background image

5

To reset the system and leave the door open:

Activate the Stop input or push the Open Jog/Reset
button on the Digital Gateway. The system will reset
and the door will remain open.

This input is inactive when the door is opening or
when the door is closed (on the close limit switch).

A loss of this connection for two seconds while the
door is open (LSO on) will keep the door from closing.
This is an alarm condition. The EdGE message will be
displayed and the reversing edge LED will blink.

To reset the system:

  Re-establish the connection,

then push the Open Jog/Reset button, or the Stop
input. (See ALARM CONDITIONS on page 9.)

OLR (Overload Relay)—Terminal 18 (N.O. Contact)

When the overload relay in the control box detects a
motor malfunction it will trip and turn the motor
contactors off. It will also send a signal to the Digital
Gateway by closing the contact connected to terminal
18. The OLr message will be displayed and blink and
the OLR LED will be on.

Once the malfunction has been corrected and the
overload reset, the OLR LED will go out, but the
Alarm Condition message OLr will continue to blink
until the system is reset. Reset the system by press-
ing the Open Jog/Reset button or the Stop input.

Open—Terminal 20 (N.O. Contact)

A momentary connection while the door is closed,
closing or stopped between limits will open the door.
This input is ignored during the opening cycle.

Close—Terminal 21 (N.O. Contact)

A momentary connection while the door is opened or
stopped between limits will close the door. This input
is ignored when the door is closed or during the
opening cycle.

Stop/Reset—Terminal 23 (N.C. Contact)

A momentary loss of this connection will stop the door
while it is opening or closing when the door was
activated by the Open or Close inputs.

This input can also be used as a remote reset for
Alarm Conditions. It will reset the system the same as
the Open Jog/Reset button.

Program 2—Terminal 24 (N.O. Contact)

This input has various functions that are explained in
the Programming section of this manual. (See OP-
TIONAL PROGRAMS on page 13.)

The default function is the LOC command. When a
connection is present and the door is closed (LSC on)
the Digital Gateway will be idle. The LOC message
will be displayed and no inputs will be active. Remov-
ing the connection will return the Digital Gateway to
normal operation.

Program 3—Terminal 26 (N.C. Contact)

This input has various functions that are explained in
the Programming section of this manual. (See OP-
TIONAL PROGRAMS on page 13.)

The default function is Photoeye AC. A loss of this
connection while the door is closing will immediately
reverse the door to the open position. The door will
remain open as long as the object is in the path of the
photoeye beam.

After the obstruction has been removed the door will
remain open (if it was originally opened by a nonauto-
matic activator: A/A, PB1 or Open-Close) until it is
closed by a nonautomatic activator. The door will
close automatically if it was originally opened with an
automatic activator (Auto or PB1-A/A with A/A Close
Delay timer on).

If the photoeye is activated while either Close Delay
timer is timing down, the timer will reset and resume
timing down after the photoeye beam has been
cleared.

The photoeye input is inactive while the door is closed
or opening.

LSB (Breakaway Kill Switch)—Terminal 27 (N.C.
Contact)

The breakaway kill switches are connected to this
input. If the breakaway bottom bar is hit and comes
apart the connection to terminal 27 is lost. The Digital
Gateway will turn off the motor contactors and the
door will stop and not operate until the system is
reset. The AJAr message will be displayed and the
LSB LED will blink.

To reset the system:

 Reassemble the breakaway

bottom bar and press the Open Jog/Reset button on
the Digital Gateway or the Stop input.

INPUTS TO THE  DIGITAL  GATEWAY—AC  INPUTS

Содержание DG1200

Страница 1: ...Revision April 15 1998 0 215 006 Rytec Corporation Digital Gateway Installation Owners Manual Model DG1200...

Страница 2: ......

Страница 3: ...NPUTS TOTHE DIGITAL GATEWAY AC INPUTS 4 Limit Switches Terminals 8 and 9 4 OPEN LSO 4 CLOSE LSC 4 PB1 Pushbutton Terminal 11 4 Alternate Action Inputs A A Momentary Contact Activators Terminal 12 4 Au...

Страница 4: ...UP PROCEDURES 8 ALARM CONDITIONS COnnECt MISSING CONNECTIONS 9 OP 0 OPEN TIME EXCEEDED 9 CL 0 CLOSE TIME EXCEEDED 10 AJAr BREAKAWAY KILL SWITCH 10 OLr OVERLOAD RELAY 10 EdGE REVERSING EDGE 10 NON ALA...

Страница 5: ...assage Limit Switch LSP 14 PROGRAM 4 PROGRAMMABLE OPTIONS 15 Close Jog 15 Open Jog 15 Reverse Delay 15 Loop Call Delay 15 PROGRAM 5 REVERSE INPUT LOGIC 15 PROGRAM 6 15 SETTING THE PROGRAM OPTIONS 15 D...

Страница 6: ...This page intentionally left blank...

Страница 7: ...oten tial for personal injury if the procedure is not performed as described CAUTION is used to indicate the potential for damage to the product or property dam age if the procedure is not followed as...

Страница 8: ...r an overview of the Digital Gateway controls A0500028 DOWN Arrow Auto Close Delay Timer A A Close Delay Timer UP Arrow Display Message Explanation CLOSE Backup Timer OPEN Backup Timer Digital Display...

Страница 9: ...button will operate while the Digital Gateway is in the AJAr or EdGE alarm condition See Figure 1 CLOSE JOG This pushbutton jogs the door closed It is not operational when the door is being controlled...

Страница 10: ...rnate Action Inputs A A Momentary Contact Activators Terminal 12 N O Contact A momentary connection while the door is closed closing or stopped between limits will open the door A momentary connection...

Страница 11: ...Conditions It will reset the system the same as the Open Jog Reset button Program 2 Terminal 24 N O Contact This input has various functions that are explained in the Programming section of this manu...

Страница 12: ...closed closing or stopped between limits The door will remain open as long as the connection is present When the connection is removed the Auto Close delay timer will count down and close the door Th...

Страница 13: ...be displayed as OP plus time CLOSE BACKUPTIMER This is the backup timer for the closing of the door It functions the same as the open backup timer When the time has been exceeded the CL 0 message will...

Страница 14: ...kup Timer A0500027 Figure 7 START UP PROCEDURES 1 Install the door following the procedures outlined in the door installation manual 2 Make all necessary electrical connections Follow the electrical s...

Страница 15: ...s must be present If neither of the limit connections are present both the LSO and LSC LEDs will blink If the limits are wired correctly and the Digital Gateway still shows a missing limit connection...

Страница 16: ...box has tripped The display message OLr will blink and the OLR LED will be on Find and correct the problem that caused the overload relay to trip reset the overload relay and reset the Digital Gatewa...

Страница 17: ...ateway is reset with the Open Jog Reset button or Stop input See Figure 14 HELLO A0500027 Figure 14 EdGE REVERSING EDGETRIPPED The message EdGE will be displayed if the door comes down on something ac...

Страница 18: ...puts of the Digital Gateway share a common power source which is terminal 4 Terminal 4 is internally connected to the 24 vac power source Terminal 5 is the open output supplying power to the open cont...

Страница 19: ...ilable program follows See SETTING THE PROGRAM OPTIONS on page 15 for programming instructions PROGRAM 1 OUTPUT 7 This output can tell you if the door is not closed fully open or about to close When o...

Страница 20: ...r is fully closed the door will open and the Passage timer PEt will begin counting down When the Passage timer reaches zero the door will stop Activating this input again will close the door If the A...

Страница 21: ...on the loop long enough to open the door but traffic approaching the door will activate the door When the Loop input is activated while the door is fully closed the Loop timer will count down and then...

Страница 22: ...e digits of the security code then press the Set button to enter the Program Mode 3 Once you have entered the program mode the display will show the various program menus See Figure 21 Press the Selec...

Страница 23: ...with a normally open N O or a normally closed N C contact connected to them See PROGRAM 5 REVERSE INPUT LOGIC on page 15 The various models of Rytec doors require slightly different combinations of N...

Страница 24: ...93 A1D1 193 A1D1 193 A1C1 MOTOR DATA 230 208 VOLTAGE 460 575 2 9 FLA 1 8 0 97 0 7 150 ma MAX 20 21 23 26 4 28 29 27 30 5 OPEN CLOSE 4 M1C M1O OLR X2 2 3 1 4 CONNECTED INTERNALLY DIGITAL GATEWAY LSO 5...

Страница 25: ...al infor mation only Due to varying require ments for individual customers a schematic is prepared for each door installation This schematic is shipped inside of the control box and must be used for t...

Страница 26: ...8 CONNECTED INTERNALLY 1 4 5 5 2 3 X2 BY OTHERS SEE MOTOR TABLE FOR FUSE SIZE 1 FUSED DISCONNECT L2 L3 L1 BY RYTEC 5 18 CLOSE 4 19 M1O M1C OLRL M1C M1O OLRH OPEN MOTOR LO MOTOR HI BRAKE MOTOR X2 4 5...

Отзывы: