Energy Plus
32
AIR
ELECTRIC
POST-HEATING COIL
BER
(to be placed on the "Intake air"
duct)
E l e c t r i c h e a t i n g c o i l c o n s i s t i n g o f a r m o r e d
elements inserted inside a galvanised sheet
metal duct section with circular flanges and
rubber gasket. The electric coil can be used in
premises with air temperature between -20° C
and +40° C and is equipped with double safety
thermostat: one with automatic reset and one
with manual reset. Operation is controlled by
the ON/OFF logic in order to reach the setpoint of the
indoor air heating controlled by the temperature probe
on the return air flux. The resistance supply circuit is
fitted with an adjustable thermostat, which has
a limiting function. Protection class IP 43.
0
2
4
6
8
10
12
14
16
18
0
500
1000
1500
2000
2500
3000
BER40/6
BER35/5
BER25/2
BER25/3
0
2
4
6
8
10
12
14
16
18
0
500
1000
1500
2000
2500
3000
BER40/6
BER35/5
BER25/2
BER25/3
0
2
4
6
8
10
12
14
16
18
0
500
1000
1500
2000
2500
3000
BER40/6
BER35/5
BER25/2
BER25/3
Air flow rate (m
3
/h)
Pressure drop (Pa)
Pressure drop
BER
c
ode
9022114
9022214
9022314
9022414
2,1
230V 50Hz 1Ph + Pe
3,0
400V 50Hz 3Ph + Pe
4,5
6,0
9,1
13,0
7,2
8,7
250
250
355
400
270
300
600
690
kW
V/Hz/Ph
A
mm
m
3
/h
Rated power
Power supply voltage
Amperes absorbed by the resistance
Circular Flange Diameter
D
Minimum air flow rate
BER 25/2/M
BER 25/3/M
BER 35/5/T
BER 40/6/T
ENY–P1
ENY–P2
ENY–P3
ENY–P4
f
or
heaT
recovery
uniT
resisTance
i
denTificaTion
Supply air
Duct fitted
by the installer