THERMASGARD

®

  RTM 1- Modbus

  |  Télégrammes

Function 04 Read Input Register

Registre

Paramètre

Data Type

Value

Range

3x0001

Température

4 s  balayage

Signed 16 Bit

– 350...+ 800

– 35.0  ...  + 80.0 °C

3x0002

Température

Filtrage

Signed 16 Bit

– 350...+ 800

– 35.0  ...  + 80.0 °C

3x0003

Potentiomètre de consigne

Signed 16 Bit

0...1000

0...100.0 %

3x0004

Point de rosée

Valeur calculée

Signed 16 Bit

0... 500 

0...+ 50.0  °C

3x0005

Humidité relative

Filtrage

Signed 16 Bit

0...1000

0...100.0 %  h.r.

Functionn 08 Diagnostics 

Les 

codes sous-fonction

 suivants sont pris en charge 

Code sous-  

fonction

Paramètre

Data Type

Réponse

00

Écho des données d'émission 

(loopback-rebouclage)

Données d'écho

01

Redémarrage Modbus 

(Reset Listen Only Mode –  

Réinit Mode Écoute Seule)

Télégramme d'écho

04

Activation Listen Only Mode 

(mode Écoute seule)

Pas de réponse

10

Efface compteur

Télégramme d'écho

11

Compteur Télégrammes de bus

Unsigned 16 Bit

Tous les télégrammes de bus valides

12

Compteur Erreur de communication 

(Parité, CRC, erreur Frame, etc.)

Unsigned 16 Bit

Télégrammes de bus erronés

13

Compteur Messages d'exception

Unsigned 16 Bit

Compteur d'erreurs

14

Compteur Télégrammes esclaves

Unsigned 16 Bit

Télégrammes esclaves

15

Compteur Télégrammes sans réponse

Unsigned 16 Bit

Message de Broadcast (adresse A)

Function 17 Report Slave ID 

Structure du télégramme de réponse 

n° de byte

Paramètre

Data Type

Réponse

00

Nombre de bytes

Unsigned 8 Bit

6

01

ID  esclave (Device Type)

Unsigned 8 Bit

4 = 

THERMASGARD

®

 MODBUS

02

ID  esclave (Device Class)

Unsigned 8 Bit

10 = 

THERMASGARD

®

 / 

THERMASREG

®

03

Statut 

Unsigned 8 Bit

255 = RUN, 0 = STOP

04

Numéro de version (release)

Unsigned 8 Bit

1...9

05

Numéro de version (version)

Unsigned 8 Bit

1…99

06

Numéro de version (index)

Unsigned 8 Bit

1

Содержание THERMASGARD RTM1

Страница 1: ...kalibrierf hig mit Modbus Anschluss G Operating Instructions Mounting Installation Room operating temperature sensor 3 on wall for temperature relative humidity dew point calibratable with Modbus conn...

Страница 2: ...RTM1 Modbus D G F r Ma zeichnung Geh use Dimensional drawing Enclosure Plan cot bo tier Baldur1 RTM1 Modbus mit Potentiometer with potentiometer avec potentiom tre T K 6 0 85 85 27 2 28 9 T K 6 0 85...

Страница 3: ...ozessanschluss mittels Schrauben Geh use Kunststoff Werkstoff ABS Farbe Reinwei hnlich RAL 9010 Abma e 85 x 85 x 27 mm Baldur 1 Montage Wandmontage oder auf UP Dose 55 mm Unterteil mit 4 Loch f r Befe...

Страница 4: ...ss mit ohne einstellbar DIP 6 EVEN gerade O N aktiv 1 Stoppbit O N aktiv O N ODD ungerade OFF inaktiv 2 Stoppbits OFF inaktiv OFF Die Baudrate bertragungsgeschwindigkeit wird ber Pos 1 und 2 des DIP S...

Страница 5: ...01 physikalischer Anzeigewert den Wert 10 enthalten Die Register 4x0002 bis 4x0012 enthalten Informationen ber die darzustellenden Zeichen und Segmente Der Dot Matrix Bereich ist ebenfalls in der Defa...

Страница 6: ...tiple Register Register Parameter Data Type Value Range 4x0001 physikalischer Anzeigewert Index im Display Unsigned 8 Bit 0 10 0 10 Temperatur 0 Defaulteinstellung Temperatur in C 1 1 Sollwert Potenti...

Страница 7: ...vierung Listen Only Mode Keine Antwort 10 L sche Z hler Echo Telegramm 11 Z hler Bustelegramme Unsigned 16 Bit alle g ltigen Bustelegramme 12 Z hler Kommunikationsfehler Parity CRC Framefehler etc Uns...

Страница 8: ...Repeater getrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabsch...

Страница 9: ...et Reklamationen werden nur vollst ndig in Originalverpackung angenommen Vor der Installation und Inbetriebnahme ist diese Anleitung zu lesen und die alle darin gemachten Hinweise sind zu beachten Die...

Страница 10: ...ange 0 50 C Temperature deviation 0 5 K at 20 C Zero point offset 10 C adjustable by potentiometer Ambient temperature storage 35 85 C operation 0 50 C Medium clean air and non aggressive non combusti...

Страница 11: ...eck selectable with without DIP 4 Bus termination selectable with without DIP 6 EVEN numbered O N Active 1 stop bit O N Active O N ODD numbered OFF Inactive no parity 2 stop bit OFF Inactive OFF Baud...

Страница 12: ...contain the value 10 The registers 4x0002 to 4x0012 contain information about the characters and segments to be displayed The dot matrix area is also programmable in the default setting register 4x000...

Страница 13: ...pe Value Range 4x0001 Physical parameter displayed Index on display Unsigned 8 Bit 0 10 0 10 Temperature 0 Default setting Temperature in C 1 1 Setpoint potentiometer in 2 2 Dew point in C 3 3 Relativ...

Страница 14: ...vation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 Bit All valid bus telegrams 12 Counter communication errors Parity CRC frame errors etc Unsigned...

Страница 15: ...several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply line and copper mesh wire shield must be used There...

Страница 16: ...ete devices returned in original packing will be accepted These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded Devices are to...

Страница 17: ...humidit relative point de ros e potentiom tre de consigne Plage de mesure 0 50 C Incertitude de mesure temp rature 0 5 K 20 C Point z ro offset 10 C r glable par potentiom tre Temp rature ambiante st...

Страница 18: ...stop O N actif O N ODD impair OFF inactif 2 bit stop OFF inactif OFF Le taux de Baud vitesse de transfert est r gl via les pos 1 et 2 de l interrupteur DIP B On peut r gler 9600 Baud 19200 Baud ou 384...

Страница 19: ...01 valeur d affichage physique doit contenir la valeur 10 Les registres 4x0002 4x0012 contiennent des informations sur les caract res et segments afficher La zone de matrice de points est galement pro...

Страница 20: ...nge 4x0001 Valeur d affichage physique Indice l cran Unsigned 8 bits 0 10 0 10 Temp rature 0 R glage par d faut T mp rature en C 1 1 Potentiom tre de consigne en 2 2 Point de ros e en C 3 3 Humidit re...

Страница 21: ...ly Mode mode coute seule Pas de r ponse 10 Efface compteur T l gramme d cho 11 Compteur T l grammes de bus Unsigned 16 Bit Tous les t l grammes de bus valides 12 Compteur Erreur de communication Parit...

Страница 22: ...ts le bus doit tre r parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de donn...

Страница 23: ...as de r clamation les appareils ne sont repris que dans leur emballage d origine et si tous les l ments de l appareil sont complets Avant de proc der toute installation et la mise en service veuillez...

Страница 24: ...rate parity Telegram indicator Reception LED green Error LED red LED internal status Offset correction temperature 10 C THERMASGARD RTM1 Modbus c Modbus 24 20 15 36 10 1 0 24 2 2 24 0 50 C 0 5 K 20 C...

Страница 25: ...A 1 8 0 247 DIP DIP 1 128 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBU...

Страница 26: ...1 C 7 4x0001 10 4 0002 4 0012 4x0001 0 7 4x0005 0 A 1 B 2 C 3 D 4 DP 5 6 7 8 9 10 11 12 13 14 15 A A B C D E F G B C D DP 14 1 14 2 14 4x0003 4x0004 0 A 1 B 2 C 3 D 4 E 5 F 6 G 7 G 8 H 9 I 10 J 11 K 1...

Страница 27: ...97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 132 142 148 153 154 223 A...

Страница 28: ...03 16 0 1000 0 100 0 3x0004 16 0 500 0 50 0 C 3x0005 16 0 1000 0 100 0 08 Diagnostics 00 Loopback 01 Modbus Reset Listen Only Mode 04 Listen Only Mode 10 11 16 12 CRC 16 13 16 14 16 15 16 0 17 Report...

Страница 29: ...6 Modbus Modbus 32 1 247 100 Profibus r THERMASGARD RTM 1 Modbus Rev 2016 V12 RU intro Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D 5 B GND B D0 D MODBUS RTU Master Slave 1...

Страница 30: ...30 r ZVEI VDE EMV VDE VDI DDC PLC 0 5 g DIN 43763 S S r...

Страница 31: ...up the bottom frame slightly Pull top cover forward and hold it Pour ouvrir le bo tier placer le tournevis 2 0 au centre de l encoche pousser vers le bas et soulever l g rement le cadre inf rieur Tir...

Страница 32: ...1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1 130 1 0 0 0 0 0 1 0 131 1 0 0 0 0 0 1 1 132 1 0 0 0 0 1 0 0 133 1 0 0 0 0 1 0...

Отзывы: