3.3.6) 

P

rogrammable Clock

The "Programmable Clock" screen  

  , "System" view,  

   allows you to program the system 

so that it behaves in a speci

fi

 c way:

• 

 Weekly planning.                                  * Planning state changes during the week.

• 

 Duration programming.                         * Programming a maximum production duration.

• 

 No programming:                                  * Basic system behaviour.

3.3.6.1) Weekly Planning

  

The 

 action button activates the ‘Planner settings’ tab:

This table shows the list of actions planned for the week (max. 14 actions), with their details (day - time 
- state wanted). 

The 

 sign at the end of a line allows you to delete the action from the list.

To add a new action, click on the 

 sign of the last line and choose the day - time - state of the 

action.

Содержание MV3-IM Series

Страница 1: ...ER Guide Hot runner temperature control Software MV3 IM and MV3 Series Multizone Controllers Written by K PERRIN Date 08 04 19 Approved by NCN Date 08 01 20 Change history Date Change description A 08...

Страница 2: ...s 18 3 1 2 Temperature control configuration 18 3 1 2 1 Temperature control configuration settings 18 3 1 2 2 Ramp Softstart Settings 19 3 1 2 3 Heating zone configuration 21 3 1 2 4 Zone Groups 26 3...

Страница 3: ...ion 46 3 3 A 46 3 3 1 Remote log in 46 3 3 2 Communication 47 3 3 3 System information 47 3 3 3 1 Restoring factory settings 48 3 3 3 2 Loading a company logo 48 3 3 4 Data acquisition 49 3 3 4 1 Data...

Страница 4: ...fter a few seconds the display screen lights up System type Serial number Software version 2 GENERAL PRESENTATION OF THE INTERFACE 2 1 C The user interface always displays these 3 elements Status bar...

Страница 5: ...graphical user interface The status bar blinks red if alarms are triggered The contents of the Action bar depend on the screen currently in view and display icons which act directly on system settings...

Страница 6: ...e level 2 enter the default password for this level 123456 to confirm press to change to privilege level 0 enter the password of the current level to confirm press To change the passwords for privileg...

Страница 7: ...mbnail to access the screen Press the tab to return to this display Press the Zone configuration table thumbnail to go to that screen You can now check the status of the control zones by clicking on t...

Страница 8: ...software configuration options The table below gives a summary of the screens available under the di erent tabs Tab Screen System Configuration files Operating Mode Time Programming Scheduling Documen...

Страница 9: ...ed zoom level and on the screen size The color indicates the status of the zone Red zone with alarm Green zone without alarm Grey zone OFF Blue zone with low temperature alarm Purple zone using the te...

Страница 10: ...its setpoint can be gradually reached The zone is in Boost mode 3 1 2 1 3 1 2 3 The zone is backed up the power applied to the zone is identical to the power applied to the slave zone 3 1 2 3 The zon...

Страница 11: ...e is above setpoint High temperature alarm Cut Thermocouple Reversed Thermocouple The zone is in manual mode after the thermocouple has been cut This function must be previously activated 3 1 2 1 Zone...

Страница 12: ...nce The zoom level can be changed in either of two ways either by swiping diagonally upwards to zoom in displaying fewer zones and diagonally downwards to zoom out displaying more zones or by using th...

Страница 13: ...y specifically selected zones These zones can be selected by pressing a zone which is then highlighted in orange Selected zone Pressing an already selected zone deselects it It is also possible to sel...

Страница 14: ...tion Software configuration is done during its first use or occasionally if you want to change an overall software setting 3 1 1 1 General configuration The overall settings of the software can be con...

Страница 15: ...his option is used to select the action of the STANDBY input see 6 4 of the Operating instructions Possible options are No action the input is ignored Standby if the input is open the system enters St...

Страница 16: ...ace click on the corresponding flag The time zone parameter must be specified when a time server is used 3 1 1 4 and for the automatic calculation of summer winter time The modifications are confirmed...

Страница 17: ...network is working The icon indicates that the system is not connected When using a remote screen or VNC client display network configuration will not be possible 3 1 2 Temperature control configurat...

Страница 18: ...o continue Boost duration The duration of the Boost function can be set in this field For more information on this function see 3 1 2 3 Configuring Boost value and 3 1 2 5 The Boost function can unblo...

Страница 19: ...within the maximum gradient A During cooling slope E will be applied down to temperature I considered cold and the fastest zones will follow the slowest zones Staggered ramp gg This ramp uses the gro...

Страница 20: ...minimum Uncontrolled cooling time Optimized cooling time Maximum cooling time Power restriction In all four start up modes power is limited to 15 at the start of the ramp for 1 minute or until the zon...

Страница 21: ...ignment to groups Quick zone modification Current setpoint On O Operating mode You can change the setpoint value currently used for the selected zone s According to the current Automatic or Manual mod...

Страница 22: ...onfigured In manual mode a power level to be applied can be specified manually The temperature is not monitored at all in this case The control system allows the user to configure 2 temperature setpoi...

Страница 23: ...h the problem of defective thermocouple probes For instance if the thermocouple of zone 1 malfunctions during production the job can still be finished by configuring the zone 1 to use the thermocouple...

Страница 24: ...r Monitoring Mode In control mode the zone controls the applied power in order to reach a setpoint In monitor only mode no power is applied Only the temperature is monitored and associated alarms can...

Страница 25: ...ccessible in the Control view You must first create a group and then assign zones to it You can then display a selected group to modify its contents or delete a selected group Creating a zone group To...

Страница 26: ...roups Group name Group type icon manifolds or nozzles This screen shows which zones are assigned to each of the various groups The composition of the various groups can be seen by pressing the and ico...

Страница 27: ...in the entry screen which is displayed 3 1 2 5 Zone configuration table To access this screen press the Control tab twice and select the Zone configuration table screen Changes the setting for zones...

Страница 28: ...s are accessible from the Quick change action bar of the configuration 3 1 3 Configuration files Configuration files enable you to store the whole configuration of the hot runner system for a given mo...

Страница 29: ...re in the column then wait 5 minutes 6 Apply reference values Control view Mold monitoring screen Power monitoring table in the sub menu select Save measurements 3 2 4 3 Once these operations have bee...

Страница 30: ...e product Notes optional notes on the configuration file Finally you must confirm Hundreds of files can be created 3 1 3 2 Displaying a configuration file It is possible to view the contents of a file...

Страница 31: ...d configuration changes 4 Go to the Configuration files screen System view 5 Press Since changing a file involves irretrievably deleting the old configuration a confirmation dialogue will appear each...

Страница 32: ...access to and Export a file To export a configuration file 1 Go to the Configuration files screen System view 2 Choose the file to be exported in the list on the left the name of the file is highlight...

Страница 33: ...rt a configuration file in PDF format 1 Go to the Configuration files screen System view 2 Choose the file to be exported as a PDF file in the list on the left the name of the file is highlighted and...

Страница 34: ...is a temporary state 3 1 2 2 Stop No zone is heating but the system is turned on It is in this state that it is recommended to make all the pre settings Transitional states When some state changes are...

Страница 35: ...et di erently in the Control view on the Temperature control settings page the Start up mode on power up can be set You can choose Stop Standby or Production The mode at power up will also depend on t...

Страница 36: ...tion bar Icon Action Activate deactivate selected zones 3 1 2 3 Toggle selected zones between manual and automatic mode 3 1 2 3 Raise lower setpoint of selected zones in stages Give access to the zone...

Страница 37: ...Standby the setpoint applied to the zone will be the temperature setpoint for the Standby state If the zone is configured in manual mode and the system in Production the setpoint applied to the zone...

Страница 38: ...me date or alarm type in increasing or decreasing order An upturned or downturned triangle marks the sort parameter and shows the direction of sorting in increasing or decreasing order Any alarm may b...

Страница 39: ...wires of the thermocouple are reversed Defective Triac triac is faulty on a zone Abnormal current the current of the zone di ers from the saved current reference value Lack of Phase phase of the zone...

Страница 40: ...when a mold is first installed or after mold maintenance to check the integrity of the mold and its connections The screen to be used for this test can be found in the Control view MoldScan screen Thi...

Страница 41: ...le zones Once the parameters have been set or checked press the button The system switches then to the MoldScan state At the end of the analysis the system switches to the Stop state You can stop the...

Страница 42: ...enu Mold monitoring o ers 3 tables the first column of which contains the zones by groups These details can be viewed zone by zone by pressing on the line of a particular group The Zones without group...

Страница 43: ...Once the control zone is monitored drift is detected by comparing the applied power values with safety tolerances set by the user When the monitoring system detects an anomaly it displays an alarm sy...

Страница 44: ...y system of quantities ohms watts amperes Applying reference values To have valid reference values the values must be saved in the Save measurements sub menu Actions that can be performed from the sub...

Страница 45: ...hen the application has started up enter the interface s IP address available on the Network Configuration screen 3 1 1 4 or an address in the format hostname local with hostname being also available...

Страница 46: ...xternal machine Communication can be set in the Configuration view External parameters screen Up to 3 simultaneous communication channels can be configured 3 3 3 System information System information...

Страница 47: ...original factory settings All control settings will be reset Upon pressing this button the interface resets completely 3 3 3 2 Loading a company logo When connecting a USB device the Import company l...

Страница 48: ...di erent landscape screen You can toggle between displays by clicking on Data recording y or Curves portrait screen The two displays are one above the other 3 3 4 1 Data recording The Data recording...

Страница 49: ...o samples must be changed by clicking on the Time between two samples input field by moving the Time between two samples cursor You can then start the acquisition by pressing stops recording Once the...

Страница 50: ...r Temperature is displayed as a solid line the setpoint as a fine dotted line and the power applied as dashes Time scale can be changed using the Zoom in and Zoom out icons A scroll bar located under...

Страница 51: ...ntation files screen System view allows you to display various factory installed documents like Operating instructions Connection diagrams Double click on the name of the document you wish to view to...

Страница 52: ...week Duration programming Programming a maximum production duration No programming Basic system behaviour 3 3 6 1 Weekly Planning The action button activates the Planner settings tab This table shows...

Страница 53: ...g is activated When the controller is powered on after a planned date the start up mode applied will be the one set as Start up mode on power up see 3 1 2 3 3 6 2 Duration Programming The action butto...

Страница 54: ...obe of a nearby zone Drop in temperature and the status bar blinks red Reversed thermocouple Low temperature alarm activated Reverse the polarities then set the zone to OFF and then to ON to acknowled...

Страница 55: ...lied is equal to 0 and the element heats permanently that means that the triac or the heater is in short circuit Switch o the system immediately Check the triac or the control card in question Check a...

Страница 56: ...s red Load partially deteriorated Heating element fault alarm activated Replace the heating element Temperature increases The symbol appears and the status bar blinks red Abnormally high temperature e...

Страница 57: ...disposal France USA Germany Tel 33 4 74 77 34 53 1 404 495 5968 49 621 5458 1654 Fax 33 4 74 73 90 18 1 404 795 0849 49 621 5458 2086 e mail sise sise plastics com sales us sise plastics com verkauf d...

Страница 58: ...Page 59 60 SISE_M_REGUL_SerieM_MV3 IM_MV3 TS_V7 3_20200108_B_En www sise plastics com...

Страница 59: ...s network SISE is your worldwide partner www sise plastics com STUTTGART SHANGHAI ATLANTA BRESIL OYONNAX Voie Romaine Groissiat 01100 OYONNAX FRANCE Tel 33 4 74 77 34 53 Fax 33 4 74 73 90 18 sise sise...

Отзывы: