REVT-05ERV 19
Object Name
Description (Control Points)
Instance Number
SAFLOW-SP-IN
Supply Air Flow Set Point Input (For the units with VFD)
AV 10188
EAFLOW-SP-IN
Exhaust Air Flow Set point Input (For the units with VFD)
AV 10091
CO2-SP-IN
CO2 Set point Input (For the units with VFD)
AV 10185
HTG-SP
Heating Set Point (For the units with Gas Heat)
AV 21236
PREHEAT-SP
Pre Heat Set Point (For the units with Electric Preheat)
AV 21238
LA-TEMP-MIN
Low Ambient Minimum Temp (For Frost Control)
AV 10092
UNIT-EN
Unit Enable
MV 25746
OCC-MODE
Occupancy Mode (For TEC series Thermostat)
MV 31996
NOCC-STS
Network Occupancy Status (For BAS)
BV 32004
HTG-EN
Heating Enable Input (From the Thermostat/BAS to turn the GAS heat ON)
BV 21829
HTG2-EN
Heating 2 Enable (For Bacnet Thermostat/BAS)
BV 32024
CLG1-SW-EN
Cooling 1 Software Enable (For Bacnet Thermostat/BAS)
BV 22415
CLG2-SW-EN
Cooling 2 Software Enable (For Bacnet Thermostat/BAS)
BV 22416
TUNING-RESET
PID Tuning Reset
BV 32041
USE-TSTAT-INPUTS
Use Thermostat Inputs (For the units with Thermostat Control)
BV 31930
USE-CO2-MODE
Use CO2 Control Mode Flag
BV 10218
USE-SSJ-MODE
Use Start Stop Jog Mode Flag
BV 10219
USE-LA-MODE
Use Low Ambient Mode Flag
BV 10216
USE-SMOKE-MODE
Use Smoke Control Mode Flag
BV 15295
USE-CLG-MODE
Use Cooling Mode Flag
BV 22433
USE-MOD-HTG
Use Modulating Post Heat Mode Flag
BV 21261
USE-PREHEAT-MODE
Use Pre Heat Mode Flag
BV 21263
USE-MOD-WHEEL
Use Modulating Wheel Mode Flag
BV 22667
USE-FILT-ALM
Use Dirty Filter Indication Mode Flag
BV 23748
USE-STAGED-HTG
Use Staged Post Heat Flag
BV 23879
USE-BYPASS-MODE
Use Bypass Mode Flag
BV 22435
EMG-STANDALONE-HTG
Emergency Standalone Heating Mode Flag
BV 32050
SSJ-MIN-TEMP
Start Stop Jog Min Temperature
AV 10186
SSJ-MAX-TEMP
Start Stop Jog Max Temperature
AV 10187
SSJ-ONTIME
Start Stop Jog Wheel On Time
AV 10184
SSJ-OFFTIME
Start Stop Jog Wheel Off Time
AV 10183
HTG-MINOFF
Gas Heat Minimum Off Time (For 2 stage Gas Heating)
AV 32052
HTG-MINON
Gas Heat Minimum On Time (For 2 stage Gas Heating)
AV 32051
WHL-INTERCEPT
Wheel Intercept
AV 10077
WHL-SLOPE
Wheel Slope
AV 10090
Object Name
Description (Monitoring Points)
Instance Number
EA-FLOW
Exhaust Air Flow (Calculated using differential pressure across the wheel)
AV 10276
SA-FLOW
Supply Air Flow (Calculated using differential pressure across the wheel.)
AV 10277
RA-CO2
Return Air CO2
AI 10008
RA-TEMP
Return Air Temperature (Calculated value using resistance input)
AV 25418
OA-TEMP
Outside Air Temperature (Calculated value using resistance input)
AV 25417
EA-TEMP
Exhaust Air Temperature (Calculated value using resistance input)
AV 25416
SA-TEMP
Supply Air Temperature (Calculated value using resistance input)
AV 25419
SAFLOW-SP
Supply Air Flow Set Point (Validated Set point)
AV 17734
EAFLOW-SP
Exhaust Air Flow Set Point (Validated Set point)
AV 17735
CO2-SP
CO2 Set Point (Validated Set point)
AV 17736
MAX-FLOW
Maximum Flow (Design flow of the unit)
AV 14835
MIN-FLOW
Minimum Flow (Design flow of the unit)
AV 14836
OCC-STS
Occupancy Status (24VAC signal from Thermostat)
BI 17564
ECON-SIG
Economizer Signal (24VAC signal from Thermostat)
BI 22410
AF-STS
Air proving Status
BI 21644
EA-FAN-STS
Exhaust Air Fan Status
BI 17500
SA-FAN-STS
Supply Air Fan Status
BI 17496
MEH-STS
Motorized Exhaust Air Damper Status
BI 17506
MOH-STS
Motorized Outside Air Damper Status
BI 17503
BYP-STS
Bypass Damper Status
BI 24231
Содержание ENERVENT+ EVT-09 Series
Страница 30: ...30 REVT 05ERV UNIT WIRING DIAGRAM ...
Страница 31: ...REVT 05ERV 31 UNIT WIRING DIAGRAM CONTINUED ...
Страница 47: ...REVT 05ERV 47 UNIT WIRING DIAGRAM XVIII WIRING DIAGRAMS ...
Страница 48: ...48 REVT 05ERV UNIT WIRING DIAGRAM CONTINUED ...
Страница 50: ...50 REVT 05ERV Optional Heat Cool Inputs Optional Pre Post Heat ...
Страница 57: ...REVT 05ERV 57 DIAGRAM 15 5 1 MODULATION GAS POST HEAT DIAGRAM 14 2 STAGE GAS POST HEAT ...