Important notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In addition, the following points are to be observed:

–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to 
be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, 

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 
prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.

–  Consequential damages caused by a fault in this device are excluded from warranty or liability.

–  These devices must be installed by authorised specialists only.

–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous 
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.

–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat 

 irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.

–  This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.

–  Modifications of these records are not permitted.

–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Devices are to be connected under dead-voltage condition. Devices 
must only be connected to safety extra-low voltage. Consequential 
damages caused by a fault in this device are excluded from war-
ranty or liability. Installation of these devices must only be realized 
by authorized qualified personnel. The technical data and connect-
ing conditions shown on the device labels and in the mounting 
and operating instructions delivered  together with the device are 
exclusively valid. Deviations from the catalogue representation are 
not explicitly mentioned and are possible in terms of technical pro-
gress and continuous improvement of our products. In case of any 
modifications made by the user, all warranty claims are  forfeited. 
Operating this device close to other devices that do not comply with 
EMC directives may influence functionality. This device must not be 
used for monitoring applications, which solely serve the purpose of 
protecting persons against hazards or injury, or as an EMERGENCY 
STOP switch for systems or machinery, or for any other similar 
safety-relevant purposes.
Dimensions of enclosures or enclosure accessories may show slight 
tolerances on the specifications provided in these instructions. 
Modifications of these records are not permitted. 
In case of a complaint, only complete devices returned in original 
packing will be accepted. 

Notes regarding mechanical mounting and attachment:
Mounting shall take place while observing all relevant regulations 
and standards applicable for the place of measurement  
(e.g. such as welding instructions, etc.). Particularly the following 
shall be regarded:
–  VDE  ⁄  VDI  directive  technical  temperature  measurements,   

measurement set - up for temperature measurements.

– The EMC directives must be adhered to. 
– It is imperative to avoid parallel laying of current-carrying lines.
– We recommend to use shielded cables with  

the shielding being attached at one side to the DDC  ⁄  PLC.

Before mounting, make sure that the existing thermometer‘s techni-

cal parameters comply with the actual conditions at the place of 
 utilization, in particular in respect of:

– Measuring range 
– Permissible maximum pressure, flow velocity 
– Installation length, tube dimensions
– Oscillations, vibrations, shocks are to be avoided (<  0.5  g)
Attention! In any case, please observe the mechanical and thermal 
load limits of protective tubes according to DIN 43763 respectively 
according to specific S+S standards!

G  

Mounting and Installation

Содержание THERMASGARD RTM1

Страница 1: ...kalibrierf hig mit Modbus Anschluss G Operating Instructions Mounting Installation Room operating temperature sensor 3 on wall for temperature relative humidity dew point calibratable with Modbus conn...

Страница 2: ...RTM1 Modbus D G F r Ma zeichnung Geh use Dimensional drawing Enclosure Plan cot bo tier Baldur1 RTM1 Modbus mit Potentiometer with potentiometer avec potentiom tre T K 6 0 85 85 27 2 28 9 T K 6 0 85...

Страница 3: ...ozessanschluss mittels Schrauben Geh use Kunststoff Werkstoff ABS Farbe Reinwei hnlich RAL 9010 Abma e 85 x 85 x 27 mm Baldur 1 Montage Wandmontage oder auf UP Dose 55 mm Unterteil mit 4 Loch f r Befe...

Страница 4: ...ss mit ohne einstellbar DIP 6 EVEN gerade O N aktiv 1 Stoppbit O N aktiv O N ODD ungerade OFF inaktiv 2 Stoppbits OFF inaktiv OFF Die Baudrate bertragungsgeschwindigkeit wird ber Pos 1 und 2 des DIP S...

Страница 5: ...01 physikalischer Anzeigewert den Wert 10 enthalten Die Register 4x0002 bis 4x0012 enthalten Informationen ber die darzustellenden Zeichen und Segmente Der Dot Matrix Bereich ist ebenfalls in der Defa...

Страница 6: ...tiple Register Register Parameter Data Type Value Range 4x0001 physikalischer Anzeigewert Index im Display Unsigned 8 Bit 0 10 0 10 Temperatur 0 Defaulteinstellung Temperatur in C 1 1 Sollwert Potenti...

Страница 7: ...vierung Listen Only Mode Keine Antwort 10 L sche Z hler Echo Telegramm 11 Z hler Bustelegramme Unsigned 16 Bit alle g ltigen Bustelegramme 12 Z hler Kommunikationsfehler Parity CRC Framefehler etc Uns...

Страница 8: ...Repeater getrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabsch...

Страница 9: ...et Reklamationen werden nur vollst ndig in Originalverpackung angenommen Vor der Installation und Inbetriebnahme ist diese Anleitung zu lesen und die alle darin gemachten Hinweise sind zu beachten Die...

Страница 10: ...ange 0 50 C Temperature deviation 0 5 K at 20 C Zero point offset 10 C adjustable by potentiometer Ambient temperature storage 35 85 C operation 0 50 C Medium clean air and non aggressive non combusti...

Страница 11: ...eck selectable with without DIP 4 Bus termination selectable with without DIP 6 EVEN numbered O N Active 1 stop bit O N Active O N ODD numbered OFF Inactive no parity 2 stop bit OFF Inactive OFF Baud...

Страница 12: ...contain the value 10 The registers 4x0002 to 4x0012 contain information about the characters and segments to be displayed The dot matrix area is also programmable in the default setting register 4x000...

Страница 13: ...pe Value Range 4x0001 Physical parameter displayed Index on display Unsigned 8 Bit 0 10 0 10 Temperature 0 Default setting Temperature in C 1 1 Setpoint potentiometer in 2 2 Dew point in C 3 3 Relativ...

Страница 14: ...vation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 Bit All valid bus telegrams 12 Counter communication errors Parity CRC frame errors etc Unsigned...

Страница 15: ...several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply line and copper mesh wire shield must be used There...

Страница 16: ...ete devices returned in original packing will be accepted These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded Devices are to...

Страница 17: ...humidit relative point de ros e potentiom tre de consigne Plage de mesure 0 50 C Incertitude de mesure temp rature 0 5 K 20 C Point z ro offset 10 C r glable par potentiom tre Temp rature ambiante st...

Страница 18: ...stop O N actif O N ODD impair OFF inactif 2 bit stop OFF inactif OFF Le taux de Baud vitesse de transfert est r gl via les pos 1 et 2 de l interrupteur DIP B On peut r gler 9600 Baud 19200 Baud ou 384...

Страница 19: ...01 valeur d affichage physique doit contenir la valeur 10 Les registres 4x0002 4x0012 contiennent des informations sur les caract res et segments afficher La zone de matrice de points est galement pro...

Страница 20: ...nge 4x0001 Valeur d affichage physique Indice l cran Unsigned 8 bits 0 10 0 10 Temp rature 0 R glage par d faut T mp rature en C 1 1 Potentiom tre de consigne en 2 2 Point de ros e en C 3 3 Humidit re...

Страница 21: ...ly Mode mode coute seule Pas de r ponse 10 Efface compteur T l gramme d cho 11 Compteur T l grammes de bus Unsigned 16 Bit Tous les t l grammes de bus valides 12 Compteur Erreur de communication Parit...

Страница 22: ...ts le bus doit tre r parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de donn...

Страница 23: ...as de r clamation les appareils ne sont repris que dans leur emballage d origine et si tous les l ments de l appareil sont complets Avant de proc der toute installation et la mise en service veuillez...

Страница 24: ...rate parity Telegram indicator Reception LED green Error LED red LED internal status Offset correction temperature 10 C THERMASGARD RTM1 Modbus c Modbus 24 20 15 36 10 1 0 24 2 2 24 0 50 C 0 5 K 20 C...

Страница 25: ...A 1 8 0 247 DIP DIP 1 128 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBU...

Страница 26: ...1 C 7 4x0001 10 4 0002 4 0012 4x0001 0 7 4x0005 0 A 1 B 2 C 3 D 4 DP 5 6 7 8 9 10 11 12 13 14 15 A A B C D E F G B C D DP 14 1 14 2 14 4x0003 4x0004 0 A 1 B 2 C 3 D 4 E 5 F 6 G 7 G 8 H 9 I 10 J 11 K 1...

Страница 27: ...97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 132 142 148 153 154 223 A...

Страница 28: ...03 16 0 1000 0 100 0 3x0004 16 0 500 0 50 0 C 3x0005 16 0 1000 0 100 0 08 Diagnostics 00 Loopback 01 Modbus Reset Listen Only Mode 04 Listen Only Mode 10 11 16 12 CRC 16 13 16 14 16 15 16 0 17 Report...

Страница 29: ...6 Modbus Modbus 32 1 247 100 Profibus r THERMASGARD RTM 1 Modbus Rev 2016 V12 RU intro Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D 5 B GND B D0 D MODBUS RTU Master Slave 1...

Страница 30: ...30 r ZVEI VDE EMV VDE VDI DDC PLC 0 5 g DIN 43763 S S r...

Страница 31: ...up the bottom frame slightly Pull top cover forward and hold it Pour ouvrir le bo tier placer le tournevis 2 0 au centre de l encoche pousser vers le bas et soulever l g rement le cadre inf rieur Tir...

Страница 32: ...1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1 130 1 0 0 0 0 0 1 0 131 1 0 0 0 0 0 1 1 132 1 0 0 0 0 1 0 0 133 1 0 0 0 0 1 0...

Отзывы: