Energy Plus
43
1
2
3
ENY-P1
ENY-P2
ENY-P3
ENY-P4
Filter, thickness 98, 285x405
F 7
M 6
425
Filter, thickness 98, 326x555
F 7
M 6
572
Filter, thickness 98, 408x595
F 7
M 6
615
Filter, thickness 98, 547x830
F 7
M 6
850
OUT
A
IN
Filters dimension Table
REPLACING THE FILTERS
(SIDE ACCESS)
Undo the Phillips head screws in the panels of
the filters. Open the filter inspection hatch and
take the filter out sideways.
Install the new filter and then close the panel
and secure it with the Philips screws.
RECOMMENDED
MAINTENANCE SCHEDULE
Replacing the filters: this depends on the level
of pollution in the air (dust, fumes, etc.).
The units are fitted with differential pressure
switches that control the pressure drop of the
filter.
The default setting of the differential
pressure switch is 120 Pa.
When this value is reached, the control board
sends a maintenance alert message to the wall
controller and the alarm symbol and filter pictogram
appear on the display (see the
T-EP
controller
on page 42).
MAINTENANCE