6.2 IEEE 1613 Type Tests
Test
Description
Test Levels
Enclosure Contact
+/- 8kV
IEEE C37.90.3
ESD
Enclosure Air
+/- 15kV
IEEE C37.90.2
Radiated RFI
Enclosure ports
35 V/m
Signal ports
+/- 4kV @ 2.5kHz
D.C. Power ports
+/- 4kV
A.C. Power ports
+/- 4kV
IEEE C37.90.1
Fast Transient
Earth ground ports
+/- 4kV
Signal ports
2.5kV common mode @ 1MHz
D.C. Power ports
2.5kV common & differential mode @ 1MHz
IEEE C37.90.1
Oscillatory
A.C. Power ports
2.5kV common & differential mode @ 1MHz
Signal ports
5 kV (Failsafe Relay)
D.C. Power ports
5 kV
IEEE C37.90
H.V. Impulse
A.C. Power ports
5 kV
Signal ports
2kVac (Failsafe Relay)
D.C. Power ports
2kVac
IEEE C37.90
Dielectric
Strength
A.C. Power ports
2kVac
Table 14 - IEEE 1613 Type Tests
NOTE:
•
If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur
but recovery is automatic).
•
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will
occur).
6.3 IEC Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 deg. C, 16 Hours
N/A
IEC 60068-2-2
Dry Heat
Test Bd
+85 deg. C, 16 Hours
N/A
IEC 60068-2-30
Humidity (Damp Heat,
Cyclic)
Test Db
95% (non-condensing), 55 deg C, 6 cycles
N/A
IEC 60255-21-1
Vibration
Tests Fc
2g @ (10-150) Hz
Class 2
IEC 60255-21-2
Shock
Tests Ea
30g @ 11ms
Class 2
Table 15 - Environmental Type Tests