26
EN
1.3
Coil connections positions
Filter (E)
Made of regenerable synthetic material removable
from below.
Condensate collection tray (F)
Made of plastic, it has the function of collecting the
condensate produced by the unit during the sum-
mer cooling phase and conveying it to the external
auxiliary tray equipped with hose connection.
Technical specifications
A-weighted sound pressure level < 70 dB(A).
For dimensions, weights and water content, see
p. 109
Operating limits
Fan coil unit
The basic specification of the fan coil and heat ex-
changer is given below:
Description
UoM
Value
Water flow
Highest working
pressure
bars
10
kPa
1000
Lowest water inlet
temperature
°C
+6
Highest water inlet
temperature
°C
+85
Power supply
Single-phase rated
operating voltage
V/Hz
230/50-60
Electric energy consumption: see technical data
label.
Valves
The technical specification of the valves with ther-
moelectric actuator is given below:
Description
UoM
Value
Water flow
Highest working pressure
bars
10
kPa
1000
Maximum glycol content in water
%
50
Highest water inlet temperature
°C
85
Power supply
Single-phase rated operating voltage
V/Hz
230/50-60
VA rating
VA
2,5
IP protection
IP
44
Initial opening and closing time
Seconds
75
Other technical data
All other important technical data (dimensions,
weights, connections, noise emissions, etc.) are giv-
en elsewhere in this User Information Manual, in the
separate technical documentation or in the technical
proposal.
Water flow rate limits for 2 row coil
Model
CFF-ECM
10
CFF-ECM
20
CFF-ECM
30
CFF-ECM
40
CFF-ECM
50
Water flow rate
Min.
l/h
40
80
120
Water flow rate
Max.
l/h
200
350
500
600
800
General notes on delivery
Notes for the installer.
The unit is supplied in cardboard packaging.
After removing the packaging, make sure the con-
tents are as requested and not damaged, and that
the machine components have not been damaged
by impacts.
Control if the threading of the tubes, which are pro-
truding from the unit, is all right.
In the event of damage or if the identification code
does not correspond to that ordered, contact your
dealer immediately, quoting the series and model.
Handling and storage
Notes for the installer.
The units must be handled by at least two persons.