Figure 4-25 Grounding Point on the Rear of the RG-S8612E Switch
To guarantee the security of the person and the device, the RG-N18000 must be well-grounded. The grounding resistance shall
be less than 1Ω.
A service person shall check whether or not the socket-outlet from which the equipment is to be powered provides a connection
the building protective earth. If not, the service person shall arrange for the installation of a protective earthing conductor from the
separate protective earthing terminal to the protective earth wire in the building.
The socket-outlet shall be installed near the equipment and shall be easily.
When installing the unit, always make the ground connection first and disconnect it last.
The cross-sectional area of protective earthing conductor shall be at least 2.5 mm
2
(12AWG).