The calibrateable humidity and temperature sensor HYGRASGARD
®
VFF / VFTF measures the relative humidity and temperature of air. It converts
the measurands humidity and tempe rature into standard signals of 0 - 10 V. The showcase sensor HYGRASGARD
®
VFF / VFTF is especially designed
for installation in ceilings or walls, inside showcases or display cabinets, in museums, galleries, movie theatres, in lecture halls or laboratories. The
measuring element is contained inside a stainless steel probe, the sensor is pluggable on one side or optional on two sides, at the probe and ⁄ or
at the electronics enclosure. Because of its very little height (ca. 5 mm) it hardly builds up and is almost unconsiderable.
TECHNICAL DATA:
Power supply: ........................ 24 V AC ⁄ DC (± 10 %)
(half-wave rectification, observe instructions!)
Power consumption: ................ < 1 VA ⁄ 24 V DC
Current consumption: .............. max. 10 mA at 24 V DC
Sensors: ............................... digital humidity sensor with integrated temperature sensor, high long-term stability
Sensor protection: ..................
stainless steel,
1.4571, V2A
protective sleeve: Ø = 10 mm,
nominal length NL = ca. 42 mm,
probe head: Ø = 25 mm
HUMIDITY:
Measuring range, humidity: ....... 0 …100 % r. H.
Operating range, humidity: ....... 10 … 99 % r. H.
Deviation, humidity: ................. ± 2 % r. H. (30…70 %) at +20 °C, otherwise ± 3 % r. H.
Output, humidity: .................... 0 - 10 V
TEMPERATURE:
Measuring range, temperature: ....... 0 ...+50 °C
Operating range, temperature: ....... 0 ...+50 °C
Deviation, temperature: ........... ± 0.3 K at 20 °C
Output, temperature: .............. 0 -10 V
Ambient temperature: ............. storage - 20 …+ 50 °C
operation 0 …+ 50 °C
Electrical connection: .............. 3- or 4-wire connection (see connecting diagram),
0.14 - 1.5 mm², via terminal screws on circuit board
Enclosure: ............................. plastic, material polyamide, 30 % glass-globe-reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour pure white (similar RAL 9010), enclosure cover for display is transparent !
Enclosure dimensions: ............. 72 x 64 x 37.8 mm (Thor III without display)
72 x 64 x 43.3 mm (Thor III with display)
Probe: .................................. stainless steel,
L = 42 mm, Ø =25 mm
Sensor cable: ......................... 2 m, PVC, 4 x 0.14 mm²
(optional also other lengths)
Cable gland: ........................... M16 x 1.5 , including strain relief, exchangeable, max. inner diameter 10.4 mm
Long-term stability:................. ± 1 % per year
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 65 (according to EN 60 529)
Standards: ............................ CE conformity,
according to EMC directive 2004 ⁄ 108 ⁄ EC,
according to EN 61326-1: 2006, according to EN 61326-2-3: 2006
ACCESSORIES: ....................... see last chapter
Optional: ............................... single-line
display,
cutout ca. 36 x15 mm (W x H),
for displaying ACTUAL temperature and ⁄ or ACTUAL humidity
Type ⁄ WG1
Designation
Measuring Range ⁄ Readout
Humidity Temperature
Output
Humidity Temperature
Item No.
Probe pluggable
U - variant
VFF1-U
0 …100 % r. H.
–
0 -10 V
–
1201-6110-0000-000
VFTF1-U
0 …100 % r. H.
0…+50 °C
0 -10 V
0 - 10 V
1201-6111-0000-000
Spare part
Probe
SFTF V2
Probe (sensor) pluggable, as replacement element
7201-6100-0000-002
Extra charge:
Single-line display,
shifting
4-wire connecting leads (
PVC
) per running meter