AUXILIARY SECTIONS
The Energy Plus heat recovery units can be matched
with the Ocean SB4 + BCR sections (condensate
collection tray) or with the Ocean SFE sections;
this is achieved by using the special Connecting
Duct.
The SB4 sections are equipped with a 4-row
heat exchange coil suitable to be fed with chilled
water.
The table below shows the recommended
combinations.
When ordering indicate the connections side of
the coil section; in the picture the connections
side is on the left.
Ocean air handling section with 4 row coil – Ocean SB4
ENY–P1
ENY–P2
ENY–P3
ENY–P4
SB4 1-2
SB4 1-2
SB4 3
SB4 4
ENP 1-2
ENP 1-2
ENP 3
ENP 4
BRC 1-2
BRC 1-2
BRC 3
BRC 4
0035004
0035004
0035019
0035034
9022116
9022116
9022316
9022416
9035020
9035020
9035021
9035022
+
+
+
+
+
+
+
+
i
denTificaTion
i
denTificaTion
i
denTificaTion
c
ode
c
ode
c
ode
c
onnecTing
d
ucT
o
cean
air
handling
secTion
wiTh
4
row
coil
o
cean
condensaTe
collecTion
Tray
for
h
eaT
r
ecovery
u
niT
Connecting Duct
Energy Plus
Air flow
Connecting
the valve actuator
of the post-treatment coil
The coil section can be used to cool the air before
release into the room, using a 2-pipe system for
cooling only, or to cool/heat, using a reversible
2-pipe system. It is equally possible to connect a
dual coil, in the case of a 4-pipe system, or a cooling
coil in combination with a post-heating electric coil.
The sections of post-treatment valves can be
managed by the main board. The valves are
open when the setpoint of the winter or summer
cooling temperature on return air is not reached
and closed if it is.