del dispositivo Se deber evitar que los ni os jueguen con el dispositivo No utilice e...

Страница 4: ...n del dispositivo Debe instalarse en ambientes bien ventilados sin humedad y lejos de la exposici n directa del sol y de la lluvia Antes de efectuar las conexiones el ctricas aseg rese de que no recib...

Страница 5: ...saestopas apropiados para fijar el cable Aseg rese tambi n de que en la red el ctrica se disponga de protecciones el ctricas en par ticular es recomendado el uso de un interruptor diferencial 300mA cl...

Страница 6: ...na carga m xima de 5A a 230Vac Programador riego Esta entrada se utiliza en caso de requerir habilitar el equipo a trav s de un programador de riego Requiere de una se al externa de hasta 48V AC o DC...

Страница 7: ...bomba Presostato Boya de nivel Sondas de dep sito Esta entrada utiliza 2 o 3 contactos en funci n de la selecci n realizada como dispositivo de arranque paro en el men 5 TIPO DE APLICACI N Solamente e...

Страница 8: ...que paro En el tipo de aplicaci n COMBINADO podr seleccionarse si la bomba a controlar por el transductor de presi n es la bomba 1 o la bomba 2 Entrada 1 Esta entrada utiliza 2 o 3 contactos en funci...

Страница 9: ...ente en el tipo de aplicaci n COMBINADO puede configurarse el dispositivo de paro de seguridad para la bomba 2 siendo las opciones disponibles BOYA DE NIVEL PRESOSTATO DE MINIMA y NINGUNA Entrada 4 En...

Страница 10: ...p sito mediante sondas de pozo y sondas de dep sito bomba 1 m s una bomba que coja el agua de ese dep sito y que arranque pare mediante presostato o transductor de presi n con una boya de nivel para p...

Страница 11: ...2 bombas independientemente o conjuntamente con alternancia de arranque o sin ella a trav s de boyas de nivel transductor de presi n cualquier dispositivo de control de nivel que proporcione una se al...

Страница 12: ...mos seleccionando el disposi tivo para la bomba 1 o para la 2 El usuario puede seleccionar el dispositivo conectado para el arranque paro de la bomba Las opciones disponibles depende r n del tipo de a...

Страница 13: ...12 11 MEN DE CONFIGURACI N...

Страница 14: ...13 11 MEN DE CONFIGURACI N...

Страница 15: ...bilitar deshabilitar el funcionamiento de las 2 bombas individualmente decidir si se requiere alternancia de arranque o no permitir la activaci n individual o conjunta de las bombas y tambi n el uso o...

Страница 16: ...i n del bot n de paro manual de la activaci n del paro del sistema autom tico o finalmente podremos a adir una programaci n horaria independiente del estado de las bomba para activar desactivar el rel...

Страница 17: ...enci n directa del instalador En los ajustes de la detecci n contra el trabajo en seco podemos fijar un tiempo de rearme fijo de manera que las paradas por detecci n de trabajo sin agua no tendr n un...

Страница 18: ...in agua Comprobar que la bomba puede aspirar agua sin problemas y posteriormente compruebe el valor de sensibilidad introducido en el punto 8 PROTECCIONES BOMBA Un valor de sensibilidad excesivamente...

Страница 19: ...la garant a y eximir al fabricante de cualquier responsabilidad en caso de accidentes a personas o da os a la propiedad y o al producto en s Una vez que el producto ha sido recibido verifique que no h...

Страница 20: ...19 17 ESQUEMA DE MONTAJE Y DIMENSIONES...

Страница 21: ...20 17 ESQUEMA DE MONTAJE Y DIMENSIONES...

Страница 22: ...ELECTRICAL CONNECTIONS 25 8 SCREEN FORMAT 28 9 TYPES OF APPLICATION 29 10 START UP WIZARD 31 11 CONFIGURATION MENU 32 12 QUICK VIEW OF BASIC SETTINGS 35 13 WARNING MANAGMENT 35 14 ALARMS 36 15 MAINTEN...

Страница 23: ...ge unless a person responsible for their safety has ex plained the instructions and supervised the handling of the device Children should be prevented from playing with the device Do not use the devic...

Страница 24: ...ill be used Installation must be done by a qualified technician General device installation recommendations It should be installed in well ventilated environments without humidity and away from direct...

Страница 25: ...is recommended 300mA class A for domestic applications It is recommended in addition to the differential switch that the installation has a magne to thermal protection and an electrical main switch t...

Страница 26: ...potential free and support a maximum load of 5A at 230Vac Irrigation controller This input is used in case you need to enable the equipment through an irrigation controller Requires an external signal...

Страница 27: ...the pump Pressure switch Float switch Tank probes This input uses 2 or 3 contacts depending on the selection made as start stop device in menu 5 TYPE OF APPLICATION Only in case of selecting 3 tank pr...

Страница 28: ...s start stop device In the COMBINED application type it can be selected whether the pump to controlled by the pressure transducer is either pump 1 or pump 2 Input 1 This input uses 2 or 3 contacts dep...

Страница 29: ...n the COMBINED application type the device can be configured safety stop for pump 2 with the available options FLOAT SWITCH MINIMUM PRESSURE SWITCH and NO PROTECTION Input 4 In the COMBINED applicatio...

Страница 30: ...pump that takes the water from that tank and starts stops by means of a pressure switch or pressure transducer with a level float switch to prevent operation without water pump 2 In 2 pump systems pum...

Страница 31: ...rough float switches pressure transducer any level control device that provides a 4 20mA signal or by time programming To avoid dry running in addition to the built in current protection there is an i...

Страница 32: ...erentiate us if we are selecting the device for pump 1 or for pump 2 User can select connected device to start stop the pump The options available will depend on the type of application previously sel...

Страница 33: ...32 11 CONFIGURATION MENU...

Страница 34: ...33 11 CONFIGURATION MENU...

Страница 35: ...he operation of the 2 pumps individually decide whether or not to require start up alternation allow individual or joint activation of the pumps and also the use or not of the analog input to enable d...

Страница 36: ...rs of pump 1 and pump 2 individually We have an independent register for pump 1 and pump 2 where we can check over time the failures due to over consumption or due to dry work that they have had We ha...

Страница 37: ...SDUCER FAILURE The pressure transducer is missing damaged or not wired correctly Check that the transducer is connected with the correct polarity to the specific input for the pressure transducer If t...

Страница 38: ...y value entered in point 8 PUMP PROTECTIONS An excessively high sensitivity value can cause false dry work detection In this case set the sensitivity value that gives you a correct measurement PHASE F...

Страница 39: ...rranty and will exempt the manufacturer from any liability in the event of accidents to people or damage to property and or the product itself Once the product has been received verify that it has not...

Страница 40: ...39 17 ASSEMBLY AND DIMENSIONS DIAGRAM...

Страница 41: ...40 17 ASSEMBLY AND DIMENSIONS DIAGRAM...

Страница 42: ...5 UE Low Voltage Directiva 2009 125 CE Directiva 2011 65 UE RoHS II Directiva 2014 53 UE RED Directiva 2004 40 CE Directiva 2006 42 EC BOMBAS SACI S A Cam de Can Muntanyola 4 22 Pol Ind Palou Nord 084...

Отзывы: