9. TYPES OF APPLICATION

The device can operate in a single-phase and three-phase installation and, depending on 

the power supplied, it will be able to control and protect 1 or 2 single-phase or three-phase 
pumps (only in the device for 2 pumps), depending on the input power received. The pumps 

will work according to the voltage and frequency to which the device has been connected, 
that is, if we connect the device to a single-phase network, the pumps that we connect must 

also be single-phase. The same case if we connect the device to a 230V three-phase network 
or to a 400V three-phase network.

The device is capable of detecting the voltage and frequency of the electrical network to which 
it is connected, without any user intervention, allowing all possible standard voltages, as well 

as connections to 50Hz and 60Hz networks.

A simple setup wizard is available when starting the device, and can be configured to control 

a water supply pressure group, a sewage discharge system, a well pump system and also 

allows a combined operation of the pumps (option available only in the device for 2 pumps).

The combined system totally differentiates pump 1 from pump 2, there is no link between 
the pumps, and allows the start/stop and safety systems of each pump to be configured in

-

dependently. In this mode, the only thing that the pumps share is the voltage and frequency 
provided by the electrical network where the device is connected. A common example of this 
mode can be a well pump that fills a tank using well probes and well probes (pump 1), plus a 

pump that takes the water from that tank and starts/stops by means of a pressure switch or 

pressure transducer, with a level float switch  to prevent operation without water (pump 2).

In 2-pump systems, pumps with the same or different nominal amperage can be configured, 
joint operation can be configured through a single trigger signal, and start alternation can be 
enabled or disabled. All of these settings are easily configurable from the setup menu.

The device has independent amperage control for each pump and for each phase, therefore 
protection against motor overcurrent, as well as protection against dry work by current, with 

configurable detection sensitivity and reset time.

The device has auto reset when a fault occurs due to overcurrent, due to excess consumption 
of one of the motor phases with respect to the others (only in three-phase connections and 

only in the panel for 2 pumps) or due to dry running. This prevents the installer from acting in 
the event of a fault, being a completely autonomous and self-resettable system.

It has an internal clock with which the activation/deactivation of the pumps and auxiliary 

relays can be programmed independently. Activation by time programming does not require 
any physical device connected to the device. It will activate and stop the pumps only paying 
attention to the current time.

It has an independent fault log per pump with the capacity to store the last faults with time, 

date and type of fault registered, for proper maintenance of the installation.

The device also has an independent operating hours control per pump, also in order to control 
the status of the installation and the pumps, as well as the correct operation of the start-up 

alternation (configurable and enabled by default).

Содержание easytronic

Страница 1: ...INSTALLATION AND MAINTENANCE MANUAL MANUAL DE INSTALACI N Y MANTENIMIENTO Cat MET Rev 07 10 2021...

Страница 2: ...EL CTRICAS 5 8 FORMATO DE PANTALLA 8 9 TIPOS DE APLICACI N 9 10 ASISTENTE DE CONFIGURACI N 11 11 MEN DE CONFIGURACI N 12 12 VISUALIZACI N R PIDA DE AJUSTES B SICOS 15 13 GESTI N DE AVISOS 16 14 ALARMA...

Страница 3: ...onocimientos salvo que un responsable de su seguridad les haya explicado las instrucciones y supervisado el manejo del dispositivo Se deber evitar que los ni os jueguen con el dispositivo No utilice e...

Страница 4: ...n del dispositivo Debe instalarse en ambientes bien ventilados sin humedad y lejos de la exposici n directa del sol y de la lluvia Antes de efectuar las conexiones el ctricas aseg rese de que no recib...

Страница 5: ...saestopas apropiados para fijar el cable Aseg rese tambi n de que en la red el ctrica se disponga de protecciones el ctricas en par ticular es recomendado el uso de un interruptor diferencial 300mA cl...

Страница 6: ...na carga m xima de 5A a 230Vac Programador riego Esta entrada se utiliza en caso de requerir habilitar el equipo a trav s de un programador de riego Requiere de una se al externa de hasta 48V AC o DC...

Страница 7: ...bomba Presostato Boya de nivel Sondas de dep sito Esta entrada utiliza 2 o 3 contactos en funci n de la selecci n realizada como dispositivo de arranque paro en el men 5 TIPO DE APLICACI N Solamente e...

Страница 8: ...que paro En el tipo de aplicaci n COMBINADO podr seleccionarse si la bomba a controlar por el transductor de presi n es la bomba 1 o la bomba 2 Entrada 1 Esta entrada utiliza 2 o 3 contactos en funci...

Страница 9: ...ente en el tipo de aplicaci n COMBINADO puede configurarse el dispositivo de paro de seguridad para la bomba 2 siendo las opciones disponibles BOYA DE NIVEL PRESOSTATO DE MINIMA y NINGUNA Entrada 4 En...

Страница 10: ...p sito mediante sondas de pozo y sondas de dep sito bomba 1 m s una bomba que coja el agua de ese dep sito y que arranque pare mediante presostato o transductor de presi n con una boya de nivel para p...

Страница 11: ...2 bombas independientemente o conjuntamente con alternancia de arranque o sin ella a trav s de boyas de nivel transductor de presi n cualquier dispositivo de control de nivel que proporcione una se al...

Страница 12: ...mos seleccionando el disposi tivo para la bomba 1 o para la 2 El usuario puede seleccionar el dispositivo conectado para el arranque paro de la bomba Las opciones disponibles depende r n del tipo de a...

Страница 13: ...12 11 MEN DE CONFIGURACI N...

Страница 14: ...13 11 MEN DE CONFIGURACI N...

Страница 15: ...bilitar deshabilitar el funcionamiento de las 2 bombas individualmente decidir si se requiere alternancia de arranque o no permitir la activaci n individual o conjunta de las bombas y tambi n el uso o...

Страница 16: ...i n del bot n de paro manual de la activaci n del paro del sistema autom tico o finalmente podremos a adir una programaci n horaria independiente del estado de las bomba para activar desactivar el rel...

Страница 17: ...enci n directa del instalador En los ajustes de la detecci n contra el trabajo en seco podemos fijar un tiempo de rearme fijo de manera que las paradas por detecci n de trabajo sin agua no tendr n un...

Страница 18: ...in agua Comprobar que la bomba puede aspirar agua sin problemas y posteriormente compruebe el valor de sensibilidad introducido en el punto 8 PROTECCIONES BOMBA Un valor de sensibilidad excesivamente...

Страница 19: ...la garant a y eximir al fabricante de cualquier responsabilidad en caso de accidentes a personas o da os a la propiedad y o al producto en s Una vez que el producto ha sido recibido verifique que no h...

Страница 20: ...19 17 ESQUEMA DE MONTAJE Y DIMENSIONES...

Страница 21: ...20 17 ESQUEMA DE MONTAJE Y DIMENSIONES...

Страница 22: ...ELECTRICAL CONNECTIONS 25 8 SCREEN FORMAT 28 9 TYPES OF APPLICATION 29 10 START UP WIZARD 31 11 CONFIGURATION MENU 32 12 QUICK VIEW OF BASIC SETTINGS 35 13 WARNING MANAGMENT 35 14 ALARMS 36 15 MAINTEN...

Страница 23: ...ge unless a person responsible for their safety has ex plained the instructions and supervised the handling of the device Children should be prevented from playing with the device Do not use the devic...

Страница 24: ...ill be used Installation must be done by a qualified technician General device installation recommendations It should be installed in well ventilated environments without humidity and away from direct...

Страница 25: ...is recommended 300mA class A for domestic applications It is recommended in addition to the differential switch that the installation has a magne to thermal protection and an electrical main switch t...

Страница 26: ...potential free and support a maximum load of 5A at 230Vac Irrigation controller This input is used in case you need to enable the equipment through an irrigation controller Requires an external signal...

Страница 27: ...the pump Pressure switch Float switch Tank probes This input uses 2 or 3 contacts depending on the selection made as start stop device in menu 5 TYPE OF APPLICATION Only in case of selecting 3 tank pr...

Страница 28: ...s start stop device In the COMBINED application type it can be selected whether the pump to controlled by the pressure transducer is either pump 1 or pump 2 Input 1 This input uses 2 or 3 contacts dep...

Страница 29: ...n the COMBINED application type the device can be configured safety stop for pump 2 with the available options FLOAT SWITCH MINIMUM PRESSURE SWITCH and NO PROTECTION Input 4 In the COMBINED applicatio...

Страница 30: ...pump that takes the water from that tank and starts stops by means of a pressure switch or pressure transducer with a level float switch to prevent operation without water pump 2 In 2 pump systems pum...

Страница 31: ...rough float switches pressure transducer any level control device that provides a 4 20mA signal or by time programming To avoid dry running in addition to the built in current protection there is an i...

Страница 32: ...erentiate us if we are selecting the device for pump 1 or for pump 2 User can select connected device to start stop the pump The options available will depend on the type of application previously sel...

Страница 33: ...32 11 CONFIGURATION MENU...

Страница 34: ...33 11 CONFIGURATION MENU...

Страница 35: ...he operation of the 2 pumps individually decide whether or not to require start up alternation allow individual or joint activation of the pumps and also the use or not of the analog input to enable d...

Страница 36: ...rs of pump 1 and pump 2 individually We have an independent register for pump 1 and pump 2 where we can check over time the failures due to over consumption or due to dry work that they have had We ha...

Страница 37: ...SDUCER FAILURE The pressure transducer is missing damaged or not wired correctly Check that the transducer is connected with the correct polarity to the specific input for the pressure transducer If t...

Страница 38: ...y value entered in point 8 PUMP PROTECTIONS An excessively high sensitivity value can cause false dry work detection In this case set the sensitivity value that gives you a correct measurement PHASE F...

Страница 39: ...rranty and will exempt the manufacturer from any liability in the event of accidents to people or damage to property and or the product itself Once the product has been received verify that it has not...

Страница 40: ...39 17 ASSEMBLY AND DIMENSIONS DIAGRAM...

Страница 41: ...40 17 ASSEMBLY AND DIMENSIONS DIAGRAM...

Страница 42: ...5 UE Low Voltage Directiva 2009 125 CE Directiva 2011 65 UE RoHS II Directiva 2014 53 UE RED Directiva 2004 40 CE Directiva 2006 42 EC BOMBAS SACI S A Cam de Can Muntanyola 4 22 Pol Ind Palou Nord 084...

Отзывы: